LC1D18P7 SQUARE D, LC1D18P7 Datasheet

no-image

LC1D18P7

Manufacturer Part Number
LC1D18P7
Description
IEC Contactor
Manufacturer
SQUARE D
Datasheet

Specifications of LC1D18P7

No. Of Poles
3
Contact Configuration
3PST-NO
Relay Mounting
DIN Rail
Width
45mm
Relay Terminals
Screw Clamp
Operating Voltage
600VAC
Switching Power Ac1
3hp
Switching Power Ac3
15hp
Switching Current Ac1
32A
Switching Current Ac3
18A
Load Current Inductive
18A
Load Current Resistive
32A
Catalog
04
TeSys™ IEC-Style
Contactors and Starters
File 8502
CONTENTS
Description
TeSys IEC Contactors and Starters Selection Guide. . . . . . . . . . . . . . . . . . . . . . . . . . 3
TeSys K-line Mini-contactors, Overload Relays, and Accessories . . . . . . . . . . . . . . 37
TeSys D-line Contactors, Enclosed Starters Overload Relays, and Accessories . . . 77
TeSys F-line Contactors, Overload Relays, and Accessories . . . . . . . . . . . . . . . . . 179
Catalog Number Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 247
Page

Related parts for LC1D18P7

LC1D18P7 Summary of contents

Page 1

Catalog 04 TeSys™ IEC-Style Contactors and Starters File 8502 CONTENTS Description TeSys IEC Contactors and Starters Selection Guide ...

Page 2

...

Page 3

Catalog 04 TeSys™ IEC-Style Contactors and Starters Selection Guide File 8502 Selection Guide CONTENTS Description Technical Information Product Standards . . . . . . . . . . . . . . . . . . . . . ...

Page 4

Technical Information: Product Standards Technical Information: Product Standards Conformity to Standards The Telemecanique D-Line, F-line, and K-line contactors, overload relays and accessories satisfy most national, European, and international standards for promoting worldwide product acceptance. These product standards precisely define the ...

Page 5

The manufacturer is obliged to ensure that all measures are taken to provide conformity to the regulations of the particular Directive applicable to his product general rule, the manufacturer certifies conformity to the essential requirements of the Directive(s) ...

Page 6

... Product Approvals The table below shows the approvals obtained or pending with the various approvals authorities as of 5/15/1995. For more detailed information, please consult your Local Square D Field Sales Office. Existing and Pending Approval of Automation System Components (except control and signalling units) ...

Page 7

Existing and Pending Approval of Automation System Components (except control and signalling units) Approvals Standard Version X : Approved O : Approval pending Special Version + : Approved ASE CSA DEMKO Ø : Approval pending Switzer Canada Denmark land AK5 ...

Page 8

Technical Information: Product Approvals Existing and Pending Approval of Automation System Components (except control and signalling units) Approvals Standard Version X : Approved O : Approval pending Special Version + : Approved ASE CSA DEMKO Ø : Approval pending Switzer ...

Page 9

Existing and Pending Approval of Automation System Components (except control and signalling units) Approvals Standard Version X : Approved O : Approval pending Special Version + : Approved ASE CSA DEMKO Ø : Approval pending Switzer Canada Denmark land XBLA ...

Page 10

... Components mounted inside the enclosure must have a “TC” finish. • If the equipment switched off for long periods, a heater must be provided (0.2 to 0.5 kW per square decimeter / 15.5 square inch of enclosure), switched on automatically when the equipment is turned off. This heater keeps the inside of the enclosure at a temperature slightly higher than the ...

Page 11

For pilot devices, the use of “TC” treatment can be extended to outdoor use provided the enclosure is made of light alloys, zinc alloys, or plastic material. In this case essential to ensure that the degree of ...

Page 12

Technical Information: Degrees of Protection Technical Information: Degrees of Protection IEC Publication 60529 Classification of Degrees of Protection Provided by Enclosures provides a system for specifying the enclosures of electrical equipment on the basis of the degree of protection provided ...

Page 13

IEC 60529 Classification Designations — Second and Third Characteristic Numerals Second Characteristic Numeral Corresponds to protection of equipment against penetration of water with harmful effects. 0 Non-protected 1 Protected against vertical dripping water (condensation). Protected against dripping 2 water at ...

Page 14

Technical Information: Kilowatt Motor Ratings Technical Information: Kilowatt Motor Ratings The tables below provide the average full-load currents of squirrel cage motors in accordance with IEC conventions. These are given only as a guide — they may vary depending on ...

Page 15

Technical Information: Horsepower Motor Ratings The table below provides the average full-load currents of squirrel cage motors based on NEC (National Electrical Code) Tables 430-148, 149, and 150. These values are given only as a guide — they may vary ...

Page 16

Definitions of Utilization Categories Definitions of Utilization Categories IEC contactors should be selected according to the utilization category which is a combination of application and duty cycle rates defined by the following: • The type of application (inductive motor loads ...

Page 17

The following tables show the results of tests performed according to standard utilization categories conforming to IEC 60947 based on rated operational current (Ie) and rated operational voltage (Ve). Contactors AC Supply Utilization Typical Applications Category Resistors, non-inductive AC-1 or ...

Page 18

Contactor Selection for Utilization Category AC-3 Contactor Selection for Utilization Category AC-3 How to Use the Electrical Life Curves The contactor electrical life curves on the following pages may be used to estimate the number of make and break operations ...

Page 19

In many applications there is a mixture of AC3 and AC4 duty. For these applications the electrical life of a particular contactor can be estimated by using the following formula: Where Estimated electrical life for mixed duty application ...

Page 20

Contactor Selection for Utilization Category AC-3 Use in Category AC-3 (Ve Control of 3-phase asynchronous squirrel cage motors with breaking while 10 running The current broken (Ic) in category AC equal to the rated operational current ...

Page 21

Use in Category AC-3 (Ve Control of 3-phase asynchronous squirrel cage motors with 10 8 breaking while 6 running. 4 The current broken (Ic) in category AC equal to the rated 1.5 operational current 1 (Ie) of the ...

Page 22

Contactor Selection for Utilization Category AC-1 Contactor Selection for Utilization Category AC-1 Maximum Operational Current (Open-mounted Device) Contactor Size Maximum operating rate operating cycles/hour Cabling to IEC 60947-1 Operational current AC-1 according to the ambient temperature to ...

Page 23

Maximum Operational Current (Open-mounted Device) LC1 LP1 Contactor Size D50 Maximum operating rate 600 operating cycles/hour cable c.s.a (AWG) (#4) Cabling to IEC Number of Bars – 60947-1 mm – bar c.s.a. inches – Operational 40 °C ...

Page 24

Contactor Selection for Utilization Categories AC-2 and AC-4 Contactor Selection for Utilization Categories AC-2 and AC-4 Utilization category AC-2 is for breaking the starting current of slip-ring motors, while utilization category AC-4 is for breaking the starting current of squirrel-cage ...

Page 25

Maximum Breaking Current for Categories AC-2 and AC-4 LC1 LP1 Contactor Size D50 In category AC-4 (Ie maximum) A 300 – Ve 440 Vac Ie maximum broken = motor – 440 Vac Ve 690 Vac A 170 ...

