3RP15051AP30 SIEMENS, 3RP15051AP30 Datasheet - Page 43

TIMER, MULTIFUNCTION

3RP15051AP30

Manufacturer Part Number
3RP15051AP30
Description
TIMER, MULTIFUNCTION
Manufacturer
SIEMENS
Datasheet

Specifications of 3RP15051AP30

Contact Configuration
SPCO
Nom Input Voltage
240V
Delay Time Range
0.5s To 10s
Adjustment Type
Screwdriver Slot
Relay Mounting
DIN Rail
Coil Voltage Vac Nom
240V
Coil Voltage Vdc Nom
24V
Selection and ordering data
Digitally adjustable evaluation units according to DIN 3440
Temperature monitoring relays are very easy to operate. The
three-digit LED display always shows the current temperature.
A separate relay with an NO contact is included for sensor
monitoring. The relay is switched off in parameterization mode.
1) NTC type: B57227-K333-A1 (100 °C: 1.8 k W ; 25 °C: 32.762 k W ).
* You can order this quantity or a multiple thereof.
3RS10 40-1GD50
"Temperature monitors" according to DIN 3440, digitally adjustable,
2 threshold values, width 45 mm; 1 CO + 1 CO + 1 NO,
memory function possible with external jumper.
Device parameters are non-volatile
"Temperature limiters" and "Temperature monitors"
according to DIN 3440, digitally adjustable, 2 threshold values,
width 45 mm; 1 CO + 1 CO + 1 NO, tripping state
and device parameters are non-volatile
Sensor
PT100/1000;
KTY83/84; NTC
(resistance
sensors)
TYPE J, K, T, E, N
(thermocouple)
PT100/1000;
KTY83/84; NTC
(resistance
sensors)
TYPE J, K, T, E,
N, R, S, B
(thermocouple)
1)
1)
Measuring range
(measuring range
limit depends on
the sensor)
- 50 … + 500 °C
- 50 … + 932 °F
- 99 … + 999 °C
- 99 … + 1830 °F AC/DC 24
- 50 … + 750 °C
- 99 … +1.800 °C AC/DC 24
Rated control
supply voltage U
AC 50-60 Hz
V
AC/DC 24
AC/DC 24 … 240 A
AC/DC 24
AC/DC 24 … 240 B
AC/DC 24
AC/DC 24 … 240 B
AC/DC 24 … 240 B
AC/DC 24
AC/DC 24 … 240 B
AC/DC 24 … 240 B
3RS10, 3RS11 Temperature Monitoring Relays
s
DT
A
B
A
B
B
B
The following parameters can be adjusted:
• Sensor type
• 2 threshold values, J1, J2
• 1 hysteresis; applies to both thresholds (0 ... 99 K)
• 1 delay time; applies to both thresholds (0 ... 999 s)
• Open/closed-circuit principle switchable
• Manual/remote RESET
• Function: Overshoot or undershoot or window monitoring
Wide-range voltage versions are electrically isolated. The
temperature ranges depend on the sensor type.
Screw-type connection
Order No.
3RS10 40-1GD50
3RS10 40-1GW50
3RS20 40-1GD50
3RS20 40-1GW50
3RS11 40-1GD60
3RS11 40-1GW60
3RS21 40-1GD60
3RS21 40-1GW60
3RS10 42-1GD70
3RS10 42-1GW70
3RS11 42-1GD80
3RS11 42-1GW80
Relays, digitally adjustable to DIN 3440
Monitoring Relays
Price
per PU
PU
(UNIT,
SET, M)
Siemens LV 1 · 2006
1
1
1
1
1
1
1
1
1
1
1
1
PS*
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
PG
101
101
101
101
101
101
101
101
101
101
101
101
Weight
per PU
approx.
kg
7/59
0.317
0.329
0.189
0.186
0.318
0.329
0.317
0.317
0.317
0.331
0.318
0.329

Related parts for 3RP15051AP30