S3K1000 SOLA HEVI DUTY, S3K1000 Datasheet

UPS - Uninterruptible Power Supplies 1000VA/750W 120V

S3K1000

Manufacturer Part Number
S3K1000
Description
UPS - Uninterruptible Power Supplies 1000VA/750W 120V
Manufacturer
SOLA HEVI DUTY
Type
Industrial, Networkr
Datasheet

Specifications of S3K1000

Power Rating
1000 VA
Output Voltage Rating
120 V
Number Of Outlets
4
Interface Port
USB
Runtime (full Load)
4 min
Runtime (half Load)
13 min
Topology
Line Interactive
Tower / Rackmount
Tower
Capacity (va / W)
1000VA / 750W
No. Of Outlets
4
Input Voltage
103V AC To 132V AC
Output Voltage
120V
Backup Time - Full Load
4min
Length
436mm
Width
140mm
Height
210mm
Weight
37lb
Output Type
Variable
Battery Type
Valve-Regulated, Non-Spillable, Lead Acid
Brand/series
S3K Series
Capacity
1000 VA
Communication
RS232
Dimensions
210 H × 140 W × 436 D mm
Frequency, Output
50⁄60 Hz
Input Type
NEMA 5-15P
Length, Cord
6 ft.
Mounting Type
Rack/Tower
Operation
Line-Interactive
Power, Rating
480 W
Standards
cULus Listed
Temperature, Operating
0 to +40 °C
Time, Backup
4 min.
Voltage, Battery
12 V
Voltage, Input
103 to 132
Voltage, Output
120 VAC
Voltage, Supply
480/700 W/VA
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Lead Free Status / RoHS Status
Lead free / RoHS Compliant, na
S3K Mini-Tower Line-Interactive UPS
The S3K is an economical choice for those applications
requiring the performance of a sinewave output, line interac-
tive UPS with the mini-tower shape for cabinet installations.
The S3K Series protects against most severe power
disturbances through state-of-the-art, line-interactive
technology. Most power disturbance corrections are ac-
complished without transferring to the internal battery. Utility
power is continually protected by the S3K Series UPS’s and
internal battery life is optimized.
The UPS has built in protection for under and over voltage
conditions including low-energy lightning surges introduced
on the input power source. All S3K Series UPS are provided
with an input circuit protector and surge protected data line
connectors. The S3K Series UPS’s are provided with a bat-
tery test function. Should the battery fail this test, the UPS
will display a warning to indicate that the battery needs to be
replaced.
Features
Selection Table
* Full/Half Load (in minutes).
66
• Mini-Tower design for control cabinet installation.
• Automatic Voltage Regulation (AVR) topology saves
• Sine wave output
• User replaceable, "hot swappable" batteries
• RS-232 Communications port
• Built-in surge protection
• Cold start capability (DC power on)
• Telephone/Modem spike protection
• Power Management software is included (UPSMON).
• 50/60 Hz auto sensing
• Fully digitized, microprocessor controlled
• Protects against most adverse power conditions
• Two Year Limited Warranty
1440/1200
1000/750
700/480
Capacity
battery power for deep voltage sag situations.
(Downtime for battery replacement not required).
including:
(VA/W)
- Frequency variations
- Sags
- Blackouts
S3K700
S3K1000
S3K1600
Number
Catalog
120/120, 50/60 Hz
120/120, 50/60 Hz
120/120, 50/60 Hz
Volts, Frequency
- Surge
- Spike
- Over and under voltages
Uninterruptible Power Systems
(In/Out)
contact Technical Services at (800) 377-4384 with any questions.
Visit our website at www.solaheviduty.com or
Typical Back-up
Time (minutes)*
5/14
4/13
3/10
Applications
Related Products
Battery Back-up Times Chart
Note:
Back-up times are at 25
• Workstations
• PLCs
• Robotics and Process Control
• Industrial Automation Systems
• Automatic Service & Dispensing Equipment
• Portable MCR Power Conditioners
• Surge Protective Devices
• Active Tracking
Load %
100
20
40
50
70
(Detached) 5-15P / (4)5-15R
(Detached) 5-15P / (4)5-15R
(Attached) 5-15P / (6)5-15R
Input Plug/Output Receptacle
o
C, 77
®
S3K700
Filters
o
F, with 100% capacity batteries and resistive loads.
45
21
14
9
5
S3K1000
37
18
13
Approx. Ship Weight
8
4
34.1 (15.5)
37.0 (16.8)
70.4 (32.0)
lbs (kg)
E179213
S3K1600
27
12
10
6
3

Related parts for S3K1000

S3K1000 Summary of contents

Page 1

... Note: Back-up times are at 25 Typical Back-up Input Plug/Output Receptacle Time (minutes)* 5/14 (Detached) 5-15P / (4)5-15R 4/13 (Detached) 5-15P / (4)5-15R 3/10 (Attached) 5-15P / (6)5-15R Visit our website at www.solaheviduty.com or E179213 Filters ® S3K700 S3K1000 S3K1600 with 100% capacity batteries and resistive loads. ...

Page 2

... Immunity * Note: 1200W at 0.75 power factor equals 1600VA. Line cord limits total load to 1440 VA (max). contact Technical Services at (800) 377-4384 with any questions. Uninterruptible Power Systems S3K700 S3K1000 700/480 1000/750 Dimensions inches (mm) 8.3 x 5.5 x 17.2 (210 x 140 x 436) 11.75 x 10.5 x 19.2 (300 x 265 x 492) 34 ...

Related keywords