Page 26

Contactor Selection for Utilization Categories AC-2 and AC-4 Use in Categories AC-2 or AC-4 (Ve Control of 3-phase asynchronous squirrel cage (AC-4) or slip- ring (AC-2) motors with breaking while motor stalled. 1 The current broken 0.8 (Ic) in category ...

Page 27

Use in Categories AC-2 or AC-4 (Ve 1 Control of 3-phase 0.8 asynchronous squirrel 0.6 cage (AC-4) or slip- 0.4 ring (AC-2) motors with breaking while motor stalled. 0.2 The current broken 0.1 (Ic) in category AC-4 0.08 is equal ...

Page 28

... Vdc 300 Vdc 460 Vdc 900 Vdc 1200 Vdc 1500 Vdc f For rated operational currents of contactors LC1 and LP1K, please consult your Local Square D Field Sales Office. Continued on next page. 28 © 2001-2004 Schneider Electric All Rights Reserved L 1 ms, ambient 55 °C [131 °F] ...

Page 29

... Vdc 2 – 1200 Vdc 3 – 1500 Vdc 4 – f For rated operational currents of contactors LC1 and LP1K, please consult your Local Square D Field Sales Office. 01/04 Contactor Selection for Utilization Categories DC-1 to DC-5 55 °C [131 °F] LC1 LC1 LC1 LC1 LC1 D115 ...

Page 30

Contactor Selection for Utilization Categories DC-1 to DC-5 Use in Category DC-1 to DC-5 The criteria for contactor selection are: • The rated operational current Ie. • The rated operational voltage Ve (see page 31). • The utilization category and ...

Page 31

Telemecanique offers a line of contactors for applications involving DC control circuits. It does not matter whether the power circuit DC. There are two considerations when using these contactors in applications involving a DC power circuit: 1. ...

Page 32

Voltage Code Tables Voltage Code Table Voltage Code Tables _ See notes pertaining to each product line at the end of this table. K-line LC1K LC7K LC2K Voltage Frequency LC8K Notes Note K4 K1 Low - ...

Page 33

Voltage Code Tables (Continued) _ See notes pertaining to each product line at the end of this table. K-line LC1K LC7K LC2K Voltage Frequency LC8K Notes Note K4 K1, K2 K2, K3 50/ 100 50/60 ...

Page 34

Voltage Code Tables Voltage Code Tables (Continued) _ See notes pertaining to each product line at the end of this table. K-line LC1K LC7K LC2K Voltage Frequency LC8K Notes Note K4 K1, K2 K2, K3 50/ ...

Page 35

Voltage Code Tables (Continued) _ See notes pertaining to each product line at the end of this table. K-line LC1K LC7K LC2K Voltage Frequency LC8K Notes Note K4 K1, K2 K2, K3 50/ 500 40-400 ...

Page 36

Definitions and Comments Definitions and Comments The low oxygen atmosphere at high altitudes reduces the dielectric strength of the air and hence the rated operational voltage of the contactor. It also reduces the cooling effect of the air and hence ...

Page 37

Catalog 04 TeSys™ K-Line Mini-Contactors, Overload Relays, and Accessories File 8502 K-Line CONTENTS Description General Information . . . . . . . . . . . . . . . . . . . . . . . . ...

Page 38

General Information General Information K-line Mini-contactors, and Overload Relays are ideal for general-duty applications where small size and reliability are key concerns. They feature: • Three contactor ratings for the USA market: — K06 rated for 3 HP motors at ...

Page 39

Characteristics of Type LC\bK and LP\bK Contactors Environment Rated insulation voltage (Vi) Rated impulse withstand voltage (Vimp) Conforming to standards Approvals Protective treatment Degree of protection Ambient air temperature around the device Maximum operating altitude Without derating Operating position Flame ...

Page 40

Characteristics of Type LC•K and LP•K Contactors Pole Characteristics Conventional thermal current (Ith) For ambient temperature Rated operational frequency Frequency limits of the operational current Rated operational voltage (Ve) Rated making capacity Rated breaking capacity Permissible short-time rating Short-circuit protection ...

Page 41

Control Circuit Characteristics Type Rated control circuit voltage (Vc) Control voltage limits ( 50 °C [122 °F]) single voltage coil Average consumption at 20 °C (68 °F) and at Vc Heat dissipation Operating time at 20 °C (68 °F) and ...

Page 42

Characteristics of Type LC•K and LP•K Contactors Auxiliary Contact Characteristics and Instantaneous Contact Blocks Number of contacts Rated operational voltage (Ve) Rated insulation voltage (Vi) Conventional thermal current (lth) Frequency of operational current Minimum switching capacity Short-circuit protection Rated making ...

Page 43

Selection of Contactors for Motor Control General-Purpose Contactors for AC Control Circuits The table below shows general-purpose contactors. The contactors mount DIN rails or with screws. The wire termination screws are in the ...

Page 44

Selection of Contactors for Motor Control Sensitive-Environment Contactors for AC Control Circuits The tables below show the kilowatt ratings (for international applications) and horsepower ratings (for North American applications) of contactors for use in sensitive environments. They are recommended for ...

Page 45

Three-Pole Contactors for DC Control Circuits The table below shows the kilowatt ratings (for international applications) and horsepower ratings (for North American applications) for three-pole contactors for DC control circuits. The contactors mount DIN rails or with ...

Page 46

Selection of Contactors for Resistive Loads Selection of Contactors for Resistive Loads Three- and Four-Pole Contactors for AC Control Circuits The tables below show general-purpose and sensitive-environment three- and four-pole contactors for AC control circuits. (The sensitive-environment contactors are recommended ...

Page 47

Three- and Four-Pole Contactors for DC Control Circuits The table below shows three- and four-pole contactors for DC control circuits. The contactors mount DIN rails or with screws. The wire termination screws are ...

Page 48

Selection of Reversing Contactors for Motor Control Selection of Reversing Contactors for Motor Control Three-Pole Reversing Contactors for AC Control Circuits The table below shows three-pole reversing contactors with integrated mechanical interlock. The contactors mount DIN rails ...

Page 49

Sensitive-Environment Reversing Contactors for AC Control Circuits The tables below show the kilowatt ratings (for international applications) and horsepower ratings (for North American applications) for reversing contactors with mechanical interlock for use in sensitive environments. They are recommended for use ...

Page 50

Selection of Reversing Contactors for Motor Control Three-Pole Reversing Contactors for DC Control Circuits The table below show the kilowatt ratings (for international applications) and horsepower ratings (for North American applications) for three-pole reversing contactors with integrated mechanical interlock for ...

Page 51

Selection of Reversing Contactors for Resistive Loads Three- and Four-Pole Contactors for AC Control Circuits The tables below show general purpose and sensitive-environment three-pole reversing and four-pole change over contactors for AC control circuits. The sensitive-environment contactors are recommended for ...

Page 52

Voltage Code Table Voltage Code Table Three- and Four-Pole Contactors for DC Control Circuits The table below shows general-purpose three-pole reversing and four-pole change over contactors for DC control circuits. The contactors incorporate an integrated mechanical interlock. The contactors mount ...

Page 53

K-line Voltage Code (Continued) K-line (see notes at end of table) LC1K Voltage Frequency LC2K Notes K1, K2 110/127 40-400 - 50/60 FE7 115 50 - 40-400 - 50/ 120 40-400 - DC - Low ...

