GFL631T-3 INSTRUMENT TRANSFORMER, GFL631T-3 Datasheet - Page 21

GROUND FAULT CURENT

GFL631T-3

Manufacturer Part Number
GFL631T-3
Description
GROUND FAULT CURENT
Manufacturer
INSTRUMENT TRANSFORMER
Datasheet

Specifications of GFL631T-3

Accuracy
15%
Current Measuring Range Ac
30A To 360A
www.GEMultilin.com
output contacts change their normal state only when a single phase, phase loss, phase unbalance, phase reversal, occurs for longer than the preset trip delay.
A total power loss de-energization of the SPVRB relay will not change the output contact position. Recommended for manually reset switches and breakers
applications. The SPVRB is suitable for loss of phase with motor loads.
Three Phase Voltage Monitor
Model SPVRB
The Model SPVRB Voltage Sensing Relay is designed to protect against single phase, phase loss, phase unbalance, phase reversal, in a power system. The
Phase Unbalance: 8 %
Adjustable Trip Delay 1 to 10 seconds after failure occurs.
Output Relay: normally de-energized: Form C
contacts for easy circuit conf iguration.
Electro - Mechanical Indicator: retains memory of fault until manually reset .
Door or Panel mounting.
Status Indicator: bi-colored LED
Single Phase, Phase Reversal, Phase Unbalance and
Phase Loss Protection: Operates the output relay after a preselected time.
Automatic or Manual mode:
Automatic mode: Upon removal of fault conditions, relay automatically resets to normal.
Manual mode: Upon removal of fault conditions, relay resets to normal after local or remote
Green: Output Relay De-energized (Normal Condition)
Red: Output Relay Energized (Fault Condition)
Dark: Output relay De-energized (Input Power Off ).
reset button has been pressed.
U L
®
103039, CANADIAN
C
®
U L
®
103039
APPLICATION:
Protection of three phase electric equipment sensitive
to damage from a phase loss or phase unbalance.
Phase reversal, phase sequence.
NORMAL INPUT VOLTAGES:
120 to 600Vac, 60Hz., 380 to 415Vac, 50Hz.
AMBIENT TEMPERATURE RANGE:
Operation: - 30
Storage - 40
Terminals screws are #6-32 nickel plated brass.
Shipping weight 2.0 lbs.
o
SPVR B-480
NUMBER
SPVRB-208
SPVR B-575
SPVRB-380
SPVRB-415
SPVRB- 120
SPVRB-240
C to + 85
MODEL
o
C to +60
10A, 1/3 H.P. AT 120 VAC
10A, 1/2 H.P. AT 240 VAC
AVAILABLE MODELS
3A, 1/2 H.P. AT 600 VAC
CONTACT RATING
o
C.
o
C.
NOMINAL
Vac
120
208
240
480
575
380
415
Hz.
60
60
60
60
60
50
50
15

Related parts for GFL631T-3