861HSSR210-AC-1 Magnecraft / Schneider Electric, 861HSSR210-AC-1 Datasheet

Solid State Relays SPST-NO 24 to 280 VAC

861HSSR210-AC-1

Manufacturer Part Number
861HSSR210-AC-1
Description
Solid State Relays SPST-NO 24 to 280 VAC
Manufacturer
Magnecraft / Schneider Electric
Datasheet

Specifications of 861HSSR210-AC-1

Control Voltage Range
24 VAC to 280 VAC
Load Voltage Rating
24 VAC to 600 VAC
Off State Leakage Current (max)
10 mA
Load Current Rating
10 A
Contact Form
SPST - NO
Output Device
SCR
Case Color
White
Relay Type
Solid State
Turn-on Switching
DC Switching
Termination Style
Screw
Control Voltage Type
AC
Operating Voltage Range
24VAC To 280VAC
Peak Surge Current
500A
Contact Configuration
SPST-NO
Load Current
10A
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Lead Free Status / RoHS Status
Lead free / RoHS Compliant, Lead free / RoHS Compliant
861H Class 1, Division 2 Certified Solid State Relay
GENERAL SPECIFICATIONS
File No. E317746
OUTPUT CHARACTERISTICS
Switching Device
Switching Type
Switching Configuration
Load Voltage Range
Resistive Load Rating (Arms)
Maximum Zero Turn-On Voltage (Vpk)
Maximum Rate of Rise Off State Voltage (dv/dt)
Incandescent Lamp Rating (Arms)
Motor Load Rating (Arms)
Minimum Load Current to Maintain On
Non-Repetitive Surge Current (1 cycle)
Maximum Rms Overload Current (1 second)
Maximum Off State Leakage Current on Output (Rms)
Typical On State Voltage Drop on Output (Rms)
Maximum On State Voltage Drop on output (Rms)
Maximum I
INPUT CHARACTERISTICS
Input Voltage
Must Release Voltage
Nominal Input Impedance
Typical Input Current @ 5 VDC
Reverse Polarity Protection on Input
Input Indication
PERFORMANCE CHARACTERISTICS
Maximum Turn-On/Turn-Off Time
Dielectric Strength (Input to Output)
Dielectric Strength (Terminals to Chassis)
ENVIRONMENT
Ambient Air Temperature
Around the Device
Safety Cover
MISCELLANEOUS CHARACTERISTICS
Thermal Resistance J to C Tj=125ºC ºC/W
Integral Heat Sink ºC/W
Maximum Terminal Wire Capacity
Maximum Terminal Screw Torque
Weight
2
t for Fusing (A
IEC 60947-1
2
sec.)
Operation
Storage
861HSSR***-DD
MOSFET
DC switching
SPST-NO
3 up to 150 VDC
8 and 15 A
N/A
N/A
N/A
N/A
20 mA
35 to 50 A
17 to 24 A
10 mA
1.25 VDC
1.6 VDC
N/A
3.5 to 32 VDC
1 VDC
Current Regulator
12 mA
Active Current Limiter
Green LED
5 ms
2500 Vrms
2500 Vrms
-30 to 80 ºC
-40 to 100 ºC
IP20
1.4 ºC/W
4.0 ºC/W
14 AWG (2.5 mm
7.1 lb-in (0.8 Nm)
4.1 oz (127.1 g)
2
)
861HSSR***-AC-1
SCR (2)
Zero cross
SPST-NO
24 up to 600 VAC
10 A
35 Vpk
200 to 500 V/uS
8 A
4.5 A
50 mA
500 A
24 A
10 mA
1.25 VDC
1.6 VDC
600 to 1250
90 to 280 VAC
10 VAC
16-25 Kohms
12 mA
N/A
Green LED
8.3 ms
4000 Vrms
2500 Vrms
-30 to 80 ºC
-40 to 100 ºC
IP20
0.66 ºC/W
4.0 ºC/W
14 AWG (2.5 mm
7.1 lb-in (0.8 Nm)
4.1 oz (127.1 g)
2
)
861HSSR***-DC-1
SCR (2)
Zero cross
SPST-NO
24 up to 600 VAC
10 A
N/A
350 to 500 V/uS
8 A
4.5 A
50 mA
500 A
24 A
10 mA
1.25 VDC
1.6 VDC
600 to 1250
3 to 32 VDC
1 VDC
Current Regulator
16 mA
Active Current Limiter
Green LED
5 ms
2500 Vrms
2500 Vrms
-30 to 80 ºC
-40 to 100 ºC
IP20
0.66 ºC/W
4.0 ºC/W
14 AWG (2.5 mm
7.1 lb-in (0.8 Nm)
4.1 oz (127.1 g)
Class 1, Division 2 certification
for use in hazardous locations
2
)
PART NUMBER EXPLANATION
Series:
Output Type:
Output Voltage:
Output Current:
Input Voltage:
Contact Configuration & Switching Type:
861H
SSR = SCR
SSR = MOSFET (DD Only)
SSRA = Alternistor Triac
1 = 3 to 50 VDC
2 = 24 to 280 VAC
2 = 3 to 150 VDC (DD Only)
4 = 48 to 480 VAC
6 = 48 to 600 VAC
08 = 8 Amps
10 = 10 Amps
15 = 15 Amps
AC = 90 to 280 VAC
DC = 3 to 32 VDC
DD = 3.5 to 32 VDC
1 = SPST-NO, Zero Cross
2 = SPST-NO, Random
4 = SPST-NC, Random
Null = SPST-NO, DC Switching
Document No. 400SP02-0709
www.magnecraft.com
©2009 SE Relays LLC.

Related parts for 861HSSR210-AC-1

861HSSR210-AC-1 Summary of contents

Page 1

... Class 1, Division 2 Certified Solid State Relay GENERAL SPECIFICATIONS File No. E317746 IEC 60947-1 OUTPUT CHARACTERISTICS 861HSSR***-DD Switching Device MOSFET Switching Type DC switching Switching Configuration SPST-NO Load Voltage Range 150 VDC Resistive Load Rating (Arms) 8 and 15 A Maximum Zero Turn-On Voltage (Vpk) ...

Page 2

... MAX (65.0) 0.23 (6.0) 0.065 (1.65) INPUT POWER SUPPLY + 3.6 1.4 (92.4) (35.6) 1.4 (35.2) 0.56 0.1 (14.3) (3.4) A minimum spacing of 17.5 mm between relays is required in order to acheive 16 15 0.62 14 (15. 0.55 10 (14. www.magnecraft.com WIRING DIAGRAM ...

Related keywords