Page 54

Selection of Auxiliary Contacts and Timers Selection of Auxiliary Contacts and Timers XX LC1/LC7/LP1K LC1/LC7/LP1K LC1/LC7/LP1K 54 © 2001-2004 Schneider Electric All Rights Reserved LA1KN LA1KN M LA1KN LA2KT2 LA1 KN P 01/04 ...

Page 55

Instantaneous Auxiliary Contact Blocks for Type LC•K and LP•K Contactors Recommended for standard applications. Clip-on front mounting, 1 block per contactor Type of Connection Screw Clamp Slip- 0.25 in 0.11 in. Spring Terminals With terminal ...

Page 56

Selection of Accessories Selection of Accessories Coil Suppressor Modules With an LED Indicator for Type LC•K and LP•K Contactors Mounting and connection Clip-on mounting on the front of LC1 and LP1 contactors. No tools required. LA4K Protection by limitation of ...

Page 57

Dimensions and Mounting of Type LC\bK and LP\bK Contactors XXX Contactors LC1K, LC7K, LP1K On panel LA1 1.22 2.24 On one asymmetrical rail DZ5MB with clip-on mounting plate LA9D973 2.24 0.83 On printed ...

Page 58

Dimensions and Mounting of Type LC•K and LP•K Reversing Contactors Dimensions and Mounting of Type LCkK and LPkK Reversing Contactors Reversing contactors LC2K, LC8K, LP2K On panel LA1K 4 mm (#6) screws 1.22 2.24 On one asymmetrical ...

Page 59

Schematics Type LC•K and LP•K Contactors and Accessories 3-pole contactors LC1K, LC7K, LP1K 3-pole + N.O. 3-pole + N.C. 4-pole contactors LC1K, LC7K, LP1K 4-pole 2-pole N.O. + 2-pole N.C. Instantaneous auxiliary contacts LA1K For contactors LC K and LP ...

Page 60

Schematics Type LC•K and LP•K Reversing Contactors and Accessories 3-pole reversing contactors LC2K, LC8K, LP2K With screw clamp terminals N.O. With Slip-on connectors or solder pins (printed circuit board N.O. 4-pole reversing contactors LC2K, LC8K, ...

Page 61

Characteristics of Type LR\bK Overload Relays Environment Conforming to standards Product certifications Protective treatment Degree of protection Ambient air temperature around the device Maximum operating altitude Operating positions Flame resistance Shock resistance, hot state (1/2 sine wave, 11 ms) Vibration ...

Page 62

Characteristics of Type LR•K Overload Relays Electrical Characteristics of the Power Circuit Rated operational voltage (Ve) Rated insulation voltage (Vi) Rated impulse withstand voltage (Vimp) Frequency limits of the operational current Power dissipated per pole Short-circuit protection and coordination Operating ...

Page 63

Selection of Type LR\bK Overload Relays These overload relays are designed for the protection of motors. They are ambient-compensated and phase-failure sensitive. They may be reset either manually or automatically. For direct mounting, the relays are placed under the contactors ...

Page 64

Dimensions, Mounting, and Schematics for Type LR•K Overload Relays Dimensions, Mounting, and Schematics for Type LR\bK Overload Relays Protection Components LR2K Direct mounting beneath the contactor 8 = 0.31 65 2.56 LR2K A H Reset/stop 64 © 2001-2004 Schneider Electric ...

Page 65

Characteristics of Type LP\bK Low-consumption Contactors Environment Rated insulation voltage (Vi) Rated impulse withstand voltage (Vimp) Conforming to standards Approvals Protective treatment Degree of protection Ambient air temperature around the device Maximum operating altitude Operating positions Flame resistance Shock resistance ...

Page 66

Characteristics of Type LP•K Low-consumption Contactors Pole Characteristics Conventional rated thermal current (Ith) Rated operational frequency Frequency limits of the operational current Rated operational voltage (Ve) Rated making capacity Rated breaking capacity Permissible short time rating Short-circuit protection Average impedance ...

Page 67

Control Circuit Characteristics Type Rated control circuit voltage (Vc) Control voltage limits ( 50 °C [122 °F]) single-voltage coil Average consumption at 20 °C (68 °F) and at Vc Heat dissipation Operating time at 20 °C (68 °F) and at ...

Page 68

... Standard control circuit voltages (variable delivery times, please consult your Local Square D Field Sales Office). f Use voltage codes on page 52 “Voltage Code Table” to complete catalog number. p LP4K06105 68 © 2001-2004 Schneider Electric All Rights Reserved Kilowatt Ratings for International Applications Standard power ratings of 3-phase ...

Page 69

... Standard control circuit voltages (variable delivery times, please consult your Local Square D Field Sales Office.). f Pre-wired power circuit connections are standard on screw clamp versions. q Use voltage codes on page 52 “Voltage Code Table” to complete catalog number. p LP5K06105 01/04 Selection of Low-consumption Reversing Contactors for Motor Control ...

Page 70

... Category AC-1 LP4K090047 Maximum current at 50 °C (122 ° Standard control circuit voltages (variable delivery times, please consult your Local Square D Field Sales Office.). f Use voltage codes on page 52 “Voltage Code Table” to complete catalog number © 2001-2004 Schneider Electric All Rights Reserved ...

Page 71

... Maximum current at 50 °C (122 ° Standard control circuit voltages (variable delivery times, please consult your Local Square D Field Sales Office.). c WARNING: These reversing contactors are pre-wired for reverse motor operation p Use voltage codes on page 52 “Voltage Code Table” to complete catalog number. 01/04 ...

Page 72

Selection of Auxiliary Contacts and Accessories for Low-consumption Contactors Selection of Auxiliary Contacts and Accessories for Low-consumption Contactors Instantaneous Auxiliary Contact Blocks (clip-on front mounting, 1 block per contactor) Type of Connection Screw clamp LA1KN Slip- 0.25 in. ...

Page 73

Dimensions and Mounting of Low-consumption Contactorsxxxxx Contactors LP4K On panel LA1 1.22 2.24 On one asymmetrical rail DZ5MB with clip-on mounting plate LA9D973 2.24 0.83 On printed circuit board 8. ...

Page 74

Dimensions and Mounting of Low-consumption Reversing Contactors Reversing contactors LP5K On panel LA1K 4 mm (#6) screws 1.22 2.24 On one asymmetrical rail DZ5MB with 2 clip-on mounting plates LA9D973 mounting plates DX1AP25. 2 ...

Page 75

Type LP\bK Schematics Type LP•K Three-Pole Low-Consumption Contactors, Reversing Contactors, and Accessories 3-pole contactors LP4K 3-pole + N.O. 3-pole reversing contactors LP5K With screw clamp terminals 3-pole + N.O. With Slip-on connectors or solder pins for printed circuit boards 3-pole ...

Page 76

Type LP•K Schematics Type LP•K Four-Pole Low-Consumption Contactors, Reversing Contactors, and Accessories 4-pole contactors LP4K 4-pole + N.O. 4-pole reversing contactors LP5K With screw clamp terminals Instantaneous auxiliary contact blocks LA1K 2 N.O. 2 N.C. LA1KN20 LA1KN02 LA1KN207 LA1KN027 Electronic ...

