H3DE-S2 Omron, H3DE-S2 Datasheet

TIMER, MULTIFUNCTION

H3DE-S2

Manufacturer Part Number
H3DE-S2
Description
TIMER, MULTIFUNCTION
Manufacturer
Omron
Datasheet

Specifications of H3DE-S2

Contact Configuration
DPCO
Nom Input Voltage
230V
Delay Time Range
0.1s To 120h
Adjustment Type
Screwdriver Slot
Relay Mounting
DIN Rail
Svhc
No SVHC (15-Dec-2010)
Coil Voltage Vac Nom
230V
Ordering Information
1.
2.
24 to 230 VAC/DC
Mounting Track
End Plate
Spacer
H3DE -
Model Number Legend
Accessories (Order Separately)
Eight operating modes (H3DE-M) and four
operating modes (H3DE-S) cover a wide range of
applications.
Programmable contact enables the building of a
self-holding relay circuit (- 2 models).
A wide time setting range of 0.10 s to 120 h.
ou
Supply voltage
Supp y o age
M: Multi-function type
S: Standard type
2: DPDT
1: SPDT
Solid-state Multi-functional Timer
g
1
ac
2
Contact output: DPDT (time-limit output SPDT and
switchable SPDT (time-limit
Contact output: SPDT (time-limit output SPDT)
50 cm (l) x 7.3 mm (t)
1 m (l) x 7.3 mm (t)
1 m (l) x 16 mm (t)
PFP-M
PFP-S
Control output
Co
o ou pu
instantaneous))
H3DE-M2
H3DE-M1
Multi-function type
PFP-50N
PFP-100N
PFP-100N2
Model
H3DE-M/-S
H3DE-S2
H3DE-S1
Standard type
5

Related parts for H3DE-S2

H3DE-S2 Summary of contents

Page 1

... Model Number Legend H3DE - Multi-function type S: Standard type 2. 2: DPDT 1: SPDT Accessories (Order Separately) Mounting Track End Plate Spacer Co Control output instantaneous (l) x 7 (l) x 7 (t) PFP-M PFP-S H3DE-M/-S Model Multi-function type Standard type H3DE-M2 H3DE-S2 H3DE-M1 H3DE-S1 PFP-50N PFP-100N PFP-100N2 5 ...

Page 2

... VAC/DC L-level 2.4 VAC/DC Contact output 250 VAC with resistive load (cos = VDC with resistive load (cos = 1) Operating:– (with no icing) Storage: – (with no icing) Operating: 35% to 85% H3DE-M/-S H3DE-S2 H3DE-S1 A: ON-delay B2: Flicker ON start E: Interval J: One-shot --- Relay: DPDT Relay: SPDT ...

Page 3

... Life expectancy EMC Enclosure rating Weight Note: 1. With the H3DE the voltage exceeds 26.4 VAC/DC, the following hold at signal OFF for C, D, and G modes: Accuracy of operating time max. at 1.2-s range Setting error: 10% +100/–50 ms max. Signal input time: 100 ms min. 2. For reference : A maximum current of 0.15 A can be switched at 125 VDC (cos =1). ...

Page 4

... Time scale display window Output indicator (orange) (Lit while Timer gives output.) Operating mode selector (select a mode from B2 and G for the H3DE-M1/-M2, from and B2 for the H3DE-S1/S2) Power-on indicator (green) (Lit while the power is on.) Output type selector switch for H3DE-M2/-S2 (default setting ...

Page 5

... Selection of Operating Mode The H3DE-M/-S can be set to any one of the operating modes Turn the operating mode selector with a screwdriver until the de- sired operating mode ( B2 for the H3DE-M and for the H3DE-S) appears in the operating mode display window located below the selector. ...

Page 6

... Output relay: NO (output indicator) 15 and 18 (25 and 28) Power indicator Note: The start input of the H3DE-M1 or H3DE-M2 model is activated by applying a voltage to B1 and A2 terminals. The voltage can be applied by turning on the contact between B1 and A1 (Refer to T erminal Arrangement ). 10 Timing chart t t–a ...

Page 7

... Power indicator Note: The start input of the H3DE-M1 or H3DE-M2 model is activated by applying a voltage to B1 and A2 terminals. The voltage can be applied by turning on the contact between B1 and A1 (Refer to T erminal Arrangement ). Timing chart t–a t–a t t–a ...

Page 8

... H3DE- 25/ (see note 2) because it offers multiple operating modes and is different from the delayed H3DE-M/-S Terminal block (black) Surface color: Light gray 5Y7/1 (OMRON) Output type selector switch (default setting: Time-limit output) Terminal block (black) H3DE- (see note 25/ (see note 2) (see note 2) ...

Page 9

... H3DE-M/-S Input Connections The inputs of the H3DE-M1/-M2 are voltage (voltage imposition or open) inputs. No-contact Input (Connection to PNP output sensor.) Sensor Timer (+) Start 24 VDC (– Operates with PNP transistor ON Voltage Input Signal Levels 1. Transistor ON Residual voltage max. (Voltage between terminals B No-contact input the rated “ ...

Page 10

... H3DE Accessories (Order Separately) Note: The undermentioned is common for all H3DE models. Note: All units are in millimeters unless otherwise indicated. Dimensions Mounting Track PFP-100N, PFP-50N 4 Length 1 m PFP-100N 50 cm PFP-50N 1 m PFP-100N2 End Plate PFP pan head screw 32 PFP-100N2 7.3 0.15 4 ...

Page 11

... Timer from the mounting track. (C) Rail stopper The H3DE can be mounted and dismounted with ease if a distance more is kept between the H3DE and the top surface of other equipment located below the H3DE. Power Supplies The H3DE Series is provided with a transformerless power supply system ...

Page 12

... Wiring (H3DE-H) The H3DE has a high impedance circuit. Therefore, the H3DE may not be reset if the H3DE is influenced by inductive voltage. In order to eliminate any influence of inductive voltage, the wires connected to the H3DE must be as short as possible and should not be installed alongside power lines. If the H3DE is influenced by induc- tive voltage that is 30% or more of the rated voltage, connect a CR filter with a capacitance of approximately 0 ...

Page 13

... H3DE Operation (H3DE-H) An interval minimum is required to turn on the H3DE after the H3DE is turned off. If the H3DE is turned on and off repeatedly with an interval of shorter than 3 s, the internal parts of the H3DE may deteriorate and the H3DE may malfunction min. Power Output state 1 ...

Page 14

... To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527. Cat. No. L092-E1-3D In the interest of product improvement, specifications are subject to change without notice. OMRON Corporation Industrial Automation Company Measuring and Supervisory Controls Division 28th Fl., Crystal Tower Bldg., 1-2-27, Shiromi, Chuo-ku, Osaka 540-6028 Japan Tel: (81)6-6949-6035 Fax: (81)6-6949-6069 36 H3DE Printed in Japan 1199-2M ...

Related keywords