GFL631T-3 INSTRUMENT TRANSFORMER, GFL631T-3 Datasheet - Page 20

GROUND FAULT CURENT

GFL631T-3

Manufacturer Part Number
GFL631T-3
Description
GROUND FAULT CURENT
Manufacturer
INSTRUMENT TRANSFORMER
Datasheet

Specifications of GFL631T-3

Accuracy
15%
Current Measuring Range Ac
30A To 360A
14
unbalance , and under and over voltage. When operating under normal power conditions, the bi-colored LED Relay Status will be green indicating the
de-energized state of the output relay.
output relay is energized and changes state. If the voltage level dips below 80% but is above 60% after the preselected time, or if the voltage exceeds 115%
for a preselected time the the output relay changes state. This output relay returns to its normal de-energized state when undervoltage returns to 90% or the
overvoltage reduces to 107%. Whenever the output relay contacts are energized indicating a fault , the bi-colored LED “ Relay Status ” will be red.
button. When the main power is restored, the output relay is energized immediately if a reset button has not been operated.
door mounted. The terminal hardware is set for panel mounting but is easily reversed for door mounting. A clear cover is provided to prevent accidental
mechanical indicator changes.
A correctly installed SPVRA Voltage Sensing Relay will protect a power system against damage due to single phase and phase loss, phase reversal, phase
If a single phase, phase sequence, phase reversal, phase loss or unbalance of 8% occurs for longer than the preselected time delay of 1 to 10 seconds, the
With the manual reset , a local reset push-button is provided on the front of the relay. Two terminals provide can be used for a normally close remote reset
The output relay has single Form C contact .
The SP VRA relay is package is in a high impact thermoplastic enclosed which can be either panel or door mounted. The terminal hardware is set for panel or
LOAD
LINE
USA, Canada, Asia, Latin America
Please refer to our website www.GEMultilin.com for more detailed contact information
e-mail: sales.multilin@ge.com
Fax: +1-905-201-2455
Tel: +1-800-547-8629
SPVRA Typical Wiring Diagram
SPVRA Operation with Options
HOW TO ORDER RELAYS
120, 208, 240, or 575Vac (60 Hz)
SPVRA - XXX
380 or 415Vac (50 Hz)
Input Voltage
1. ELECTROMECHANICAL
2. BI-Colored LED INDICATOR
3. ADJUSTABLE SYSTEM DELAY:
e-mail: gemultilin.euro@ge.com
Europe, Middle East , Africa
DIAGNOSTIC INDICATOR
Phase Loss.
Power system condition.
Normal (green)
Trip (red).
Single phase.
Phase loss.
Phase unbalance
Phase reversal
Under & over voltage.
Contacts transfer
only on a fault .
Fax: +34-94-485-88-45
Tel: +34-94-485-88-00
Electronic Products

Related parts for GFL631T-3