C30CNE20A0 EATON CUTLER HAMMER, C30CNE20A0 Datasheet - Page 20

Lighting Contactor

C30CNE20A0

Manufacturer Part Number
C30CNE20A0
Description
Lighting Contactor
Manufacturer
EATON CUTLER HAMMER
Datasheet

Specifications of C30CNE20A0

No. Of Poles
2
Contact Configuration
DPST-NC
Relay Mounting
DIN Rail
Coil Voltage Vac Nom
120V
Contact Current Max
30A
Mounting Type
DIN Rail
External Height
187.6mm
Continuous Load Current
30A
Operating Voltage
600VAC
Switching Current Ac1
30A
Switching Current Ac3
30A
Load Current Inductive
30A
Contactor Direction
Reversing
Rohs Compliant
No
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
37
37-20
Contents
Description
Product Family Overview . . . . 37-20
C30CN Electrically
CN35 Electrically Held . . . . . . . 37-24
A202 Magnetically
Combination . . . . . . . . . . . . . . . 37-28
Wiring Diagrams. . . . . . . . . . . . 37-29
Product Description
Eaton’s Cutler-Hammer
Contactors are designed to provide
a safe, convenient means for local
or remote switching of tungsten
(incandescent filament) or ballast
(fluorescent and mercury arc) lamp
loads. They are also suitable for other
loads such as low pressure and high
pressure sodium lamp loads and other
non-motor (resistive) loads. They are
not recommended for most sign
flashing loads.
These lighting contactors are designed
to withstand the large initial inrush
currents of tungsten lamp loads with-
out contact welding. They are fully
rated and do not require derating.
Application Description
Loads:
Ballast Lamps — Fluorescent, Mercury
Vapor, Metal Halide Sodium Vapor,
Quartz — 600V maximum.
Filament Lamps — Incandescent,
Infrared, Heating — 480V maximum,
line to line; 277V maximum line to
neutral.
Resistance Heating — Radiant and
convection heating, furnaces and
ovens.
Standards and Certifications
Note: See P03300001E for additional infor-
mation on Standards and Certifications that
apply to all Cutler-Hammer Enclosed Control
products.
and Mechanically Held . . . . . 37-23
Latched . . . . . . . . . . . . . . . . . 37-26
UL Listed
cUL Listed
ABS Type Approved
Cover Control . . . . . . . . . . . 37-22
Catalog Number
Lighting Contactors
UL Rated AC — Enclosed
Product Family Overview
Selection . . . . . . . . . . . . . . 37-21
®
Lighting
Page
Accessories
Auxiliary Contacts
C30CN Electrically Held Contactors — The base C30CN product line can accept up
to four auxiliary contacts (2NO/2NC), which are mounted on the top of the unit.
The auxiliary contacts, rated A600, are also suitable for use on low-level circuits
down to 12V, 5 mA.
CN35 Electrically Held Contactors — Include a NO maintaining auxiliary contact
mounted on the right side of the contactor. The 10 – 60A devices will accept addi-
tional auxiliary contacts on the top (front) and/or sides. The 100 – 400A sizes will
accept side mounted auxiliaries only.
Mechanically Held and Magnetically Latched — Holding circuit auxiliary contact, if
needed, is not included and should be added separately as an option.
Power Poles for C30CN
The C30CN can be configured with up
to 12 poles (30A maximum per pole).
Power poles are available in single or
double pole designs and can be
mounted to provide either normally
open or normally closed operation
with a maximum of 12 NO poles or 8
NC and 4 NO poles. Each pole is capa-
ble of accepting up to 8 AWG wire.
2-Wire or 3-Wire Control Module
for C30CN
A mechanical latch with a 2- or 3-wire
electronic control module delivers reli-
able performance and protection from
such application abnormalities as line
noise, leakage currents from controller
outputs, or short repetitive commands
burst from faulty controllers. For
Enclosed Control, units come standard
with 2-wire control.
IMPORTANT: Add the C18 Modification
code to get 3-wire control with the
C30CN contactor.
Table 37-42. Type 1 2-Wire Control Relay
Description
2-Wire
Control Relay
For more information visit: www.eaton.com
Magnetic
Coil
Voltage
120
208
240
277
480
Type 1
Catalog
Number
ECLC201A
ECLC201E
ECLC201B
ECLC201H
ECLC201C
Price
U.S. $
Mechanically Held Kit for C30CN
A modification kit allows the conver-
sion of an electrically held lighting
contactor into a mechanically held
contactor.
Coil Kits for C30CN
The C30CN line comes in a wide range
of input voltages and with coils from
24V AC to 600V AC.
2-Wire Control Relay for A202
The 2-wire control relay is designed
to field convert 3-wire magnetically
latched lighting contactors to operate
controls such as photocells and timers.
Terminal blocks included for fast wiring
installation.
Discount Symbol . . . . . . . . . . . . . . . . . . . . 1CD-1C
Enclosed Lighting Contactors
Type 3R
Catalog
Number
ECLC202A
ECLC202E
ECLC202B
ECLC202H
ECLC202C
Price
U.S. $
CA08102001E
June 2008

Related parts for C30CNE20A0