Page 77

Catalog 04 TeSys™ D-Line Contactors, Enclosed Starters, Overload Relays, and Accessories File 8502 D-Line CONTENTS Description CONTENTS General Information . . . . . . . . . . . . . . . . . . . . . ...

Page 78

Schneider Electric All Rights Reserved 01/04 ...

Page 79

General Information The D-line contactors and overload relays are the largest selling line of contactors and starters in the world. They offer high reliability with long mechanical and electrical life and the most complete line of accessories in the industry. ...

Page 80

Characteristics of Type LC•D and LP•D Contactors Characteristics of Type LC\bD and LP\bD Contactors Environment Type UL/CSA To IEC 60947-4-1, overvoltage Rated insulation voltage (Vi) category III, degree of pollution: 3 Conforming to UL, CSA Rated impulse withstand voltage Conforming ...

Page 81

Environment Type UL/CSA To IEC 60947-4-1, overvoltage Rated insulation voltage (Vi) category III, degree of pollution: 3 Conforming to UL, CSA Rated impulse withstand Conforming to IEC 60947 voltage (Vimp) Meets the essential Conforming to standards requirements of the LV ...

Page 82

Characteristics of Type LC•D and LP•D Contactors Control Circuit Characteristics Type Rated control circuit voltage (Vc coils Control voltage limits ( 55 °C [131 °F]) 50/60 Hz coils Average consumption at 20 °C ...

Page 83

Control Circuit Characteristics Type Rated control circuit voltage (Vc coils Control voltage limits ( 55 °C [131 °F]) 50/60 Hz coils Average consumption at 20 °C (68 °F) and ...

Page 84

Characteristics of Type LC•D and LP•D Contactors DC Control Circuit Characteristics Type of contactor Rated control circuit voltage (Uc) dc Conforming to IEC 60947-1 Rated insulation voltage Conforming to UL, CSA Operational Control voltage limits Drop-out Average consumption at 20 ...

Page 85

Contactor Integral Auxiliary Contact Characteristics Linked contacts conforming to draft Each contactor has two N.O. and N.C. contacts mechanically linked on the same movable contact holder. standard IEC 60947-4-5 Mirror contact The N.C. contact on each contactor represents the state ...

Page 86

Characteristics of Type LC•D and LP•D Contactors Power Circuit Connections Type Stranded cable without cable end Stranded cable with cable end Cabling (for screw clamp terminals) Solid cable without cable end Phillips head type Screwdriver Ø Hexagon spanner Tightening torque ...

Page 87

Power Circuit Connections Type Stranded cable without cable end Stranded cable with cable end Cabling (for screw clamp terminals) Solid cable without cable end Phillips head type Screwdriver Ø Hexagon spanner Tightening torque Bar c.s.a. Lug external Ø Bus bar ...

Page 88

Selection of Contactors for Motor Control Selection of Contactors for Motor Control The tables below show the kilowatt ratings (for international applications) and horsepower ratings (for North American applications) of contactors for motor control. AC and DC Control Circuit — ...

Page 89

The tables below show the kilowatt ratings (for international applications) and horsepower ratings (for North American applications) of contactors for motor control. LC1D123 AC and DC Control Circuit — 3-pole Contactors for Spring Terminal Connections (AC-3 category) Maximum horsepower ratings ...

Page 90

Selection of Contactors for Motor Control The tables below show the kilowatt ratings (for international applications) and horsepower ratings (for North American applications) of contactors for motor control. LC1D1506 AC and DC Control Circuit — 3-pole Contactors for Ring-tongue Terminals ...

Page 91

Selection of Contactors for Resistive Loads (AC-1) and Inductive Loads (AC-3) Selection of Contactors for Resistive Loads AC and DC Control Circuit — 4-Pole Screw Terminal Connections (AC-1 Category) Maximum Current Utilization Categories AC LC1DT20 32 ...

Page 92

Resistive Loads (AC-1) and Inductive Loads (AC-3) Resistive Loads AC and DC Control Circuit — 4-pole Contactors For Ring Terminals or Bus Bar Power Connections (AC-1 category) Maximum Current Utilization Categories AC-1 20 LC1D150 ...

Page 93

Selection of Reversing Contactors for Motor Control The tables below show the kilowatt ratings (for international applications) and horsepower ratings (for North American applications) of contactors for motor control. The contactors are pre-assembled, horizontally-mounted, and have pre-wired power connections. Order ...

Page 94

Selection of Reversing Contactors for Motor Control The tables below show the kilowatt ratings (for international applications) and horsepower ratings (for North American applications) of contactors for motor control. The contactors are pre-assembled, horizontally-mounted, and have pre-wired power connections. Order ...

Page 95

The tables below show the kilowatt ratings (for international applications) and horsepower ratings (for North American applications) of contactors for motor control. The contactors have pre-wired power connections. Order accessories separately. For information on auxiliary contact blocks and modules, see ...

Page 96

Selection of Changeover Contactors for Resistive Loads (AC-1) and Inductive Loads (AC-3) Selection of Changeover Contactors for Resistive Loads The contactors have pre-wired power connections. Order accessories separately. For information on auxiliary contact blocks and modules, see pages 106 to ...

Page 97

Selection of Changeover Contactors for Resistive Loads (AC-1) and Inductive Loads (AC-3) AC and DC Control Circuit— 4-pole Changeover Contactors with Ring-tongue Terminal or Bus Bar Power Connection (AC-1 category) Maximum Current Utilization Categories AC ...

Page 98

Component Parts for Reversing and Two Speed Contactors Component Parts for Reversing and Two Speed Contactors For 3-pole Motor Reversing Contactors Contactors with Screw Clamp Terminals or Connectors Horizontally Mounted, Assembled by Customer LA9D4002 Using 2 Identical Contactors (1) Including ...

Page 99

Component Parts for Assembling Changeover Contactor Parts for Distribution Component Parts for Assembling Changeover Contactor Parts for Distribution For 4-pole Changeover Contactor Pairs (3-phase distribution + neutral) Contactors with Screw Clamp Terminals or Connectors Horizontally Mounted, Assembled by Customer LA9D4002 ...

Page 100

Characteristics of Auxiliary Contacts, Timers, and Accessories Characteristics of Auxiliary Contact Blocks, Timers, and Accessories Auxiliary Contact Blocks without Dust and Damp Protected Contacts for Contactors Environment Contact block type Conforming to standards Product certifications Protective treatment Conforming to IEC ...

Page 101

Auxiliary Contact Blocks with Dust and Damp Protected Contacts for Contactors Operational Power of Contacts (conforming to IEC 60947-5-1) AC supply, categories AC-14 and AC-15 Electrical durability (valid up to 3600 operating cycles/hour inductive load such as the ...

Page 102

Characteristics of Auxiliary Contacts, Timers, and Accessories Auxiliary Contact Blocks with Dust and Damp Protected Contacts for Contactors Environment Contact block type Conforming to standards Product certifications Protective treatment Conforming to IEC 60068 Degree of protection Conforming to VDE 0106 ...

Page 103

Interface Modules for Contactors Environment Conforming to standards Product certifications Protective treatment Conforming to IEC 60068 Degree of protection Conforming to VDE 0106 Storage Ambient air temperature Operation around the device Permissible for operation at Uc Other Characteristics Module type ...

