K8ABVW3200230VAC Omron, K8ABVW3200230VAC Datasheet

RELAY, VOLTAGE, 1P, 20-600V

K8ABVW3200230VAC

Manufacturer Part Number
K8ABVW3200230VAC
Description
RELAY, VOLTAGE, 1P, 20-600V
Manufacturer
Omron
Series
K8ABr
Datasheet

Specifications of K8ABVW3200230VAC

Contact Configuration
SPDT
Power Consumption
5VA
Supply Voltage Max
230VAC
Relay Mounting
DIN Rail
Control Voltage Type
AC
Svhc
No SVHC (15-Dec-2010)
Contact Current Ac Max
6A
Ideal for voltage monitoring for industrial
facilities and equipment.
• Monitor for overvoltages and undervoltages simultaneously.
• Manual resetting and automatically resetting supported by one
• Pre-alarm Mode (H/HH and L/LL operating modes)
• Two SPDT output relays, 6 A at 250 VAC (resistive load).
• Process control signal (0 to 10 V) and current splitter input
• Relay warning status easily monitoring using LED indicator.
• Input frequency of 40 to 500 Hz supported.
• Easy wiring with ferrules
• CE mark compliance certified by third party.
Model Number Structure
■ Model Number Legend
1. Basic Model
2. Functions
3. Measuring Current
4. Supply Voltage
Cat. No. N144-E1-01
K8AB-@@
Separate settings and outputs supported for overvoltages and
undervoltages.
Relay.
supported.
2 × 2.5 mm
UL certification pending.
Single-phase Voltage Relay
K8AB-VW
K8AB:
VW:
1:
2:
3:
24 VDC:
24 VAC:
100-115 VAC: 100 to 115 VAC
200-230 VAC: 200 to 230 VAC
1
2 3
2
solid or 2 × 1.5 mm
Measuring and Monitoring Relays
Single-phase Voltage Relay (Simultaneous upper and lower limit monitoring)
6 to 60 mV AC/DC, 10 to 100 mV AC/DC, 30 to 300 mV AC/DC
1 to 10 V AC/DC, 3 to 30 V AC/DC, 15 to 150 V AC/DC
20 to 200 V AC/DC, 30 to 300 V AC/DC, 60 to 600 V AC/DC
24 VDC
24 VAC
4
2
standard ferrules.
Single-phase Voltage Relay
K8AB-VW
1

Related parts for K8ABVW3200230VAC

K8ABVW3200230VAC Summary of contents

Page 1

Single-phase Voltage Relay K8AB-VW Ideal for voltage monitoring for industrial facilities and equipment. • Monitor for overvoltages and undervoltages simultaneously. Separate settings and outputs supported for overvoltages and undervoltages. • Manual resetting and automatically resetting supported by one Relay. • ...

Page 2

Ordering Information ■ List of Models Single-phase Voltage Relay Measuring voltage AC/DC 100 mV AC/DC 300 mV AC/ AC/DC AC/DC 150 V ...

Page 3

Specifications Ambient operating temperature Storage temperature Ambient operating humidity Storage humidity Altitude Operating voltage range Rated power supply frequency Output relays Resistive load Inductive load Minimum load Maximum contact voltage 250 VAC Maximum contact current Maximum ...

Page 4

Connections Wiring Diagram Overvoltage and Undervoltage Operation Diagram Control power Overvoltage setting (AL1) Voltage input value Undervoltage set value (AL2) Flashing AL1 alarm indicator Flashing T Lit AL2 alarm indicator Overvoltage (AL1) relay Undervoltage (AL2) relay T: Operating time (0.1 ...

Page 5

Nomenclature ■ Front Power indicator Relay status indicator Alarm indicator ■ Function Selection DIP Switch ON SW1 SW2 SW3 SW4 Dimensions K8AB-VW Cat. No. N144-E1-01 Indicators Power indicator (PWR: Green) Relay status indicator (RY: Yellow) Alarm indicators Voltage knob (AL1) ...

Page 6

... DC input, use a SELV power-supply capable of overcurrent protection. Specifically, a SELV power-supply has a double or reinforced insulation for input and output, and output voltage of 30 Vr.m.s with 42 peak or DC60V maximum. Recommended power-supply: Model S8VS-06024@. (Omron product) 6 Single-phase Voltage Relay ■ Precautions for Correct Use For Proper Use 1 ...

Page 7

... COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT LIABILITY event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR ...

Related keywords