KRP-C-1600SP Cooper/Bussmann, KRP-C-1600SP Datasheet

FUSE 1600A 600V T-LAG CLASS L

KRP-C-1600SP

Manufacturer Part Number
KRP-C-1600SP
Description
FUSE 1600A 600V T-LAG CLASS L
Manufacturer
Cooper/Bussmann
Series
KRP-Cr
Type
Cylinderr
Datasheet

Specifications of KRP-C-1600SP

Fuse Type
Slow Blow, Time Lag
Voltage - Rated
600VAC, 300VDC
Current
1.6kA
Package / Case
Bolt Mount
Size / Dimension
3.000" Dia x 10.750" L (76.20mm x 273.05mm)
Mounting Type
Bolt Mount
Acting
Slow Blow
Voltage Rating (vac)
600V
Voltage Rating (vdc)
300V
Current Rating
1600A
Mounting
Screw
Product Depth (mm)
Not Requiredmm
Product Height (mm)
Not Requiredmm
Housing Material
Glass Melamine
Voltage Rating
600 VoltsAC / 300 VoltsDC
Fuse Size / Group
Class L
Termination Style
Blade
Body Material
Glass Melamine
Dimensions
10 3/4 in L x 3 1/2 in W
Product
Industrial Power Fuse
Interrupt Rating
300 KAmps
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Operating Temperature
-
Color
-
Lead Free Status / Rohs Status
 Details
Catalog Symbol: KRP-C_SP
Time-Delay – 4 seconds (minimum) at 500% rated current
Current-Limiting
Ampere Rating: 2001 to 6000 Amperes
Voltage Rating: 600 Volts AC (or less)*
Interrupting Rating: 300,000A RMS Sym. (UL)
Agency Approvals:
UL Listed – Special Purpose £ , Guide JFHR, File E56412
CSA Certified (200,000 AIR), Class 1422-02, File 53787
*601-3000A is rated 340 VDC and 50 KAIC.
£Meets all performance requirements of UL Standard 248-10 for Class L fuses.
Ampere Ratings†
KRP-C-2001SP
KRP-C-2400SP
KRP-C-2500SP
KRP-C-3000SP
KRP-C-3500SP
KRP-C-3800SP
KRP-C-4000SP
**
LOW-PEAK
Class L – 600 Volt
A99119
11-12-99
†Special purpose rating of 300,000 AIR.
Class L per CSA-C22.2 No. 248.10
Weight per carton.
Catalog
Number
Rev. A
Ctn.
Qty. Lbs.
1
1
1
17.25 7.824
18.25 8.278
23.50 10.659
Weight**
Kg.
®
Time-Delay Fuses
KRP-C-4500SP
KRP-C-5000SP
KRP-C-6000SP
Catalog
Number
Ctn.
Qty.
1
1
Dimensional Data
Lbs.
29
36
Weight**
5.03" Max.
1.75"
2001A
2500A
3.5"
13.154
16.329
.75"
to
5"
.88"
Kg.
5.03" Max.
General Information:
• All purpose silver-linked fuse for both overload and short-circuit
• Time-delay (minimum of four seconds at five times amp rating)
• Current-limiting action of the fuse generally affords consider-
• Interrupting rating of 300,000 amperes complies with NEC
• O-ring seals maximize pressure build-up during current-limiting
• High grade silica-sand filler; accelerates response of fuse to
• 99.9% pure silver fuselinks. The high conductivity of silver gives
• Selective coordination (blackout prevention)
• Glass melamine tube.
• Silver-plated end bells.
3000A
.81"
.75"
4"
5"
protection for high capacity systems (mains and large feeders).
for close sizing.
able reduction in bus bracing.
Sections 110-9 and 230-65 for today’s large capacity systems.
action and ensure filler retention.
short-circuits by having quenching effect upon the fuse arc.
low watt loss and low operating temperature at normal current
levels; maximizes total clearing I
(50-1000 VAC, 75-1500 VDC). Refer to BIF document #8002 or contact
Bussmann Application Engineering at 636-527-1270 for more information.
1.38"
CE logo denotes compliance with European Union Low Voltage Directive
5.79" Max.
3500A
4000A
5.75"
4.75"
.75"
to
1.75"
1.63"
7.17" Max.
4500A
5000A
6.25"
5.25"
1"
to
.88"
2
1.38"
t fault energy let-through.
Hole diameters and slot widths (±0.03)
7.17" Max.
1"
6000A
7.13"
5.75"
2001-6000A
Form No. KRP-C 2001-6000
All other tolerances (± 0.02)
Bussmann
3.75"
Terminals:
Width ( 0.06)
Thickness ( 0.03)
KRP-C
6.75"
BIF Doc #1009
Page 1 of 3
( 0.09)
10.75"
®

Related parts for KRP-C-1600SP

KRP-C-1600SP Summary of contents

Page 1

... All other tolerances (± 0.02) 1.63" 1.38" .88" 6.75" 4500A 3.75" to 6000A 10.75" 5000A ( 0.09) 1" 1" Terminals: Width ( 0.06) Thickness ( 0.03) 5.25" 5.75" 6.25" 7.13" 7.17" Max. 7.17" Max. t fault energy let-through. 2 Form No. KRP-C 2001-6000 Page BIF Doc #1009 ® ...

Page 2

... LOW-PEAK ® Time-Delay Fuses Class L – 600 Volt Time-Current Characteristic Curves–Average Melt 300 100 .01 11-12-99 A99119 Rev. A AMPERE RATING CURRENT IN AMPERES Bussmann ® KRP-C 2001-6000A Form No. KRP-C 2001-6000 Page BIF Doc #1009 ...

Page 3

... Bussmann also reserves the right to change or update, without notice, any technical informa- tion contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications. 11-12-99 A99119 Rev. A Bussmann ® KRP-C 2001-6000A Form No. KRP-C 2001-6000 Page BIF Doc #1009 ...

Related keywords