DMB51CM24 CARLO GAVAZZI, DMB51CM24 Datasheet - Page 2

TIME DELAY RELAY, SPDT, 100H, 240VAC/DC

DMB51CM24

Manufacturer Part Number
DMB51CM24
Description
TIME DELAY RELAY, SPDT, 100H, 240VAC/DC
Manufacturer
CARLO GAVAZZI
Datasheet

Specifications of DMB51CM24

Contact Configuration
SPDT
Nom Input Voltage
240V
Delay Time Range
0.1s To 100h
Timing Adjustment
Knob
Relay Mounting
DIN Rail
Supply Voltage Ac, Min
24VAC
Supply Voltage Ac, Max
240VAC
Contact Carrying Power
1.5W
Contact Rating
5A
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant

Available stocks

Company
Part Number
Manufacturer
Quantity
Price
Part Number:
DMB51CM24
Manufacturer:
CARLO GAVAZZI
Quantity:
500
Part Number:
DMB51CM24
Manufacturer:
TOKO
Quantity:
22 000
Part Number:
DMB51CM24B006
Manufacturer:
Carlo gavazzi
Quantity:
500
Part Number:
DMB51CM24B006
Manufacturer:
Carlo gavazzi
Quantity:
500
DMB51, DMB71
Supply Specifications
Power supply
Voltage interruption
Rated operational power
Time Setting
Upper knob:
Setting of function:
Mode of Operation
2
Function Op
Delay on operate
The time period begins as
soon as the trigger contact
is closed.
At the end of the set delay
time the relay operates and
does not release until the
trigger contact is closed
again or the power supply is
disconnected. If the trigger
contact is closed before the
end of the delay time, the
device resets and a new
time period starts.
Function In
Interval
The relay operates and the
time period begins as soon
as the trigger contact is
closed. The relay releases at
Rated operational voltage
through terminals:
(DMB51C)
(DMB71D)
(DMB51C)
(DMB71D)
Op - delay on operate
In - interval
Io - interval on trigger open
Id - double interval
Dr - delay on release
R - symmetrical recycler
(ON first)
Rb - symmetrical recycler
(OFF first)
A1, A2 M24:
A1, A2 M24:
DC supply:
AC supply:
DC supply
AC supply
W24:
W24
Centre knob:
Time setting on relative scale:
1 to 10 with respect to the
chosen range.
Lower knob:
Setting of time range
the end of this period or
when the power supply is
disconnected.
operates again when the trig-
ger contact is closed again. If
the trigger contact is closed
before the end of the delay
time, the device resets and a
new time period starts.
Function Io
Interval on trigger open
The relay operates and the
time period begins as soon
as the trigger contact is
opened. At the end of the
set delay or when the power
supply is disconnected the
relay releases. The relay
operates again when the
trigger contact is opened
again. If the trigger contact
Overvoltage cat. II
(IEC 60664, IEC 60038)
24 VDC ± 15% and
24 to 240 VAC + 10% -15%,
45 to 65 Hz
12 to 240 VDC + 10% -15%
and
12 to 240 VAC
+ 10% -15%, 45 to 65 Hz
24 VDC ± 15%
24 to 240 VAC + 10% -15%,
45 to 65 Hz
12 to 240 VDC + 10% -15%
and
12 to 240 VAC +10% -15%,
45 to 65 Hz
≤ 10 ms
4 VA
1.5 W
5.5 VA
2 W
The
relay
is opened before the end of
the delay time the relay
keeps ON and a new time
period begins.
Function Id
Double interval
The relay operates and the
time period begins as soon
as the trigger contact is
closed. The relay releases at
the end of this period or
when the power supply is
disconnected.
trigger contact is opened
the relay operates again for
the set delay period. If the
trigger contact is opened
before the end of the first
time period the second one
begins; if the trigger contact
is closed before the end of
Power ON delay
Indication for
Environment
Housing
Weight
Screw terminals
Approvals
CE Marking
EMC
General Specifications
Power supply ON
Output relays ON
Degree of protection
Pollution degree
Operating temperature
Storage temperature
Dimensions
Material
Tightening torque
Immunity
Emissions
Specifications are subject to change without notice (18.06.07)
When the
DMB51C
DMB71D
the second time period the
device resets and the first
time period begins again.
Function Dr
Delay on release
The relay operates as soon
as the trigger contact
closed.
begins when the trigger con-
tact is opened. The relay
releases at the end of the
set delay time or when the
power supply is disconnect-
ed. The relay operates again
when the input contact is
closed again. If it is opened
before the end of the delay
time the relay keeps ON, a
new time period begins as
soon as the contact is
closed again.
≤ 100 ms
LED, green
LED, yellow
(flashing when timing)
(EN 60529)
IP 20
2 (IEC 60664)
-20° to +60°C, R.H. < 95%
-30° to +80°C, R.H. < 95%
17.5 x 81 x 67.2 mm
35.5 x 81 x 67.2 mm
PA66
75 g
Max. 0.5 Nm according to
IEC EN 60947
UL, CSA
RINA (DMB 51 only)
Yes
Electromagnetic Compatibillity
According to EN 61000-6-2
According to EN 61000-6-3
The
time
period
is

Related parts for DMB51CM24