Page 104

Characteristics of Auxiliary Contacts, Timers, and Accessories Electronic Serial Timer Modules for Contactors Environment Module type Conforming to standards Product certifications Protective treatment Conforming to IEC 60068 Degree of protection Conforming to VDE 0106 Storage Ambient air temperature Operation around ...

Page 105

Control Modules, Coil Suppressor Modules and Mechanical Latch Blocks for Contactors Environment Conforming to standards Product certifications Protective treatment Conforming to IEC 60068 Degree of protection Conforming to VDE 0106 Storage Ambient air temperature Operation around the device Permissible for ...

Page 106

Selection of Auxiliary Contact Blocks Selection of Auxiliary Contact Blocks aaa LC1D LAD-8N The LA6DK cannot be utilized with LC1D09 through D38 TeSys contactors. q 106 © 2001-2004 Schneider Electric All Rights Reserved LAD-N10, N01 (for LC1-D40 through D95 only) ...

Page 107

Instantaneous Auxiliary Contact Blocks for Connection by Screw Clamp Terminals For use in normal operating environments Number of contacts per block (see table below for Clip-on mounting maximum number of contacts Front 4 4 includes one N.O. and ...

Page 108

Selection of Time-Delay Blocks, and Mechanical-Latch Blocks Selection of Time-Delay Blocks, and Mechanical-Latch Blocks Time Delay Auxiliary Contact Blocks for Connection by Screw Clamp Terminals Maximum number of auxiliary contact blocks that can be attached per contactor, see page 107. ...

Page 109

E1 E2 LADLVRT 1.9 (47 LAD4BB Contactors 32 A and less LADLVRT E1 E2 1.3 (32 Contactors Dimensions 1.77 45 1.67 42.4 1.51 38.4 Typical Wiring Scheme for 3-Wire ...

Page 110

Selection of Electronic Timers and Interface Modules LA4-DT LA4-DF LC1-D09 to D38 (AC only) LC1DT20 to DT40 (AC only) 110 © 2001-2004 Schneider Electric All Rights Reserved Selection of Electronic Timers and Interface Modules LA4-DL LAD-4BB ** **See Cabling Accessories ...

Page 111

Electronic Serial Timer Modules (1) 3-pole contactors LC1D40 to D150 and 4-pole contactors LC1D65 to D115: mounted directly across terminals A1 and A2 of contactor k (screw mounting). On-delay Type Operational Voltage 250 V LC1 D09 ...

Page 112

Selection of Coil Suppressor Modules Selection of Coil Suppressor Modules RC Circuits (resistor-capacitor) Effective protection for circuits highly sensitive to “high frequency” interference. For use only in cases where the voltage is virtually sinusoidal, i.e. k less than 5% total ...

Page 113

Selection of Accessories for Contactors and Reversing Contactors Accessories for Main Pole and Control Connections Description Connectors for cable, sizes (1 connector) LA9D3260 Connectors for cable, sizes (2 connectors) Connector for lug type terminals (2 connectors) Protective covers for lug ...

Page 114

Selection of Accessories for Contactors and Reversing Contactors Sets of Contacts and Arc Chambers Description Set of contacts Arc chambers GV2G245 Cabling Accessories For adapting existing wiring to a new product Set busbars for paralleling of contactors ...

Page 115

D-line Voltage Code Table D-line Voltage Code D-line (see notes at end of table) LC1D09 - D38 Voltage Frequency LC2D09 - D38 Notes D1 Low Consump AL DC 50/ Low Consump JL ...

Page 116

D-line Voltage Code Table D-line Voltage Code (Continued) D-line (see notes at end of table) LC1D09 - D38 Voltage Frequency LC2D09 - D38 Notes D1, D3 50/ 230 60 - 40-400 - DC - 230/240 50/60 - ...

Page 117

Selection of AC Coils AC Coils for Contactors LC1D09 to D38 3-pole and 4-pole LC1DT20 to DT40 Specifications Control circuit voltage Uc V Average consumption at 20 °C (68 °F): - inrush (cos - sealed (cos Operating range ( 12 ...

Page 118

Selection of AC Coils AC Coils for 3 or 4-pole Contactors LC1D40, D50, D65, D80, D95 Specifications Control circuit voltage Uc V Average consumption at 20 °C (68 °F): - inrush (cos - sealed (cos Operating range ( 24 32 ...

Page 119

Selection of AC Coils AC Coils for 3 or 4-pole Contactors LC1D115 Control circuit voltage Uc V Specifications Average consumption at 20 °C (68 °F): - inrush (cos - sealed (cos Operating range ( LX1D8 kk ...

Page 120

Selection of DC Coils Selection of DC Coils DC Coils for 3-pole Contactors LC1D40 to D65 or 4-pole Contactors LP1D65 Control circuit voltage Uc V Specifications Average consumption Operating range: 0.85 to 1.1 Uc LX4D6 ...

Page 121

DC Coils for 3 or 4-pole Contactors LC1D115, D150 Control circuit voltage Uc V Specifications Consumption: inrush 270 to 365 W, sealed 2.4 to 5.1 W. Operating range: 0.7 to 1.2 Uc. Coils have integral suppression device as standard, class ...

Page 122

Dimensions for Type LC1D Contactors Dimensions for Type LC1D Contactors D-Line Contactors AC Control Circuits X LC1D09 to D18 (3-pole) Minimum electrical clearance 0. LC1 D09 to D18 b without add-on blocks 3.03 (77) b1 ...

Page 123

D-Line Contactors DC Control Circuit or Low Consumption LC1D09 to D18 (3-pole) Minimum electrical clearance 0. LC1 b c without cover or add-on blocks with cover, without add-on blocks c1 with LADN or C (two ...

Page 124

Mounting Information for Type LC1D and LP1D Contactors Mounting Information for Type LC1D and LP1D Contactors xx On mounting rail AM1DP200, DR200 or AM1DE200 (width 35 mm) LC1D09 to D38, DT20 to DT60 c LC1 D09 to D18 D25 to ...

Page 125

LC1D09 to D38 and LC1DT20 to DT60 On two mounting rails DZ5MB DZ5-ME8 0 LC1D09 to D38 and LC1DT20 to DT60 On pre-slotted mounting plate AM1PA, PB AF1-EA4 Control circuit: ac LC1 D09 to D18 c ...

Page 126

Schematics for Type LC1D Contactors Schematics for Type LC1D Contactors 3-Pole Contactors LC1D09 to D150 4-Pole Contactors LC1 and LP1 LC1 and LP1 D12004 to D80004 D12008 to D25008 LC1D115004 Front Mounting Add-on Contact Blocks Instantaneous Auxiliary Contacts One N.O. ...

Page 127

Front Mounting Add-on Contact Blocks Dust and Damp Protected Instantaneous Auxiliary Contacts Two N.O. (24-50 V) Two N.C. (24-50 V) LA1DX20 LA1DX02 Front Mounting Add-on Contact Blocks Time-delay Auxiliary Contacts On-delay one N.O. + one N.C. Off-delay one N.O. + ...

Page 128

Dimensions for Type LC2D Contactors Dimensions for Type LC2D Contactors LC2D09 to D38 2 x LC1D09 to D38 2xM0.16 2xM4 LC2 LC1 (1) D09 to D18 ac 3.54 (90) 3.03 ...

