4304.4022 Schurter Inc, 4304.4022 Datasheet

Power Entry Modules w/Fuseholder and Switch 250 VAC 2A

4304.4022

Manufacturer Part Number
4304.4022
Description
Power Entry Modules w/Fuseholder and Switch 250 VAC 2A
Manufacturer
Schurter Inc
Type
Filter/Fuse/Switchr
Datasheets

Specifications of 4304.4022

Filtered
Yes
Filter Type
Standard and Medical
Product
Modules
Current Rating
2 A
Voltage Rating
250 V
Housing Material
Thermoplastic
Mounting Style
Screw
Operating Temperature Range
- 25 C to + 85 C
Flammability Rating
UL 94 V-0
Termination Style
Quick Connect
Connector Type
IEC-320 C-14
Capacitance, Cx
68
Capacitance, Cy
2.2
Current, Leakage
<0.25 mA
Current, Rating
2 A
Cut Out, Panel
29.5×61 mm
Dielectric Strength
>1.7 kVDC (L-N), >2.7 kVDC (L/N-PE)
Gender
Male
Inductance
2×4 mH
Material, Housing
Thermoplastic
Mount Method
Front
Mounting Type
Panel/Screw-On
Number Of Poles
2
Resistance
1 Megohms
Temperature, Operating
-25 to +85 °C
Termination
Quick Connect
Thickness, Panel
8 mm
Version
Standard
Voltage, Rating
125 VAC (UL/CSA), 250 VAC (IEC)
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Power Entry Modules with Line Filter
Description
- Panel Mount:
Screw-on mounting from front side
- 4 Functions:
Appliance Inlet Protection class I, Line Switch 2-pole, Fuseholder for
- Quick connect terminals 6.3 x 0.8 mm
Approvals
- VDE Certificate Number: 40004665
- UL File Number: E72928
Technical Data
Ratings IEC
Ratings UL/CSA
Leakage Current
Dielectric Strength
Allowable Operation Temp.
Climatic Category
Degree of Protection
Protection Class
Terminal
Panel Thickness s
Material: Housing
Aluminum
IEC Appliance Inlet C14 with Filter, Fuseholder 2-pole, Line Switch 2-pole
fuse-links 5 x 20 mm 2-pole, Line filter in standard and medical version
70° C
C14
1 - 10 A @ Ta 40 °C / 250 VAC; 50 Hz
1 - 10 A @ Ta 40 °C / 125 VAC; 60 Hz
standard < 0.25 mA (250 V / 60 Hz)
medical < 5 µA (250 V / 60 Hz)
> 1.7 kVDC between L-N
> 2.7 kVDC between L/N-PE
Test voltage (2 sec)
-25 °C to 85 °C
25/085/21 acc. to IEC 60068-1
from front side IP 40 acc. to IEC 60529
Suitable for appliances with protection
class 1 acc. to IEC 61140
Quick connect terminals 6.3 x 0.8 mm
Screw: max 8 mm
Mounting screw torque max 0.5 Nm
Thermoplastic, black, UL 94V-0
Nickel plated steel
EMC Products
Characteristics
- Compact design with optimal shielding
- All single elements are already wired
- Plug removal necessary for fuse-link replacement
If the power entry module is installed as normal, it is not possible to
Fuse drawer meets requirements of medical standard IEC/EN 60601-1
The fuseholder is accessible from the equipment front
- With EMC-shield
- Qualified for use in equipment according IEC/EN 60950
Other versions on request
- Medical version M80
References
Weblinks
General Product Information, Approvals, RoHS, CHINA-RoHS, Mating
Connectors, e-Store, SCHURTER-Stock-Check, Distributor-Stock-
Check, Accessories
Appliance-Inlet/-Outlet
Fuseholder
Rated Power Acceptance @
Ta 23 °C
Power Acceptance @ Ta >
23°C
Line Switch
Line Filter
MTBF
touch any live parts with the test-finger according to IEC60529
www.schurter.com/pg06
C14 acc. to IEC/EN 60320-1,
UL 498, CSA C22.2 no. 42 (for cold
conditions) pin-temperature 70 °C, 10 A,
Protection Class 1
2-pole, Shocksafe category PC2 acc. to
IEC 60127-6,
for fuse-links 5 x 20 mm
5 x 20: 1.6 W (2-pole)
Admissible power acceptance at hig-
her ambient temperature see derating
curves
Rocker switch 2-pole, non-illuminated,
acc. to IEC 61058-1
Technical details
Standard and Medical Version, IEC
60939, IEC 60601-1, UL 1283, UL 544,
EN 133 200, CSA C22.2 no. 8
Technical details
> 1'700'000 h acc. to MIL-HB-217 F
Standard- or Medical-Filter
FKI


Related parts for 4304.4022

4304.4022 Summary of contents

Page 1

Power Entry Modules with Line Filter IEC Appliance Inlet C14 with Filter, Fuseholder 2-pole, Line Switch 2-pole Aluminum C14 70° C Description - Panel Mount: Screw-on mounting from front side - 4 Functions: Appliance Inlet Protection class I, Line Switch 2-pole, Fuseholder for fuse-links 2-pole, Line filter in standard and medical version - Quick connect terminals 6.3 x 0.8 mm Approvals - VDE Certificate Number: 40004665 - UL File Number: E72928 Technical Data Ratings IEC °C / 250 VAC Ratings UL/CSA °C / 125 VAC Leakage Current standard < 0.25 mA (250 Hz) medical < 5 µA (250 Hz) ...

Page 2

FKI www.schurter.com/pg06 Dimensions Case ±0.5 ±0.5 Case ±0.5 ±0.5 Technical Data of Filter-Components Rated Current Filter-Type [A] 1 Standard Version 2 Standard Version 4 Standard Version 6 Standard ...

Page 3

Power Entry Modules with Line Filter Diagrams Standard version Medical version Line 1) Line 2) only FKI 2) Load 3) Load Derating Curves 2-pole 1.6 1.4 1 1 ...

Page 4

... EMC Products Power Entry Modules with Line Filter Comment Order Number - 4304.4061 - 4304.4062 - 4304.4063 - 4304.4064 - 4304.4065 - 4304.4091 - 4304.4092 - 4304.4092 - 4304.4094 - 4304.4095 - 4304.4021 - 4304.4022 - 4304.4023 - 4304.4024 - 4304.4025 - 4304.4066 - 4304.4067 - 4304.4068 - 4304.4069 - 4304.4070 0859.0074 4787 4788 5091 5092 0101 0102 0102-G 0112 4012 ...

Page 5

Power Entry Modules with Line Filter Category / Description Power CordOverview complete Power Cord with IEC Connector C13, Angled Power Cord with IEC Connector C13, Angled Power Cord with IEC Connector C13, Angled Power Cord with IEC Connector C13, Angled ...

Related keywords