DLP-THS-H DLP Design Inc, DLP-THS-H Datasheet

Industrial Humidity Sensors TEMP/HUMIDITY SENSOR

DLP-THS-H

Manufacturer Part Number
DLP-THS-H
Description
Industrial Humidity Sensors TEMP/HUMIDITY SENSOR
Manufacturer
DLP Design Inc
Datasheet

Specifications of DLP-THS-H

Rh Range
0 % to 100 %
Rh Accuracy
+/- 3 % to +/- 5 %
1.0 INTRODUCTION
The DLP-UTH8 is a low-cost, easy-to-use active hub used for connecting multiple temperature and
humidity sensors to one PC featuring 4
taken from the host PC via the USB port. The temperature and humidity sensor modules (shown
below) connect to the DLP-UTH8 using standard Cat-5 intranet cable.
The software running in the hub continuously checks all ports for the presence of sensor modules and
automatically reads the data from all connected sensors. The most current data is held in memory
until requested by the host PC.
2.0 SPECIFICATIONS
The DLP-UTH8 is compatible with two sensor modules: the DLP-THS-T and DLP-THS-H. The
specifications for each module are shown here.
Module
Temperature
Humidity
Accuracy (T)
Accuracy (H)
Rev. 1.4 (August 2008)
8-CHANNEL DATA COLLECTION HUB
DLP-THS-T
(Temperature Only)
-55 to 125°C (-67 to 257°F)
±0.5°C (-10 to 85°C)
th
generation USB silicon from FTDI. All operational power is
1
DLP-THS-H
(Temperature and Humidity)
-40 to 123.8°C (-40 to 254.9°F)
0 to 100% RH
±2.0°C (-30 to 80°C)
±3%RH (20 to 80%), ±5%RH (0 to 100%)
D
D
LEAD-FREE
L
L
P
P
© DLP Design, Inc.
-
-
U
U
T
T
H
H
8
8

Related parts for DLP-THS-H

DLP-THS-H Summary of contents

Page 1

... The most current data is held in memory until requested by the host PC. 2.0 SPECIFICATIONS The DLP-UTH8 is compatible with two sensor modules: the DLP-THS-T and DLP-THS-H. The specifications for each module are shown here. Module DLP-THS-T ...

Page 2

... Begin by opening the COM port, set the baud rate to 9600 (1 start bit, no parity, 8 data bits, 1 stop bit), and send single-byte commands as shown below. The Ping command can be used to locate the correct COM port to be used for communicating with the DLP-UTH8, or you can look in Device Manager to see which port Windows has assigned to the DLP-UTH8. ...

Page 3

... Return CH8 humidity data 6.0 RETURN DATA TYPES By default, the DLP-UTH8 returns data to the host PC in the form of ASCII text such that it can be easily displayed using a simple terminal emulator. Alternatively, data can be returned in binary form requiring the user’s host application to calculate the current temperature. ...

Page 4

... LSByte | (MSByte << 8); tempC = (float)(( -40.00 + (0.01 * (double)degc))); rhlin = -4.0 + (.0405*(float)hum_temp) + (-2.8e-6*(float)hum_temp*(float)hum_temp); rhtrue = (tempC - 25.0) * (.01 + .00008 * hum_temp) + rhlin; return rhtrue; } Rev. 1.4 (August 2008) 4 © DLP Design, Inc. ...

Page 5

... This product and its documentation are supplied on an as-is basis, and no warranty as to their suitability for any particular purpose is either made or implied. DLP Design, Inc. will not accept any claim for damages whatsoever arising as a result of the use or failure of this product. Your statutory rights are not affected ...

Page 6

Vss VDD 6 Vss VDD VDDCORE AGND 33 7 GND 18 GND 28 21 GND 7 26 TEST 23 2 GND 4 VCCIO ...