Page 129

Schematics for Type LC2D Contactors xxx Reversing contactors for motor control, horizontally mounted LC2D09 to D150 Reversing contactor with overload relay ...

Page 130

LR2 and LR3D 3-pole Bimetallic Overload Relays LR2 and LR3D 3-pole Bimetallic Overload Relays Description D-Line 3-pole thermal overload relays are designed to protect ac circuits and motors against overloads, phase failure, long starting times and prolonged stalling of the ...

Page 131

Electrical Characteristics of Power Circuit Relay type Tripping class To UL 508, IEC 60947-4-1 Conforming to IEC 60947-4-1 Rated insulation voltage (Ui) Conforming to UL, CSA Rated impulse withstand voltage (Uimp) Frequency limits Of the operational current Setting range Depending ...

Page 132

LR9D 3-pole Solid-state Overload Relays LR9D 3-pole Solid-state Overload Relays Description LR9D electronic thermal overload relays are designed for use with contactors LC1D115 and D150. In addition to the protection provided by model d thermal overload relays, (see page 130), ...

Page 133

Electrical Characteristics of Power Circuit Relay Type Tripping Class Rated Insulation Voltage (Ui) Rated Impulse Withstand Voltage (Uimp) Frequency Limits Setting Range Power Circuit Connections Operating Specifications Temperature Compensation Tripping Threshold Sensitivity to Phase Failure Alarm Circuit Specifications Rated Supply ...

Page 134

Selection of 3-pole Class 10 Bimetallic Overload Relays Selection of 3-pole Class 10 Bimetallic Overload Relays Differential (Single Phase Sensitive) Thermal Overload Relays Compensated Relays with Manual or Automatic Reset, with Relay Trip Indicator, for ac or dc. Short-circuit Protection ...

Page 135

Selection of 3-pole Class 20 Bimetallic and Class 10 Solid-state Overload Relays Selection of 3-pole Class 20 Bimetallic and Class 10 Solid-state Overload Relays Differential (Single Phase Sensitive) Thermal Overload Relays Compensated relays with manual or automatic reset, with relay ...

Page 136

Selection of Overload Relay Accessories Selection of Overload Relay Accessories DX1-AP25 LA7-D03 DX1-AP26 LA7-D902 136 © 2001-2004 Schneider Electric All Rights Reserved LAD-7B10 LAD-703 LRD- LA7-D1064 LA7-D03 LR2-D15 LA7-D2064 LA7-D901 LR2-D25 LA7-D3064 LRD-3 LR2-D35 LAD-7305 LRD- LA7-D305 LRD-3 LRD- LRD-3 ...

Page 137

Accessories (to be ordered separately) Description Pre-wiring kit allowing direct connection of the N.C. contact of relay LRD01 LR3D01 to D35 to the contactor Separate Mount Kits Terminal blocks (1) for separate mounting rail ...

Page 138

Dimensions for 3-pole Bi-metalic and Solid-state Overload Relays Dimensions for 3-pole Bi-metallic and Solid-state Overload Relays D-Line Thermal Overload Relays LRD-01-35 Direct mounting beneath contactors with screw LC1• D09 - D18 D25 - D38 b 4.84 (123) 5.39 (137) c ...

Page 139

Mounting Information for Bimetallic and Solid-state Overload Relays D-Line Thermal Overload Relays LRD-01-35 Independent mounting centers or on rail AM1DP200 or DE200 LAD-7B10 3.15 0.08 1. Remote tripping or electrical reset LAD-703 (1) 1.26 ...

Page 140

Mounting Information for Bimetallic and Solid-state Overload Relays D-Line Thermal Overload Relays LRD3••• and LR2D35•• Independent mounting centers or on rail AM1DP200 or DE200 LA7-D3064 4.76 d 2x¯0.18 121 2x¯4.5 AM1DP200 AM1DE200 d 0.08 (2) 0.37 (9.5) ...

Page 141

Capacitor-switching Contactors (International Applications Only) For Switching 3-phase Capacitor Banks used for Power Factor Correction - Selection Standard Contactors Capacitors, together with the circuits to which they are connected, form oscillatory circuits which can, at the moment of switch-on, give ...

Page 142

Capacitor-switching Contactors (International Applications Only) For Switching 3-phase Capacitor Banks, used for Power Factor Correction Direct Connection without Choke Inductors - References Special Contactors Special contactors LC1DkK are designed for switching 3-phase, single or multiple-step capacitor banks; they conform to ...

Page 143

For Switching 3-phase Capacitor Banks, used for Power Factor Correction Dimensions, Schematics - References zzz Dimensions LC1DFK, DGK c LC1 c Type of Mounting DFK 117 LC1D12 DGK 122 LC1D18 LC1DLK, DMK c LC1 c Type of Mounting DLK 117 ...

Page 144

Plate-mounted Starters LC4D (International Applications Only) Plate-mounted Starters LC4D (International Applications Only) AC D.O.L. Starters, Plate Mounted, for Motor Control kW, (1), with Isolating Device, Pre-Assembled - References Utilization Category ac-3 Standard Power Ratings of 3-phase Motors ...

Page 145

D.O.L. Starters, Plate Mounted, for Motor Control kW, with Isolating Device, Pre-assembled - Dimensions, Schematics z Dimensions D.O.L. Starters Plate Mounted, Pre-assembled LC4D09 to D25A 4.69 119 3.94 0.17 100 4 2. ...

Page 146

AC Wye-delta Starters LC3D (International Applications Only) AC Wye-delta Starters LC3D (International Applications Only) 5.5 to 132 kW, (1), without Isolating Device, Pre-assembled - References NOTE: Wiring methods differ from typical North American practice. Contains UL listed, CSA certified, CE ...

Page 147

Wye-delta Starting Current Starting in direct delta connection 2 Starting in wye connection Torque 2,5 2 1 Starting in direct delta connection 2 Starting in ...

Page 148

AC Wye-delta Starter Kits (International Applications Only) AC Wye-delta Starter Kits (International Applications Only) a 148 © 2001-2004 Schneider Electric All Rights Reserved 01/04 ...

Page 149

Wye-delta Starters, for Motor Control, 7.5 to 132 kW (1), without Mechanical Interlock, for Customer Assembly (on plate or on mounting rail) (2) - References Starters for Direct Combination with Circuit-breaker Maximum Operating Rate: 30 starts/hour. Maximum starting time: 30 ...

Page 150

AC Wye-delta Starter Kits (International Applications Only) Wye-delta Starters - Dimensions, Schematics Dimensions for Wye-delta Starters On mounting rail AM1-DP, pre-assembled LC3-D090A to D320A KM2 6.30 c 160 6.89 LC3 D090A to D180A b 6.0 (153) c with LAD-S 5.4 ...

Page 151

Enclosed Contactors and Starters Horsepower Ratings for North American Applications of D-Line Products in Metal Enclosures D-line enclosed full voltage starters are available in Type 1 and Type 12/3R enclosures through 460 Vac. See pages 106 to ...

Page 152

Enclosed IEC Non-Combination Starters Enclosed IEC Non-combination Starters Enclosed starter overload relay selection table Code LE2D093A62 Available in ...

