M1PRC/S 400V BROYCE CONTROL, M1PRC/S 400V Datasheet

RELAY, PHASE SEQUENCE FAILURE

M1PRC/S 400V

Manufacturer Part Number
M1PRC/S 400V
Description
RELAY, PHASE SEQUENCE FAILURE
Manufacturer
BROYCE CONTROL
Datasheet

Specifications of M1PRC/S 400V

Contact Configuration
SPDT
Phase Type
3 Phase
Power Consumption
20VA
Supply Voltage Max
400VAC
Switching Voltage Max
250VAC
Operating Time Range
0.2s To 10s
Relay Mounting
DIN Rail
Contact Current Ac Max
8A
Ac Power
4VA
Adjustment Type
Knob
Applying power.
Setting the unit.
Troubleshooting.
The table below shows the status of the unit during a fault condition.
Type: M1PRC/S & M1PRC/S-4W
Phase Failure, Phase Sequence, Under and Over Voltage plus Time Delay
q
q
q
q
q
q
q
q
Supply fault
Phase or Neutral (4-wire only) missing
Phases reversed (no delay)
Under or Over Voltage condition (during timing)
Under or Over Voltage condition (after timing)
Phase below 70% of Un (fixed under trip level [2])
Phase below 50% of Un
Telephone: +44 (0) 1902 773746 Facsimile: +44 (0) 1902 420639 Email: sales@broycecontrol.com Web: http://www.broycecontrol.com
The information provided in this literature is believed to be accurate (subject to change without prior notice); however, use of such information shall be entirely at the user’s own risk.
FUNCTION DIAGRAM
INSTALLATION AND SETTING
BEFORE INSTALLATION, ISOLATE THE SUPPLY.
Connect the unit as required. The diagram below shows a typical installation, whereby the supply to
the load is being monitored by the relay. If a fault should occur (i.e. fuse blowing), the contactor is de-
energised removing the 3-phase supply to the load. The contactor only re-energises after the fault has
cleared.
Set the “over %” adjustment to maximum and the “under %” adjustment to minimum. Set the
“time delay” to minimum.
Apply power and the green “supply on” and red “relay” LED’s will illuminate, the relay will energise
and contacts 15 and 18 will close. Refer to the troubleshooting table if the unit fails to operate
correctly.
Set the “over %” and the “under %” adjustments to give the required monitoring range.
If large supply variations are anticipated, the adjustments should be set further from the nominal
voltage.
Set the “time delay” as required. (Note that the delay is only effective should the supply increase
above or drop below the set trip levels. However, if during an under voltage condition the supply
drops below the 2
de-energises).
CONNECTION DIAGRAM
17.5mm DIN rail housing
Monitors own supply and detects if one or more phases exceed the set Under or Over Voltage
trip levels
M1PRC/S measures phase to phase voltage and M1PRC/S-4W measures phase to neutral voltage
Detects incorrect phase sequence, phase loss and neutral loss (4-wire only)
Adjustments for under and over voltage trip level
Adjustment for time delay (from under or over voltage condition)
1 x SPDT relay output 8A
Intelligent LED indication for supply and relay status
(4-wire only) N
Fixed
Under trip [2]
3~ Supply
Monitored
Output
L1
L2
L3
N*
Supply / Monitored
L1, L2
L2, L3
L3, L1
Local Fuse
Voltage
nd
Board
Over trip
Hyst.
Hyst.
Under trip
under voltage trip level, any set time delay is automatically cancelled and the relay
Td
t
Broyce Control Ltd., Pool Street, Wolverhampton, West Midlands WV2 4HN. England
Phase monitor
t
N*
Green LED
Off
Flashing
On
On
On
Off
L1
16 18
15
time delay automatically cancelled as
phase drops below 2nd trip point
L2
L3
tr
Red LED
Off
Off
Flashing
Off
Off
Off
Contactor
*N - Neutral connection
only available on 4-wire
version
Installation work must be carried
tr
out by qualified personnel.
Phases reversed
Relay
De-energised
De-energised
Energised for set delay (t)
De-energised
De-energised
De-energised
LOAD
Td
Supply / monitoring
Frequency range:
Supply variation:
Isolation:
Rated impulse
Power consumption (max.):
Trip levels:
Measuring ranges:
Repeat accuracy:
Hysteresis:
Response time:
Time delay (t):
Delay from
Power on delay (Td):
Ambient temp:
Relative humidity:
Output (15, 16, 18):
Output rating:
Electrical life:
Dielectric voltage:
Rated impluse
Housing:
Weight:
Mounting option:
Terminal conductor size:
Approvals:
Options:
1.
voltage Un* (L1, L2, L3):
withstand voltage:
withstand voltage:
phase/neutral loss (tr):
TECHNICAL SPECIFICATION
The unit is also available with a double-pole relay output. Refer to separate data sheet
for M3prc/s/2 and M3prc/s/2-4w.
MOUNTING DETAILS
surface mounting
Withdraw clips
(L1, L2, L3, N):
fully when
Insert screwdriver
Under [2]:
Over:
Under:
63.5V:
120V:
127V:
220V:
230V:
240V:
110V:
208V:
220V:
380V:
400V:
415V:
to release clips
to DIN 43880
3-wire: 110, 208, 220, 380, 400, 415V AC (phase to phase)
4-wire: 63.5, 120, 127, 220, 230, 240V AC (phase to neutral)
48 - 63Hz
70 - 130% of Un
Over voltage cat. III
4kV (1.2 / 50 S) IEC 60664
3-wire: L1: 20VA, L2: 0.2VA, L3: 20VA
4-wire: L1: 13VA, L2: 0.1VA, L3: 0.1VA
70% of Un (fixed) 2%
75 - 95% of Un
105 - 125% of Un
Under [2]
44.5V
84V
90V
154V
161V
168V
77V
146V
154V
266V
280V
290V
** measured phase to neutral
0.2 - 10 sec ( 5%)
Note: actual delay (t) = adjustable delay + response time
-20 to +60 C
+95%
SPDT relay
AC1
AC15
DC1
2kV AC (rms) IEC 60947-1
4kV (1.2 / 50 S) IEC 60664
Orange flame retardant UL94 VO
On to 35mm symmetric DIN rail to BS5584:1978
(EN50 002, DIN 46277-3) Or direct surface mounting via 2 x
M3.5 or 4BA screws using the black clips provided on the rear
of the unit.
Conforms to IEC. CE and
0.5% @ constant conditions
2% of trip level (factory set)
50 mS
100 mS (worst case = tr x 2)
1sec. (worst case = Td x 2)
150,000 ops at rated load
70g
2 x 2.5mm
W. 17.5mm
Dims:
89 (excl. clips)
93 (+/- 1mm)
2
solid or stranded
Under
48 - 60V
90 - 114V
95 - 121V
165 - 209V
173 - 218V
180 - 228V
83 - 105V
156 - 197V
165 - 209V
285 - 361V
300 - 380V
311 - 394V
250V 8A (2000VA)
250V 5A (no), 3A (nc)
25V 8A (200W)
45
Compliant.
Over
67 - 79V (4-wire **)
126 - 150V(4-wire **)
133 - 159V (4-wire **)
231 - 275V (4-wire **)
241 - 288V (4-wire **)
252 - 300V (4-wire **)
116 - 138V (3-wire)
218 - 260V (3-wire)
231 - 275V (3-wire)
399 - 475V (3-wire)
420 - 500V (3-wire)
436 - 519V (3-wire)
Terminal Protection to IP20
Supply / monitoring
voltage when ordering
Please state
49 59
M1PRCS-2-A

Related parts for M1PRC/S 400V