PXL-10.924 BRODERSEN, PXL-10.924 Datasheet

RELAY, V/I, THRESHOLD, 24VDC

PXL-10.924

Manufacturer Part Number
PXL-10.924
Description
RELAY, V/I, THRESHOLD, 24VDC
Manufacturer
BRODERSEN
Series
PXLr
Datasheet

Specifications of PXL-10.924

Contact Configuration
SPDT
Power Consumption
2W
Supply Voltage Max
24V
Relay Mounting
DIN Rail
Control Voltage Type
DC
Coil Voltage Vdc Nom
24V
Contact Current Ac Max
8A
Signal Converters & Isolators
Threshold Relay PXL-10
DESCRIPTION
A threshold relay for the monitoring or control of common types of
process signals. The process signal to be monitored is selected on
the front panel and the threshold value is also adjusted via a setpoint
potentiometer on the front of the relay. As the input signal attains the
threshold plus the hysteresis the output relay energises. When the
input signal drops and passes the threshold, minus hysteresis, the
relay de-energises. The hysteresis is adjustable on the front, ±0,5
- 20%.
By strapping 2 terminals, the relay can be inverted.
A red LED indicates if the relay is energised.
There is also a latch function where the relay after energising will
remain energised, regardless of input, until the latch jumper or the
operating voltage is disconnected. Typically used in safety circuits.
Features
• Input 0 - 5V/0-10V/-10-+10VDC/0-20/4-20mA in one version.
• Adjustable setpoint.
• Hysteresis adjustable ±0,5-20%.
• Automatic locking (Latch).
• Inversion of relay function.
• Output SPDT.
• Operating voltage 24VDC, 24/115VAC or 24/230VAC.
VERSIONS/ORDERING CODES
Type:
Threshold relay
Supply voltage
24V DC
115V / 24V AC
230V AC / 24V AC
74
PXL-10
230
924
115
Export:
Tel:
Fax:
E-mail: bc@brodersencontrols.com
+45 46 74 00 00
+45 46 75 73 36
PXL-10
230
OPERATION
Output signal
MECHANICAL DIMENSIONS
setpoint
inv
inv
supply
latch
United Kingdom:
Tel:
Fax:
E-mail: bcs@brodersen.co.uk
+44 020 8546 4283
+44 020 8547 3628
hysteresis
104.0 mm
Germany:
Tel:
Fax:
E-mail: ba@brodersen.de
22.5 mm
+49 208 46954-0
+49 208 46954-50

Related parts for PXL-10.924

PXL-10.924 Summary of contents

Page 1

... Signal Converters & Isolators Threshold Relay PXL-10 DESCRIPTION A threshold relay for the monitoring or control of common types of process signals. The process signal to be monitored is selected on the front panel and the threshold value is also adjusted via a setpoint potentiometer on the front of the relay. As the input signal attains the threshold plus the hysteresis the output relay energises ...

Page 2

... L(115/230) L(24V) + (24V) SPECIFICATIONS: PXL-10 is designed and developed with regard to relevant specifi- cations: • EN60204-1 / VDE0113 electrical material on machines. • VDE0110 / IEC664 Isolation specifications/creepage and clear- ance • Electrical safety in accordance with EN61010. • IEC414 Safety regulations for control and monitoring equipment. ...

Related keywords