5600310 Phoenix Contact, 5600310 Datasheet

Circuit Breakers TMC 42-01-15A

5600310

Manufacturer Part Number
5600310
Description
Circuit Breakers TMC 42-01-15A
Manufacturer
Phoenix Contact
Series
TMCr
Type
Thermal/Magneticr
Datasheet

Specifications of 5600310

Product Type
Circuit Breakers
Current Rating
15 Amps
Voltage Rating
250 VoltsAC / 80 VoltsDC
Mounting Style
DIN Rail
Termination Style
Screw
Circuit Function
ON/OFF
Color
Black
Features
Narrow Profile Housing, Recessed Terminals, DIN Rail Mounting and Precision CBE Performance
Height
53 mm
Illuminated
No
Length
80 mm
Product
Thermal Magnetic Circuit Breakers
Width
25 mm
Number Of Poles
1 Pole
Actuator Type
Pushbutton
Brand/series
TMC Series
Characteristic
Medium Delay
Current, Rating
15 A
Dimensions
80mmLx12.5mmWx69mmH
Mounting Type
DIN Rail
Phoenix Part Number
TMC 42-01-15A
Termination
Screw
Voltage, Rating
250/80 VAC/VDC
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Thermal-Magnetic Circuit Breaker | TMC 42-01/42-02
Single pole thermal-magnetic circuit breaker with tease-free, triple-free, snap action mechanism
and two button operation (M-type TMCBE to IEC 934). Featuring a narrow profile housing,
recessed terminals, standard DIN-rail mounting and precision CBE performance.
Typical Applications
Circuit protection for process control systems, equpiment manufacturers and instrumentation.
Approvals
Label Slot
ZB6 Marking System
6
Authority
VDE, Demko
UL 1077, CSA
ABS, BV, LRoS
Technical Data
Maximum Voltage Rating
Current Rating Range
Typical Life
Temperature Range
Creepage Resistance
Insulation Co-ordination
(IEC 664 and 664A)
Operating Area
Dielectric Strength
(IEC 664 and 664A)
Operating Area
Insulation Resistance
Interrupting Capacity
(VDE 0660, Part 101, P-2)
Interrupting Capacity
(UL 1077/EN60934 PC1)
Environmental Protection
(IEC 529/DIN 40050)
Vibration
Shock
Corrosion
Humidity
Weight
Conductor Size
Recommended Torque
C-Rail Adapter
Voltage Ratings
AC 250 V, DC 65 V
AC 250 V, DC 80 V
AC 250 V, DC 65 V
AC 250 V, 50/60 Hz; DC 80 V
42-01 : 0.10...16 A
5,000 operations at 2xl
0° to 55°C (+32° to +131°F)
PTI 600 to IEC 112
Rated Impulse Withstand Voltage Pollution Degree
4k V
Test Voltage
AC 4,000 V (double insulation)
>100 MΩ (DC 500 V)
0.05 to 0.8 A
1 to 2 A
2.5 to 16 A
I
0.05 to 4.5 A
0.05 to 16 A
0.05 to 16 A
Operating Area IP 40,Terminal Area IP 20
5g (57-50 Hz), +0.38 mm (10-57 Hz) to IEC 68-2-6,
Test Fc 10 frequency cycles/axis
25g (11ms) to IEC 68-2-27,Test Ea
96 hours at 5% saltspray to IEC 68-2-11,Test Ka
240 hours at 95% RH to IEC 68-2-3,Test Ca
Approx. 60g
0.5-6mm
0.8 Nm max
5650505
N
2
(AWG 20-AWG 10)
Self Limiting
200 A
400 A
U
250 V AC
250 V AC
80 V DC
N
N
Current Ratings
0.10 to 16 A
0.10 to 16 A
0.3 to 16 A
3
Self Limiting
200 A
1,000 A
1,000 A
