3G3JX-AE022 Omron, 3G3JX-AE022 Datasheet - Page 27

AC Motor Drive

3G3JX-AE022

Manufacturer Part Number
3G3JX-AE022
Description
AC Motor Drive
Manufacturer
Omron
Datasheet

Specifications of 3G3JX-AE022

Supply Voltage Range
200V To 240V
No. Of Phases
Single Or Three
Power Rating
2200W
Output Voltage Max
240V
Output Frequency Max
400Hz
Mounting Type
DIN Rail
Output Voltage Min
200V
External Height
189mm
Frequency Range
0.5 To 400Hz
Rohs Compliant
Yes
External Depth
157.5mm
External Width
110mm
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Protective and Diagnostic Functions
●Error Code List
*1.
*2.
*3.
*4.
*5.
*6.
Display on Digital Operator
data initialization or copying.
to release the trip.
monitor.
After a trip occurs, normal operation is restored in 10 seconds by resetting.
Check the set data again if the EEPROM error
If the power is shut off during data initialization, an EEPROM error
If an undervoltage trip
The ground fault trip
If the multi-function output (relay output) is set to 05 (alarm), the signal may not be output during the CPU error
ek k0k1
ek k0k2
ek k0k3
ek k0k4
ek k0k5
ek k0k6
ek k0k7
ek k0k8
ek k0k9
ek k1k1
ek k2k2
ek k1k2
ek k1k3
ek k1k4
ek k1k5
ek k2k1
ek k2k3
ek k3k5
ek k1k4
ek k0k9
Overcurrent trip
Overload trip
Braking resistor overload
trip
Overvoltage trip
EEPROM error
Undervoltage trip
CPU error
External trip
USP trip
Ground fault trip
Incoming overvoltage trip
Temperature error
Gate array error
Thermistor error
(Available when the
thermistor trip function is
used)
cannot be released with the reset input. Shut off the power and check the wiring.
occurs with the USP terminal set to ON, the trip, after released by resetting, becomes a USP error
*4
Name
*6
*1
*2 *3
*5
ek k0k8
Multi-functional Compact Inverters SYSDRIVE
Constant
speed
Deceleration
Acceleration
Others
If an Inverter output current is detected and the motor is overloaded, an electronic thermal inside the
Inverter works to shut off the Inverter output.
When the usage rate of the braking resistor is exceeded, this function detects overvoltage due to
operation stop of the control circuit and shuts off the Inverter output.
If the incoming voltage and regenerative energy from the motor are too high, a protection circuit works
to shut off the Inverter output when the voltage on the converter exceeds the specified level.
Shuts off the output if an error occurs in the EEPROM built into the Inverter due to external noise and
abnormal temperature rise.
Shuts off the output if the incoming voltage drops below the specified level, causing the control circuit
not to work properly during a momentary power interruption.
Shuts off the output if the internal CPU has worked erroneously or abnormally.
If an error occurs in the external equipment or devices, the Inverter receives the signal, and the output
is shut off.
(Available with the external trip function selected)
Appears if the Inverter is turned on with the RUN command being input. (Available with the USP
function selected)
Shuts off the output if a ground fault between the Inverter output unit and the motor is detected when
turning on the power.
Appears if the incoming voltage has remained high for 100 seconds while the Inverter output is
stopped.
Shuts off the output if the temperature has risen in the main circuit due to malfunction of the cooling fan
or other reason.
Displayed when a fault is detected in communication behavior between the built-in CPU and the gate
array.
Detects the resistance of the external thermistor and shuts off the Inverter output.
occurs.
ek k0k8
If the motor is restrained or rapidly accelerated or decelerated, a large current will flow
through the Inverter, which will result in breakage.
To avoid this, an overcurrent protection circuit works to shut off the Inverter output.
may occur when the power is next turned on. Shut off the power after completing
Description
ek k2k2
. In this case, no data is stored in the trip
MX
Series
ek k1k3
. Reset again