3G3JX-AE022 Omron, 3G3JX-AE022 Datasheet - Page 35

AC Motor Drive

3G3JX-AE022

Manufacturer Part Number
3G3JX-AE022
Description
AC Motor Drive
Manufacturer
Omron
Datasheet

Specifications of 3G3JX-AE022

Supply Voltage Range
200V To 240V
No. Of Phases
Single Or Three
Power Rating
2200W
Output Voltage Max
240V
Output Frequency Max
400Hz
Mounting Type
DIN Rail
Output Voltage Min
200V
External Height
189mm
Frequency Range
0.5 To 400Hz
Rohs Compliant
Yes
External Depth
157.5mm
External Width
110mm
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Common Specification
Item
Enclosure rating
Cooling method
Control method
Output frequency range
Frequency precision
Frequency resolution
Voltage/Frequency characteristics
Speed fluctuation
Overload current rating
Acceleration/Deceleration time
Starting torque
DC injection braking
Input
Output
Display monitor
Other functions
Carrier frequency modification range
Protective functions
Multi-function input
Thermistor input terminal 1 terminal (Positive/Negative temperature coefficient of resistance element switchable)
Multi-function output
Multi-function monitor
output terminal
IP20
Forced air cooling
Phase-to-phase sinusoidal modulation PWM
0.1 to 400Hz
Digital command: ±0.01% of the max. frequency
Analog command: ±0.2% of the max. frequency (25°C ±10°C)
Digital setting: 0.01 Hz
Analog setting: Max. frequency/4000
(Terminal FV: 12 bits/0 to +10 V), (Terminal FV2: 12 bits/−10 to +10 V),
(Terminal FI: 12 bits/0 to +20 mA)
V/f optionally changeable at base frequencies of 30 to 400 Hz, V/f braking constant torque, reduction torque, sensorless
vector control, sensor-less vector control at 0 Hz
±0.5% (under sensor-less vector control or sensorless vector control at 0 Hz)
150%/60 s, 200%/3 s
0.01 to 3600.0 s (line/curve selection)
200%/0.3 Hz
(under sensorless vector control or sensor-less vector control at 0 Hz)
150%/Torque at 0 Hz (under sensor-less vector control at 0 Hz, or when the motor with one frame fewer than the
maximum applicable motor is connected)
Operates when the starting frequency is lower than that in deceleration via the STOP command, when the frequency
reference is lower than the operation frequency, or via an external input (braking power, time, and frequency settable)
8 terminals, NO/NC switchable, sink/source logic switchable
[Terminal function] 8 functions can be selected from among 60.
Reverse (RV), Multi-step speed 1 (CF1), Multi-step speed 2 (CF2), Multi-step speed 3 (CF3), Multi-step speed 4 (CF4),
Jogging (JG), External DC injection braking (DB), 2nd control (SET), 2-step acceleration/deceleration (2CH), Free-run
stop (FRS), External trip (EXT), USP function (USP), Commercial switch (CS), Soft lock (SFT), Analog input selection
(AT), 3rd control (SET3), Reset (RS), 3-wire startup (STA), 3-wire stop (STP), 3-wire forward/reverse (F/R), PID disabled
(PID), PID integral reset (PIDC), Control gain switching (CAS), Remote operation accelerated (UP), Remote operation
decelerated (DWN), Remote operation data clear (UDC), Forced operator (OPE), Multi-step speed bit 1 (SF1),
Multi-step speed bit 2 (SF2), Multi-step speed bit 3 (SF3), Multi-step speed bit 4 (SF4), Multi-step speed bit 5 (SF5),
Multi-step speed bit 6 (SF6), Multi-step speed bit 7 (SF7), Overload limit switching (OLR), Torque limit enabled (TL),
Torque limit switching 1 (TRQ1), Torque limit switching 2 (TRQ2), P/PI switching (PPI), Brake confirmation (BOK),
Orientation (ORT), LAD cancel (LAC), Position deviation clear (PCLR), Pulse train position command input permission
(STAT), Frequency addition function (ADD), Forced terminal (F-TM), Torque reference input permission (ATR),
Integrated power clear (KHC), Servo ON (SON), Preliminary excitation (FOC), General-purpose input 1 (MI1),
General-purpose input 2 (MI2), General-purpose input 3 (MI3), General-purpose input 4 (MI4), General-purpose input 5
(MI5), General-purpose input 6 (MI6), General-purpose input 7 (MI7), General-purpose input 8 (MI8), Analog command
held (AHD), No allocation (no)
5 open collector output terminals: NO/NC switchable, sink/source logic switchable
1 relay (SPDT contact) output terminal: NO/NC switchable
[Terminal function] 6 functions can be selected from among 43.
During operation (RUN), Constant speed reached (FA1), Set frequency exceeded (FA2), Overload warning (OL),
Excessive PID deviation (OD), Alarm signal (AL), Set frequency only (FA3), Overtorque (OTQ), Signal during
momentary power interruption (IP), Signal during undervoltage (UV), Torque limit (TRQ), RUN time over (RNT),
Power ON time over (ONT), Thermal warning (THM), Brake release (BRK), Brake error (BER), Zero-speed signal (ZS),
Excessive speed deviation (DSE), Position ready (POK), Set frequency exceeded 2 (FA4), Set frequency only 2 (FA5),
Overload warning 2 (OL2), PID FB status output (FBV), Network error (NDc), Logic operation output 1 (LOG1), Logic
operation output 2 (LOG2), Logic operation output 3 (LOG3), Logic operation output 4 (LOG4), Logic operation output 5
(LOG5), Logic operation output 6 (LOG6), Capacitor life warning (WAC), Cooling fin overheat warning (WAF), Starting
contact signal (FR), Cooling fin overheat warning (OHF), Low current signal (LOC), General-purpose output 1 (MO1),
General-purpose output 2 (MO2), General-purpose output 3 (MO3), General-purpose output 4 (MO4), General-purpose
output 5 (MO5), General-purpose output 6 (MO6), Operation ready (IRDY), During forward operation (FWR),
During reverse operation (RVR), Fatal fault (MJA), Alarm codes 0 to 3 (AC0 to AC3)
Analog voltage output, Analog current output,
Pulse train output (A-F, D-F {multiplied by "n", pulse output only}, A, T, V, P, etc.)
Output frequency, Output current, Output torque, Frequency conversion value, Trip record, I/O terminal status,
Electric power, etc.
V/f free setting (7), Upper/lower frequency limit, Frequency jump, Curve acceleration/deceleration, Manual torque boost
level/break, Energy-saving operation, Analog meter adjustment, Starting frequency, Carrier frequency adjustment,
Electronic thermal function, (free setting available), External start/end (frequency/rate), Analog input selection, Trip retry,
Restart during momentary power interruption, Various signal outputs, Reduced voltage startup, Overload limit,
Initialization value setting, Automatic deceleration at power-off, AVR function, Fuzzy acceleration/deceleration, Auto
tuning (Online/Offline), High-torque multi-operation control (sensor-less vector control of two monitors with one Inverter)
0.5 to 15 kHz
Overcurrent protection, Overvoltage protection, Undervoltage protection, Electronic thermal protection, Temperature
error protection, Momentary power interruption/Power interruption protection, Input open-phase protection, Braking
resistor overload protection, Ground-fault overcurrent detection at power-on, USP error, External trip, Emergency shutoff
trip, CT error, Communication error, Option error, etc.
Advanced General-purpose Inverters SYSDRIVE
Specifications
RX
Series
43