GFL631T-3 INSTRUMENT TRANSFORMER, GFL631T-3 Datasheet - Page 9

GROUND FAULT CURENT

GFL631T-3

Manufacturer Part Number
GFL631T-3
Description
GROUND FAULT CURENT
Manufacturer
INSTRUMENT TRANSFORMER
Datasheet

Specifications of GFL631T-3

Accuracy
15%
Current Measuring Range Ac
30A To 360A
www.GEMultilin.com
This GFM systems is designed for all polyphase applications and is ideally suited for motor control, motor control centers, and high voltage starters. System
can be wye or delta, ground or resistance grounded. When the ground fault current exceed a pre-selected condition (current and time setting) the relay trips.
The relay contacts can be connected in the control circuit of a motor starter, to the shunt trip of a circuit breaker or similar disconnecting or alarm devices. The
system has an inverse time characteristic to prevent nuisance tripping. The relay tripping current value is f ield adjustable over the trip current range of the
sensor. The adjustable trip time delay relay is f ield setable up 36 cycle.
Ground Fault Current Detection Systems
Model GFM (Relay)
1.5 to 65 Amp Trip Currents
ADJUSTABLE OPERATING RANGE:
Trip currents from 1.5 to 65 Amperes.
Time delay from instantaneous to 36 cycles.
INPUT POWER:
FREQUENC Y:
AMBIENT TEMPERATURE RANGE:
-30
Positive “ON” (Green)
and “OFF” (Red) condition
indication, manual reset .
SPD T contacts:
Form C, rated 10 Amps
continuous, 23 Amps inrush,
250 volts ac.
Only for use with GFM sensors.
The class 1 model GFM Ground Fault protection systems are designed to minimize damage or loss to equipment caused by destructive arcing ground faults.
o
C to +60
Model GFM - 252 & Model 262
Push Button (P .B.) Style Door Mount .
o
C
Self powered.
50/60 Hz.
Model GFM - 252 & Model 262
Model GFM - 353, 363,453, and 463
Rear terminal kit and clear plastic cover standard with door mounting.
U L
®
110395
LR80793
Model GFM - 353, 363,453, and 463
3