C25BNF230B EATON CUTLER HAMMER, C25BNF230B Datasheet - Page 18

Definite Purpose Contactor

C25BNF230B

Manufacturer Part Number
C25BNF230B
Description
Definite Purpose Contactor
Manufacturer
EATON CUTLER HAMMER
Datasheet

Specifications of C25BNF230B

Load Current Inductive
30A
Load Current Resistive
40A
No. Of Poles
2
Contact Configuration
DPST-NO
Relay Mounting
Panel
Coil Voltage Vac Nom
240V
Contact Voltage Ac Nom
600V
Horsepower
5hp
35
35-18
Overload Relays
These tripping characteristics are the
mean values of the spread at 20°C
ambient temperature in a cold state.
Table 35-49. Overload Relay — Technical Data and Specifications
General
Description
Standards
Climatic Proofing
Ambient Temperature
Temperature Compensation
Mechanical Shock Resistance (IEC/EN 60068-2-27)
Degree of Protection
Protection against Direct Contact when Actuated
from Front (IEC 536)
Insulation Voltage (U i ) VAC
Overvoltage Category /Pollution Degree
Impulse Withstand Voltage (U imp ) VAC
Operational Voltage (U e ) VAC
Safe Isolation to VDE 0106 Part 101 and Part 101/A1
Overload Relay Setting Range
Temperature Compensation Residual Error >20°C (%/K)
Current Heat Loss (3 Conductors)
Terminal Capacity
Solid or Stranded, AWG
Terminal Screw
Tools
Half-sinusoidal Shock 10 mS
Between auxiliary contacts and main contacts (VAC)
Between main contacts (VAC)
Lower value of setting range, W
Upper value of setting range, W
Solid, mm
Flexible with ferrule, mm
Tightening Torque
Pozidrive screwdriver
Standard screwdriver
Ambient temperature operating range to IEC/EN 60947, PTB: -5°C to +50°C.
6 mm
Main contact terminal capacity, solid and stranded conductors with ferrules: When using 2 conductors use identical cross-section.
Nm
Lb-in
Definite Purpose Contactors & Starters
Starters
Overload Relay Specifications
2
flexible with ferrules to DIN 46228.
2
2
Tripping time depends on response
current. With devices at operating tem-
perature, the tripping time of the over-
load relay reduces to approximately
25% of the read off value. Specific
characteristics for each individual
setting range can be found in
MN03402001E.
For more information visit: www.eaton.com
XTOB…CC1
IEC/EN 60947, VDE 0660, UL, CSA
Damp heat, constant, to IEC 60068-2-78;
Damp heat, cyclic, to IEC 60 068-2-30
-25 to 50°C [-13 to 122°F]
Continuous
10g
IP20
Finger and back of hand proof
690
III/3
6000
690
440
440
0.1 – 32A
2.5
6
2 x (1 – 6)
2 x (1 – 4)
2 x (1 – 6)
14-8
M4
1.8
16
Size 2
1 x 6
0.25
Figure 35-8. Tripping Characteristics
XTOB…DC1
IEC/EN 60947, VDE 0660, UL, CSA
Damp heat, constant, to IEC 60068-2-78;
Damp heat, cyclic, to IEC 60 068-2-30
-25 to 50°C [-13 to 122°F]
Continuous
10g
IP20
Finger and back of hand proof
690
III/3
6000
690
440
440
6 – 75A
3
7.5
2 x (1 – 16)
1 x 25
2 x (1 – 10)
14-2
M6
3.5
31
Size 2
1 x 6
0.25
100
0.6
2h
60
40
20
10
40
20
10
6
4
2
1
6
4
2
1
1 1.5 2
2-Phase
3 4
XTOB...CC1,
XTOB...DC1
6 8 10 15 20
3-Phase
CA08102001E
October 2008

Related parts for C25BNF230B