Page 153

Enclosed IEC Combination Starters Horsepower Ratings for North American Applications of D-Line Products in Metal Enclosures with Fusible Disconnect Switch or Circuit Breaker IEC combination starters combine the requirements of motor overload and short circuit protection in one convenient compact ...

Page 154

Enclosed IEC Combination Starters Enclosed starter overload relay selection table Code LE1D406C72 Available in Class 10 only q Available ...

Page 155

Factory Modifications and Insta-Kit Selection Add the Factory Modification Code to the end of the catalog number created from pages 151 and 152. Only one operator scheme (factory modification code or field-installable Insta-Kit option) can be used. Only the combinations ...

Page 156

Dimensions for Enclosed Combination and Non-Combination IEC Starters Dimensions for Enclosed Combination and Non-Combination IEC Starters Combination Starter Dimensions with Rotary Disconnect Handle - Type 1 Knockout Schedule Knockout Conduit Size, in. (mm) A 0.50 (12.7) B 1.00 (25.4); 1.25 ...

Page 157

Schematics for Enclosed IEC Non-Combination Starters Non-Reversing, Non-Combination 3-Phase Starter Reset Reversing, Non-Combination 3-Phase Starter Reset 01/04 Schematics for Enclosed IEC Non-Combination Starters White Plug-in connector Yellow Brown Plug-in Connector Jumper Jumper Wire 4 ...

Page 158

Schematics for Enclosed IEC Combination Starters Schematics for Enclosed IEC Combination Starters Non-Reversing, Combination 3-Phase Starter Reversing, Combination 3-Phase Starter Reset 158 © 2001-2004 Schneider Electric All Rights Reserved White Plug-in connector Yellow Reset ...

Page 159

International Enclosed Contactors LE1D (International Applications Only) D.O.L. AC Starters for Motor Control (1) 2 kW, without Isolator Device Applications Only Characteristics Conforming to standards Degree of protection to IEC 60529 IP 659: LE2K, IP 657: LEpD09 to ...

Page 160

Enclosed Contactors LE1D and LE2D D.O.L. AC Starters for Motor Control (1) 2 without Isolator Device, Non-reversing Description Standard versions comprise: • For non-reversing starters: • For reversing starters: — LE2K: — LE2D09 to D35: LE1D12••A04 — ...

Page 161

International Enclosed Contactors with Fused Disconnect Switch LE4K/D (International Application Only) D.O.L. AC Starters for Motor Control (1), 2 with Isolator Device Applications Only Characteristics Conforming to standards Degree of protection to IEC 529 Ambient air temperature ...

Page 162

Enclosed Reversing Starters with Fused Disconnect Switch LE2, LE4 and LE8 International Enclosed Reversing Starters with Fused Disconnect Switch LE2D (Int’l App. Only) Applications Only D.O.L. AC Starters for Motor Control (1) 2 with Isolator Device Description ...

Page 163

Wye-delta Starters LE3D (International Applications Only) Wye-Delta Starters for Motor Control from kW, without Off-Load Isolator (1) - References Selection Standard Power Ratings of Squirrel Cage Motors Mains Voltage - Delta Connection (kW) 220 V Maximum operating ...

Page 164

Wye-delta Starters with Fused Disconnect Switch LE3D (International Applications Only) Wye-delta Starters with Fused Disconnect Switch LE3D (International Applications Only) International NOTE: Wiring methods differ from typical North American practice. Applications Only Contains UL Listed, CSA Certified, and CE marked ...

Page 165

... Mounting kit for head ZB5AL432 Operating Heads for Reset Pushbuttons Flush blue “R” (2) Mounting kit for head ZB5AA0 + ZBA639 ZB5AL432 Operating Heads for Selector Switches Description 3 position stay put 2 position stay put 3 position spring return to center Contact Blocks LAD9091 1 N.O. ...

Page 166

Spare Parts and Accessories (International Applications Only) Empty Enclosures for D.O.L. Starters Without Isolator Device For use with LE1D09, D12 DE1DS1A04 LE1D18 to D35 DE1DS1A05 DE1DS1 DE1DS1A13 166 © 2001-2004 Schneider Electric All Rights Reserved Push button operating head(s) or ...

Page 167

LE·D Dimensions (International Applications Only) Enclosed D-line Starters Without Fused Disconnect Switch LE1D09 and D12 0. Standard version 5.05 (128.5) Version A04 4.7 (120) Version A05 5.05 (128.5) Version A09 5.31 (135) ...

Page 168

LE·D Dimensions (International Applications Only) Enclosed D-line Starters With Fused Disconnect Switch LE4K06 and K09 LE8K06 and K09 1.15 x 0.21 0.74 0.78 3 6.88 4.72 175 120 c1 c1 LE4K LE8K Standard version 5.74 (146) 5.74 ...

Page 169

LE·K Dimensions (International Applications Only) Enclosed K-line Starters Without Fused Disconnect Switch LE3K065, K095 0.74 (19) 0.15 x 0.20 4.72 120 5.74 3.3 146 84 6.88 175 LE3D405 to D505 0. 8.85 225 14.4 367 LE3D805 ...

Page 170

LG1K and LG1D Dimensions (International Applications Only) Starters Without Isolator LE6D09 to D18 0. 7.32 186 c1 Standard version 6.90 (175.5) Version A04 6.57 (167) Version A05 6.90 (175.5) LE3D406 to D806 = 0.15 x ...

Page 171

LE1K and LE1D Wiring Diagrams (International Applications Only) LE1D09 to D955 – KM1 LE2K06, K09 – KM1 – KM2 LE2D09 to D955 – KM1 – KM2 01/04 LE1K and LE1D Wiring Diagrams (International Applications Only) LE1D09 to D955 A O ...

Page 172

LE2K and LE2D Wiring Diagrams (International Applications Only) LE2K and LE2D Wiring Diagrams (International Applications Only) LE6D09 to D18 – Q1 – KM2 – KM3 – KM1 LE3D326 t0 D806 – Q1 – KM3 – KM1 – KM2 172 © ...

Page 173

LE4K, LE4D, LE8K, and LE2D Dimensions (International Applications Only) LE3K065 and K095 – KM2 – KM3 – KM1 Recommended cabling for reversal of motor rotation (standard motor, viewed from shaft end). LE3D09 to D805 Ð KM2 Ð KM3 Ð KM1 ...

Page 174

LG1K, LG1D, LG7K, LG7D, and LG8K Dimensions (International Applications Only) LG1K, LG1D, LG7K, LG7D, and LG8K Dimensions (International Applications Only) LE4K06, K09 LE4K06, K09 LE4D09 to D806 A – – KM1 O – KM1 B LE8K06, K09 – ...

Page 175

Cross-Reference Table 3-Pole AC Contactors(1) Connection for Cables with or without Cable End Old Catalog No. LC1D0900 LC1D0910 LC1D0901 LC1D1200 LC1D1210 LC1D1201 LC1D1800 LC1D1810 LC1D1801 LC1D2500 LC1D2510 LC1D2501 LC1D3200 LC1D3210 LC1D3201 LC1D3810 LC1D3801 LC1D4011 LC1D5011 LC1D6511 LC1D8011 LC1D9511 LC1D11500 LC1D15000 ...

