FLUKE-i30 Fluke, FLUKE-i30 Datasheet

Clamp Multimeters & Accessories MULTIMETER CURRENT CLAMP

FLUKE-i30

Manufacturer Part Number
FLUKE-i30
Description
Clamp Multimeters & Accessories MULTIMETER CURRENT CLAMP
Manufacturer
Fluke
Datasheet

Specifications of FLUKE-i30

Accuracy
+/- 1 %
Frequency
DC to 20 KHz (- 0.5 dB)
Maximum Ac Current
20 A
Voltage
300 V
Ranging
30 mA to 30 A DC, 30 mA to 20 A AC
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
2584920
Electrical specifications
Specified current range: 30 mA to 30 A DC,
30 mA to 20 A AC rms
Usable current range: 5 mA to 30 A DC,
30 mA to 20 A AC rms
Crest factor: 1.4
Output sensitivity: 100 mV/A
Accuracy (at +25 °C): ± 1 % of reading ± 2 mA
Resolution: ± 1 mA
Load impedance: > 10 k Ohms and ≤ 100 pF
Conductor position sensitivity: ± 1 % relative to
center reading
Frequency range: DC to 20 kHz (- 0.5 dB)
Temperature coefficient: ± 0.01 % of reading/°C
Power supply: 9 V Alkaline, MN1604/PP3,
30 hours, low battery indicator
Working voltage (see Safety Standards section):
300 V ac rms or dc
AC/DC Current Clamp
Fluke i30
General specifications
Maximum conductor size: 19 mm (.748 in)
diameter
Output connection: 4 mm (.157 in) safety
connector
Output zero: Manual adjust via thumbwheel
Cable length: 1.5 m (4.91 ft)
Operating temperature range: 0 °C to +50 °C
(-32 °F to 122 °F)
Storage temperature range (with battery
removed): -20 °C to +85 °C (-4 °F to 185 °F)
Operating humidity: 15 % to 85 %
(non-condensing)
Weight: 250 g (.55 lb)
The i30 current clamp is based
on Hall effect technology for use
in measurement of both dc and
ac current. The i30 may be used
in conjunction with multimeters,
recorders and other suitable
recording instruments for accurate
non-intrusive current measurement.
Technical Data

FLUKE-i30 Summary of contents

Page 1

... Fluke i30 AC/DC Current Clamp Electrical specifications Specified current range DC rms Usable current range DC rms Crest factor: 1.4 Output sensitivity: 100 mV/A Accuracy (at +25 °C): ± reading ± Resolution: ± Load impedance: > Ohms and ≤ 100 pF Conductor position sensitivity: ± relative to center reading Frequency range kHz (- 0 ...