2510KG1 SQUARE D, 2510KG1 Datasheet - Page 3

Motor Starter

2510KG1

Manufacturer Part Number
2510KG1
Description
Motor Starter
Manufacturer
SQUARE D
Datasheet

Specifications of 2510KG1

No. Of Phases
Single
Power Rating
3hp
Current Rating
30A
Peak Reflow Compatible (260 C)
No
Contactor Direction
Non Reversing
Frame Size
Standard
Load Voltage Max
600VAC
Leaded Process Compatible
No
Supply Voltage Range
115VAC To 230VAC / 460VAC To 575VAC
Rohs Compliant
No
Current Max (full Load)
30A
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Type FG2P
12/97
Type FO2
FRACTIONAL HORSEPOWER MANUAL STARTERS
WITH MELTING ALLOY TYPE THERMAL OVERLOAD RELAY
Application Data
Type F fractional horsepower starters provide overload protection as well as manual “On-Off” control for
small motors in a variety of industrial and commercial installations. Typical applications include fans,
conveyors, pumps, and small machine tools.
They are available in one or two pole versions. Both one-pole and two-pole versions are suitable for use
with AC single phase motors rated up to 1 horsepower. Two-pole starters may also be used with DC
motors rated up to 0.75 horsepower.
Voltage Rating
Horsepower Ratings
Continuous Current Rating
Enclosures
Pilot Light
Handle Guard/Lock-Off
Terminals
Mounting
Operator
Thermal Units
© 1997 Square D All Rights Reserved
230 VDC maximum (2 pole only)
thermoplastic wrap-around cover for convenience in wiring. The NEMA
Type 1 enclosure is also available in an oversized version that allows
more space for wiring. A zinc alloy die casting is used for NEMA Type 4
enclosures, and a cast aluminum enclosure is offered for NEMA Type
3R, 7 & 9 applications.
NEMA Type 1 surface and flush mounting and NEMA Type 4
enclosures. They are also available as a field modification kit for NEMA
Type 1 enclosures and gray flush plates.
Use order number as is for red pilot light; add a G to the number for a
green pilot light.
accidental operation of the toggle operator and allows the toggle
operator to be padlocked in either the On or Off position.
The handle guard can be factory installed on NEMA Type 1 enclosed
starters. It is also available in kit form for field installation on NEMA Type
1 surface and flush mounting enclosures. Standard NEMA Type 4 and
NEMA Type 3R, 7 & 9 enclosures include provision for locking in the Off
position.
wire, and are accessible from the front. All terminals are clearly marked.
and can be used with any cover plate having a standard toggle cutout.
Single-unit flush mounting types, including those with pilot light, are
suitable for wall mounting in a standard switch box or for machine cavity
mounting without a box.
discourage unauthorized operation.
thermal units so that the markings face the front of the starter.
277 VAC maximum (1 or 2 pole)
16 A
NEMA Type 1 surface mounting enclosures are sheet steel with a
Red or green neon pilot light units are available factory installed in
An optional handle guard on NEMA Type 1 enclosed starters prevents
Binder head screw type terminals are suitable for #10 or smaller copper
Open types without a pilot light fit standard single gang switch boxes,
Available with toggle handle or with removable key type operator to
Starters will not operate without properly installed thermal units. Install
115 to 230
Volts
277
1 Pole
1
1
AC Single Phase
Maximum Horsepower
Class 2510, 2512 Type F
2 Pole
1
1
2 Pole Only
DC
3
/
4
3