RM4TR32 SQUARE D, RM4TR32 Datasheet - Page 6

no-image

RM4TR32

Manufacturer Part Number
RM4TR32
Description
PHASE FAILURE RELAY 300V 5A RM4
Manufacturer
SQUARE D
Datasheet

Specifications of RM4TR32

Rohs Compliant
YES
Phase Type
3 Phase
Supply Voltage Max
300V
Supply Current Max
3A
Switching Voltage Max
250VAC
Relay Mounting
DIN Rail
Product data sheet
Performance Curves
Electrical Durability and Load Limit Curves
AC Load
Curve 1: Electrical durability of contacts on resistive load in millions of operating cycles
X
Y
Curve 2: Reduction factor k for inductive loads (applies to values taken from durability Curve 1)
X
Y
Example: An LC1-F185 contactor supplied with 115 V/50 Hz for a consumption of 55 VA or a current consumption equal to 0.5 A and cos φ =
0.3.
For 0.5 A, curve 1 indicates a durability of approximately 1.5 million operating cycles.
As the load is inductive, it is necessary to apply a reduction coefficient k to this number of cycles as indicated by curve 2.
For cos φ = 0.3: k = 0.6
The electrical durability therefore becomes:
1.5 x 10
DC Load
Load limit curve
X
Y
1
2
3
6
Current broken in A
Millions of operating cycles
Power factor on breaking (cos φ)
Reduction factor K
Current in A
Voltage in V
L/R = 20 ms
L/R with load protection diode
Resistive load
6
operating cycles x 0.6 = 900 000 operating cycles
RM4TR32

Related parts for RM4TR32