Solid State Timer

H3CR-A8E 100-240VAC/100-125VD

Manufacturer Part Number
H3CR-A8E 100-240VAC/100-125VD
Description
Solid State Timer
Manufacturer
Omron

Specifications of H3CR-A8E 100-240VAC/100-125VD

Contact Configuration
SPDT
Nom Input Voltage
240VAC
Timing Adjustment
Knob
Relay Mounting
DIN Rail
H3CR-F
Note: A power supply with a ripple of 20% max. (single-phase power supply with full-wave rectification) can be used with each DC Model.
Rated supply voltage (see note)
Operating voltage range
Power reset
Power consumption
Control outputs
Accuracy of operating
time
Setting error
Reset time
Reset voltage
Influence of voltage
Influence of
temperature
Insulation resistance
Dielectric strength
Impulse withstand
voltage
Noise immunity
Static immunity
Vibration resistance
Shock resistance
Ambient temperature
Ambient humidity
Life expectancy
EMC
Case color
Enclosure ratings
Weight
Ratings
Characteristics
±0.2% FS max. (±0.2% FS ±10 ms max. in ranges of 1.2 and 3 s)
±5% FS ±50 ms max.
0.1 s max.
10 % max. of rated voltage
±0.2% FS max. (±0.2% FS ±10 ms max. in ranges of 1.2 and 3 s)
±1% FS max. (±1% FS ±10 ms max. in ranges of 1.2 and 3s)
100 MΩ min. (at 500 VDC)
2,000 VAC, 50/60 Hz for 1 min (between current-carrying metal parts and exposed non-current-carrying
metal parts)
2,000 VAC, 50/60 Hz for 1 min (between control output terminals and operating circuit)
2,000 VAC, 50/60 Hz for 1 min (between contacts of different polarities)
1,000 VAC, 50/60 Hz for 1 min (between contacts not located next to each other)
3 kV (between power terminals) for 100 to 240 VAC, 48 to 125 VDC
1 kV for 12 VDC, 24 VAC/DC
4.5 kV (between current-carrying terminal and exposed non-current-carrying metal parts) for 100 to 240 VAC,
48 to 125 VDC
1.5 kV for 12 VDC, 24 VAC/DC
±1.5 kV (between power terminals), square-wave noise by noise simulator (pulse width: 100 ns/1 µs, 1-ns
rise)
±400 V for 12 VDC
Malfunction: 8 kV
Destruction: 15 kV
Destruction:10 to 55 Hz with 0.75-mm single amplitude for 2 hrs each in three directions
Malfunction:10 to 55 Hz with 0.5-mm single amplitude for 10 min each in three directions
Destruction: 980 m/s
Malfunction: 98 m/s
Operating:–10°C to 55°C (with no icing)
Storage: –25°C to 65°C (with no icing)
Operating: 35% to 85%
Mechanical:20 million operations min. (under no load at 1,800 operations/h)
Electrical:
(EMI)
Emission Enclosure:
Emission AC Mains:
(EMS)
Immunity ESD:
Immunity RF-interference from AM Radio Waves:
Immunity RF-interference from Pulse-modulated Radio Waves: IEC61000-4-3:10 V/m (900±5 MHz) (level 3)
Immunity Conducted Disturbance: IEC61000-4-6:
Immunity Burst:
Immunity Surge:
Light Gray (Munsell 5Y7/1)
IP40 (panel surface)
Approx. 100 g
100,000 operations min. (5 A at 250 VAC, resistive load at 1,800 operations/h)
100 to 240 VAC (50/60 Hz),12 VDC, 24 VAC/DC (50/60 Hz), 48 to 125 VDC
85% to 110% of rated supply voltage; 90% to 110% with 12-VDC models
Minimum power-opening time: 0.1 s
100 to 240 VAC: approx. 10 VA (2.1 W) at 240 VAC
24 VAC/VDC:
48 to 125 VDC:
12 VDC:
Contact output: 5 A at 250 VAC/30 VDC, resistive load (cosφ = 1)
2
2
three times each in six directions
three times each in six directions
approx. 2 VA (1.7 W) at 24 VAC
approx. 1 W at 24 VDC
approx. 1.5 W at 125 VDC
approx. 1 W at 12 VDC
EN61812-1
EN55011 Group 1 class A
EN55011 Group 1 class A
EN61812-1
IEC61000-4-2:
IEC61000-4-4:
IEC61000-4-5:
6 kV contact discharge (level 3)
8 kV air discharge (level 3)
IEC61000-4-3:10 V/m (80 MHz to 1 GHz)
10 V (0.15 to 80 MHz) (level 3)
2 kV power-line (level 3)
2 kV I/O signal-line (level 4)
1 kV line to line
2 kV line to ground (level 3)
(level 3)
H3CR-F
25