PXL-20.924 BRODERSEN, PXL-20.924 Datasheet - Page 2

RELAY, V/I, THRESHOLD, 24VDC

PXL-20.924

Manufacturer Part Number
PXL-20.924
Description
RELAY, V/I, THRESHOLD, 24VDC
Manufacturer
BRODERSEN
Series
PXLr
Datasheet

Specifications of PXL-20.924

Contact Configuration
DPCO
Power Consumption
2W
Supply Voltage Max
24V
Relay Mounting
DIN Rail
Control Voltage Type
DC
Coil Voltage Vdc Nom
24V
Contact Current Ac Max
100mA
TECHNICAL DATA
Input:
Output:
Supply voltage:
AC
General data:
Export:
Tel:
Fax:
E-mail: bc@brodersencontrols.com
Input signal
0-5V DC
0-10V DC
-10-+10V DC
0-20mA DC
4-20mA DC
Selected via switch on the front panel.
Hysteresis:
Response time:
Upper critical frequency 30 Hz.
Versions:
Net frequency:
Consumption:
Ambient temperature:-20 to 55°C.
Storage temperature:-40 to 80°C.
Mounting:
Terminals:
Indicators:
Protection:
Electric isolation:
Housing:
Terminal block:
Weight:
+45 46 74 00 00
+45 46 75 73 36
Green LED = operating voltage.
Impedance
>100kOhm
>100kOhm
>100kOhm
50 Ohm
50 Ohm
±0,5-20% of range, adjustable.
Time constant ( = approx. 0,1s,
worst case of response time max. 5x ).
Solid state (NO/NC)
U
I
On resistor min. 15 ohm, max. 35 ohm.
Off state leak = max. 1µA.
See fig. 1.
924 = 24V DC (20,4-27,6)V DC
115 = 24/115V AC (20,4-27,6/98-132)V AC
230 = 24/230V AC (20,4-27,6/196-264)V
45-65Hz.
AC; 3VA.
DC; 2W.
35mm DIN-rail (EN50022).
Screw terminals with dual compartment.
Terminal screws are combined crosshead/
slotted. Up to 2 x 2,5mm2 wire
(2 x 1,5mm2 inc. ferrule).
Recommended torque, 0,5Nm, Max. 0,7 Nm
(VDE0609-1).
Terminal identification in accordance with
DIN46199/EN50005.
Red LED = relay switched on.
IP20.
3,75kVAC (1 min.) between input,
supply and relay output (EN60950).
Noryl (GE), UL94V1.
Noryl (GE), UL94V0.
180 g.
MAX
MAX
= 100mA
= ±35V DC/24VAC
United Kingdom:
Tel:
Fax:
E-mail: bcs@brodersen.co.uk
U
I
MAX
MAX
+44 020 8546 4283
+44 020 8547 3628
= 50mA
= 50Vp-p
WIRING DIAGRAM
SPECIFICATIONS:
PXL-20 is designed and developed with regard to relevant specifica-
tions:
• EN60204-1 / VDE0113 electrical material on machines.
• VDE0110 / IEC664 Isolation specifications/creepage and clear-
ance distances.
• Electrical safety in accordance with EN61010.
• IEC414 Safety regulations for control and monitoring equipment.
• EMC:
• Humidity in accordance with IEC68-2-3; RH=95%, 40°C.
• Vibration in accordance with IEC68-2-6.
• Shock when mounted, in accordance with IEC68-2-27.
PXL-20 is CE-marked in accordance with EMC and the Low Voltage
Directive.
L (115/230)
+ (24V)
Germany:
Tel:
Fax:
E-mail: ba@brodersen.de
Input 0
A1
Y1
A3
no
L(24V)
+49 208 46954-0
+49 208 46954-50
com
-
no
nc
com
Y2
Z1
nc
I
+
IN
N
-(0V)
V
+
IN
Z2
A2
Z3
Y3
Inversion
relay
AC supply
DC supply
Latch
active
Emission EN50081-1
Immunity EN50082-2
Signal Converters & Isolators
Coding:
Relay inverter: Z1-Z2
Latching:
Threshold Relay PXL-20
Z1-Z3
77