Page 176

Cross-Reference Table 3-Pole Contactors, Low Consumption (1) Connection for Cables with or without Cable End Old Catalog No. LP4D0910 LP4D0901 LP4D1210 LP4D1201 LP4D1810 LP4D1801 LP4D2500 3-Pole Reversing Contactors, Low Consumption (1) LP5D0910 LP5D1210 LP5D1810 LP5D2500 (1) Coil voltages: codes to ...

Page 177

Thermal Overload Relays For Use with Balanced Loads Old Catalog No. LR2D1301 LR2D1302 LR2D1303 LR2D1304 LR2D1305 LR2D1306 LR2D13X6 LR2D1307 LR2D1308 LR2D1310 LR2D1312 LR2D1314 LR2D1316 LR2D1321 LR2D1322 LR2D2353 LR2D2355 LR2D1508 LR2D1510 LR2D1512 LR2D1514 LR2D1516 LR2D1521 LR2D1522 LR2D2553 LR2D3322 LR2D3353 LR2D3355 LR2D3357 ...

Page 178

Schneider Electric All Rights Reserved 01/04 ...

Page 179

Catalog 04 TeSys™ F-Line Contactors, Overload Relays, and Accessories File 8502 F-Line CONTENTS Description General Information . . . . . . . . . . . . . . . . . . . . . . . . ...

Page 180

Schneider Electric All Rights Reserved 01/04 ...

Page 181

General Information The F-line contactors and overload relays offer proven performance for resistive loads or large motor starting applications such as fans, crushers, pumps, compressors and overhead cranes. They offer high reliability with long mechanical and electrical life and the ...

Page 182

... In the least favorable direction, without change of contact state (coil at Vc). c Paralleling of poles must be carried out only in accordance with the fuse manufacturer's recommendations. q Sine wave without interference, above these values, please consult your Local Square D Field Sales Office. p 182 © 2001-2004 Schneider Electric All Rights Reserved ...

Page 183

... Wire pressure screw In the least favorable direction, without change of contact state (coil at Vc). c Paralleling of poles must be carried out only in accordance with the fuse manufacturer's recommendations. q Sine wave without interference, above these values, please consult your Local Square D Field Sales Office. p 01/04 LC1F330 LC1F400 ...

Page 184

Characteristics Contactors Type LC1F (115 to 800 A) Control Circuit: AC Supply Type Control Circuit Characteristics (LX1/LX8 type coils) Rated control circuit voltage (Vc coils Control voltage limits ( 55 °C [131 ...

Page 185

Contactors Type LC1F (115 to 800 A) Control Circuit: AC Supply Type Control Circuit Characteristics (LX1/LX8 type coils) Rated control circuit voltage (Vc coils Control voltage limits ( 55 °C [131 °F]) ...

Page 186

Characteristics Contactors Type LC1F (115 to 800 A) Control Circuit: DC Supply Type Control Circuit Characteristics (LX4/LX8 type coils) Rated control circuit voltage (Vc) DC Operational Control voltage limits 55 °C [131 °F]) Drop-out Average consumption °C ...

Page 187

Contactors Type LC1F (115 to 800 A) Control Circuit: DC Supply Type Control Circuit Characteristics (LX4/LX8 type coils) Rated control circuit voltage (Vc) DC Operational Control voltage limits 55 °C [131 °F]) Drop-out Average consumption °C (68 ...

Page 188

Selection – Contactors Selection - Contactors Control Circuit Kilowatt Ratings for International Applications 2-, 3-, and 4-Pole Contactors Standard power ratings of 3-phase motors 50/ category AC-3 220 V 380 V 230 V 400 V ...

Page 189

Control Circuit Horsepower Ratings for North American Applications 2-, 3-, and 4-Pole Contactors Standard power ratings of 3-phase motors 50/ category AC-3 200 V 208 V HP LC1F225 Current Rated 60 75 ...

Page 190

Mechanical Interlocks and Power Connections Mechanical Interlocks and Power Connections Components for Assembling 3-Pole Reversing Contactors and Changeover Contactor Pairs, for Customer Assembly Horizontally mounted Reversers assembled using 2 contactors of identical rating, type: LC1F115 LC1F150 LC1F185 LC1F225 LC1F265 LC1F330 ...

Page 191

Components for Assembling 3-Pole Reversing Contactors and Changeover Contactor Pairs, for Customer Assembly. How to order: Components are available for customer assembly of F-line reversing contactors and changeover contactors. For example the following components must be ordered to build a ...

Page 192

Mechanical Interlocks and Power Connections Components for Assembling 3- and 4-Pole Changeover Contactor Pairs, for Customer Assembly Horizontally mounted Reversers assembled using 2 contactors of identical rating, type: LC1F1154 LC1F1504 LC1F1854 LC1F2254 LC1F2654 LC1F3304 LC1F4004 LC1F5004 LC1F6304 Vertically mounted Reversers ...

Page 193

Components for Assembling 3 and 4-Pole Changeover Contactor Pairs, for Customer Assembly For additional information see How to Order on page 191. Using 2 contactors of identical rating For assembly of 4-pole changeover contactor pairs Contactor Type c Horizontally mounted ...

Page 194

Auxiliary Contacts and Timers Auxiliary Contacts and Timers aaa LADN10 LC1F LADN01 194 © 2001-2004 Schneider Electric All Rights Reserved LADN LADN LADC LADT LADS LADR LA1DX, LA1DY, LA1DZ 01/04 ...

Page 195

Contactors and Reversing Contactors Type LC1F Auxiliary Contact Blocks and Interface Module Instantaneous Auxiliary Contact Blocks For use in normal operating environments Number of contacts With terminal referencing conforming to standard EN 50012 2 4 See page ...

Page 196

Accessories and Spare Parts Accessories and Spare Parts LA9D09981 Contactors and Reversing Contactors Type LC1F Suppressor Blocks and Cabling Accessories Suppressor Blocks Type of Suppressor RC (Resistor-Capacitor) LA9F980 Varistor Bi-directional Diode Diode LA9F 602 Mounting bracket (for 35mm DIN rail ...

Page 197

Contactors and Reversing Contactors Type LC1F Suppressor Blocks and Cabling Accessories Right-Angled Connectors LA9F 981 For contactors or thermal overload relays For use on Contactors LC1F115 LC1F150, F185 LC1F225, F265. F330, F400 LC1F500 LC1F630, F800 LA9F 979 Connection Accessories For ...

Page 198

Accessories and Spare Parts Contactors and Reversing Contactors Type LC1F Cabling Accessories and Spare Parts Lug Kits Lugs can be ordered either individually (for 2-pole and 4-pole contactors sets of 6 (for 3-pole contactors). Mounting hardware is provided ...

Page 199

Contactors and Reversing Contactors Type LC1F Spare Parts Main Contact Sets Per pole: 2 stationary contacts and 1 moving contact, 2 deflectors, 1 leaf spring, screws and washers For contactor 2-pole LA5FG431 3-pole 4-pole Arc Chambers LA5F40050 For contactor 2-pole ...

Page 200

F-line Voltage Code Table F-line Voltage Code Table F-line Voltage Code F-line (see notes at end of table) LC1F115 LC1F265 Voltage Frequency - F225 - F400 Note F1, Note F1 Low - - Consump DC 50/60 - ...