LC1D186B7 SQUARE D, LC1D186B7 Datasheet - Page 2

no-image

LC1D186B7

Manufacturer Part Number
LC1D186B7
Description
IEC Contactor
Manufacturer
SQUARE D
Datasheet

Specifications of LC1D186B7

No. Of Poles
3
Contact Configuration
3PST-NO
Relay Mounting
DIN Rail
Coil Voltage Vac Nom
24V
Width
45mm
Relay Terminals
Screw Clamp
Contact Rating
18A
Operating Voltage
600VAC
Switching Power Ac1
3hp
Switching Power Ac3
15hp
Switching Current Ac1
32A
Switching Current Ac3
18A
Load Current Inductive
18A
Load Current Resistive
32A
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
2
Main
Range of product
Product or component
type
Device short name
Contactor application
Utilisation category
Poles description
Power pole contact
composition
[Ue] rated operational
voltage
[Ie] rated operational
current
Motor power kW
Motor power HP (UL /
CSA)
Control circuit type
Control circuit voltage
Auxiliary contact com-
position
[Uimp] rated impulse
withstand voltage
Overvoltage category
[Ith] conventional free
air thermal current
Irms rated making ca-
pacity
Rated breaking capac-
ity
[Icw] rated short-time
withstand current
Associated fuse rating
Average impedance
TeSys D
Contactor
LC1D
Motor control
Resistive load
AC-1
AC-3
3P
3 NO
<= 690 V DC for power circuit
<= 690 V AC 25...400 Hz for power circuit
18 A (<= 60 °C) at <= 440 V AC AC-3 for power cir-
cuit
32 A (<= 60 °C) at <= 440 V AC AC-1 for power cir-
cuit
10 kW at 660...690 V AC 50/60 Hz
10 kW at 500 V AC 50/60 Hz
9 kW at 415...440 V AC 50/60 Hz
7.5 kW at 380...400 V AC 50/60 Hz
4 kW at 220...230 V AC 50/60 Hz
15 hp at 575/600 V AC 50/60 Hz for 3 phases mo-
tors
10 hp at 460/480 V AC 50/60 Hz for 3 phases mo-
tors
5 hp at 230/240 V AC 50/60 Hz for 3 phases motors
5 hp at 200/208 V AC 50/60 Hz for 3 phases motors
3 hp at 230/240 V AC 50/60 Hz for 1 phase motors
1 hp at 115 V AC 50/60 Hz for 1 phase motors
AC 50/60 Hz
24 V AC 50/60 Hz
1 NO + 1 NC
6 kV conforming to IEC 60947
III
32 A at <= 60 °C for power circuit
10 A at <= 60 °C for signalling circuit
300 A at 440 V for power circuit conforming to IEC
60947
250 A DC for signalling circuit conforming to IEC
60947-5-1
140 A AC for signalling circuit conforming to IEC
60947-5-1
300 A at 440 V for power circuit conforming to IEC
60947
84 A <= 40 °C 1 min power circuit
40 A <= 40 °C 10 min power circuit
240 A <= 40 °C 1 s power circuit
145 A <= 40 °C 10 s power circuit
140 A 100 ms signalling circuit
120 A 500 ms signalling circuit
100 A 1 s signalling circuit
35 A gG at <= 690 V coordination type 2 for power
circuit
50 A gG at <= 690 V coordination type 1 for power
circuit
10 A gG for signalling circuit conforming to IEC
60947-5-1
2.5 mOhm at 50 Hz - Ith 32 A for power circuit