GFL631T-3 INSTRUMENT TRANSFORMER, GFL631T-3 Datasheet - Page 40

GROUND FAULT CURENT

GFL631T-3

Manufacturer Part Number
GFL631T-3
Description
GROUND FAULT CURENT
Manufacturer
INSTRUMENT TRANSFORMER
Datasheet

Specifications of GFL631T-3

Accuracy
15%
Current Measuring Range Ac
30A To 360A
34
trip power. The CTDA-6 converts ac buss voltage to dc voltage and stores enough energy to operate a lock out relay or trip a circuit breaker. Voltage is
available from the ac power supply for tripping immediately upon ac power up. The capacitors charge time is approximately 8 seconds, but full wave bridge
rectif ier power from the ac line is available immediately for use. Capacitor charge current is limited to protect the control power system from a large current in
rush. This feature allows the use of many CTDA-6 units from the same control power voltage source without coordination problems. Additionally, the CTDA-6 is
self-protected from short circuit damage on the output . Nominal ac voltage is applied across terminals #8 and # 10. This voltage is full wave bridge rectif ied
and applied across the trip capacitors producing a steady state output trip voltage. The charge stored in theses capacitors is available across terminals #12
(positive) and # 14 (negative).Charging time: 8 seconds, 0 to 90% of nominal output voltage, 60 hertz. Operating temperature: -30 deg C to +60 deg C
Electrical specif ications are 25 deg C.
Notice: Ac power must be applied continually for minimum of 2 hours before the CTDA-6 is capable of developing full charge on the output capacitors
with sustained interruption in ac input . The CTDA-6 capacitor trip device is not intended for ac dc power supply. The self-protecting feature of the unit
will severely limit the continuous output current and voltage.
Servicing:
1. Remove the AC control voltage.
2. Discharge the Capacitor trip device.
(A5-watt resistor of approximately 1000
ohms across Terminal #12 and #14
can be used for this purpose).
Danger!
Lethal voltages are present qualif ied
persons should install, operate, and
service this device.
Capacitor Trip Device
Model CTDA
APPLICATION:
Provides a source of energy
for circuit breaker in the
event of a power loss.
Tripping power is available
immediately upon
energization before
capacitors charged.
NORMAL INPUT:
120/240 Volts ac.
The
Capacitor Trip Device (CTDA-6) is used to trip circuit breakers and lock out relay when a battery standby source is not available to provide circuit breaker
-
6
USA, Canada, Asia, Latin America
Please refer to our website www.GEMultilin.com for more detailed contact information
e-mail: sales.multilin@ge.com
Fax: +1-905-201-2455
Tel: +1-800-547-8629
Specif ications
Max. Input Voltage:
2 Va burden continuous
2 Va burden continuous
Available Energy:
CTDA-6-120: 64 joules
CTDA-6-240: 57 joules
Normal Output Voltage:
CTDA-6120: 169 Vdc
CTDA-6-240: 340Vdc
Capacitance:
CTDA-6-120: 4500 uF + 20%
CTDA-6-240: 990 uF+ 20%
Approx charge time to 90% at 60Hz. is 8 seconds.
e-mail: gemultilin.euro@ge.com
Europe, Middle East , Africa
Fax: +34-94-485-88-45
Tel: +34-94-485-88-00
U L
®
IND. CONT. EQUIP.
LISTED
Operating temperature range:
-30
Storage temp range:
-50
Short Circuit Protection:
Continuous
Mounting:
Vertical or horizontal
Input Surge Protection:
MOV protected to 65 joules puls e surge
o
o
C to 60
C to 80
C
U L
®
o
o
C
C
FILE NO.
E103039
Electronic Products
*