Dimensions
Single Pole
Double Pole
Internal Wiring Diagram
Internal Wiring Diagram
Standard current ratings and typical internal resistance values
Typical time/current characteristics at 23°C
Visit www.phoenixcon.com to view our selection of power outlets.
Thermal-Magnetic Circuit Breakers
Ohms
* Indicates breakers that are made-to-order and may require an 8 week lead time.
131.00
<0.02
<0.02
<0.02
<0.02
<0.02
<0.02
<0.02
40.00
19.30
10.40
7.10
4.30
2.50
1.67
1.22
0.61
0.55
0.38
0.24
0.19
0.16
0.09
0.09
0.06
0.07
0.04
0.04
0.03
0.02
0.02
Current Rating
10.00
11.00
12.00
13.00
14.00
15.00
16.00
0.10
0.20
0.30
0.40
0.50
0.60
0.80
1.00
1.22
1.50
1.80
2.00
2.50
3.00
3.50
4.00
4.50
5.00
5.50
6.00
6.50
7.00
8.00
9.00
Type
TMC42-01-0.1 A
TMC42-01-0.2 A
TMC42-01-0.3 A
TMC42-01-0.4 A
TMC42-01-0.5 A
TMC42-01-0.6 A
TMC42-01-0.8 A
TMC42-01-1.0 A
TMC42-01-1.2 A
TMC42-01-1.5 A
TMC42-01-1.8 A
TMC42-01-2.0 A
TMC42-01-2.5 A
TMC42-01-3.0 A
TMC42-01-3.5 A
TMC42-01-4.0 A
TMC42-01-4.5 A
TMC42-01-5.0 A
TMC42-01-5.5 A
TMC42-01-6.0 A
TMC42-01-6.5 A
TMC42-01-7.0 A
TMC42-01-8.0 A
TMC42-01-9.0 A
TMC42-01-10 A
TMC42-01-11 A
TMC42-01-12 A
TMC42-01-13 A
TMC42-01-14 A
TMC42-01-15 A
TMC42-01-16 A
TMC 42-01 Single Pole
Direct Current – Magnetic tripping currents are
increased by 30% in DC circuits with the effect
of shifting the magnetic trip range 30% to the
right of AC trip curves.
The time/current characteristic curve depends on the ambient temperature prevailing.
In order to eliminate nuisance tripping, please multiply the circuit breaker current
ratings by the derating factor shown below.
Ambient temperature
Derating factor
Part#
5530915*
5650102
5650103*
5530944*
5650106
5530960*
5530986*
5650108
5531008*
5650109
5650110*
5600314
5650113*
5650114
5531053*
5531066
5650115*
5531082
5531095*
5531105
5650116*
5650117*
5650120
5531147*
5650121
5531163*
5650122*
5531189*
5531192*
5600310
5531202
°F -22
°C -30
0.76
-20
-4
0.79
Type
TMC42-02-0.1 A
TMC42-02-0.2 A
TMC42-02-0.3 A
TMC42-02-0.4 A
TMC42-02-0.5 A
TMC42-02-0.6 A
TMC42-02-0.8 A
TMC42-02-1.0 A
TMC42-02-1.2 A
TMC42-02-1.5 A
TMC42-02-1.8 A
TMC42-02-2.0 A
TMC42-02-2.5 A
TMC42-02-3.0 A
TMC42-02-3.5 A
TMC42-02-4.0 A
TMC42-02-4.5 A
TMC42-02-5.0 A
TMC42-02-5.5 A
TMC42-02-6.0 A
TMC42-02-6.5 A
TMC42-02-7.0 A
TMC42-02-8.0 A
TMC42-02-9.0 A
TMC42-02-10 A
TMC42-02-11 A
TMC42-02-12 A
TMC42-02-13 A
TMC42-02-14 A
TMC42-02-15 A
TMC42-02-16 A
-10
14
0.83
TMC 42-02 Double Pole
32
0
0.88
73.4
23
1
104
40
1.08
122
Part #
5650123*
5650124*
5650127*
5531244*
5531257*
5531260*
5531286*
5531299
5531309*
5650129*
5531325*
5531388
5650130*
5650131
5531367*
5650134*
5650135*
5651396
5531406*
5650136*
5650137*
5531435*
5650138*
5531451*
5531464
5531477*
5650141*
5531493*
5531503*
5600309
5650142*
50
1.16
140
60
1.24
7

Related parts for 5600310