AFPX-E16T PANASONIC EW, AFPX-E16T Datasheet - Page 10

Compact Brick Style PLC Expansion Unit

AFPX-E16T

Manufacturer Part Number
AFPX-E16T
Description
Compact Brick Style PLC Expansion Unit
Manufacturer
PANASONIC EW
Datasheet

Specifications of AFPX-E16T

Controller Output Type 1
Transistor
No. Of Inputs
8
No. Of Outputs
6
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
10
"Require slightly more functions", "Want to add functions to the existing equipment"
- The rich variety of expansion boards helps solve these requirements.
Expansion
I The
I When further expansion or functions are required, use the existing
The add-on cassette can be mounted onto the control unit easily.
Up to 2 cassettes on C14 or up to 3 cassettes on C30/C60 can be mounted.
Only communication cassette can be double-stacked upper side. (Communication cassette should be only one totally.)
Note) Please refer to the manual for the number of mountable units and position.
All control units can be expanded by up to 3 FP0 expansion units via an adapter.
Applications can be expanded by using [Transistor outputs], [Analog input/outputs],
[Thermocouple input] and [I/O link (network)].
When further expansion or functions are required, use the existing FP0 expansion unit.
* Only one expansion FP0 adapter unit can be attached to a control unit.
*1: Each of RS485 and RS422 is an insulated type.
Up to 7 FP-X expansion units can be used when the expansion FP0 adapter is attached.
Product number
FP0-E8X
FP0-E16X
FP0-E8YT
FP0-E8YRS
FP0-E16YT
FP0-E32T
FP0-E8RS
FP0-E16RS
Cannot be used with a
transistor output type
DC input
Transistor output
Pulse I/O
AFPX-PLS
Analog input
AFPX-AD2
Master memory
AFPX-MPTC
Add-on cassette
Add-on Cassette
AFPX-COM1
AFPX-COM2
AFPX-COM3
AFPX-COM4
AFPX-COM5
8 ch. DC input, MIL connector
16 ch. DC input, MIL connector
8 ch. transistor output, MIL connector
8 ch. relay output, screw terminal block
16 ch. transistor output, MIL connector
16 ch. DC input, 16 ch. transistor output,
MIL connector
4 ch. DC input, 4 ch. relay output,
screw terminal block
8 ch. DC input, 8 ch. relay output,
screw terminal block
AFPX-TR8
AFPX-IN8
C60
Specifications
24 V DC input, 8 ch., bidirectional input (sync/source)
NPN, 8 ch., 0.3 A
High-speed counter input
➔ Single-phase 2 ch. 80 kHz or two-phase
Pulse output
➔ Single-axis 100 kHz (CW/CCW, Pulse+Sign)
2 ch., 12 bits (non-insulated), 2 ms/2 ch.
0 to 10 V or 0 to 20 mA
32-kstep program storage and transfer
Calendar timer
RS232C
RS232C
RS485/RS422 selectable
RS485 + RS232C
Ethernet 1ch + RS232C 1 ch (Available April 2007)
1 ch. 30 kHz
E30
easily adds small quantities of functions and I/O points.
Max. 7 units (210 points)
*2 Provided from Panasonic Electric Works Europe AG
Product number
FP0-A21
FP0-A80
FP0-A04V
FP0-A04I
FP0-TC4
FP0-TC8
FP0-IOL
FP0-CCL
FP0-E32RS*
FP0-RTD6*
FP0-DPS2*
*1
Specifications
*1
E30
2
2
2
1 ch.
2 ch.
1 ch.
1 ch. each
Analog 2 ch. input, 1 ch. output
Analog 8 ch. input
Analog (voltage) 4 ch. output
Analog (current) 4 ch. output
Thermocouple 4 ch. input
Thermocouple 8 ch. input
I/O link unit
CC-link unit
16ch DC input, 16ch relay output
screw terminal block
6ch RTD input
PROFIBUS remote I/O unit
Specifications
Max. 96 points
FP0 expansion unit.
Expansion FP0 adapter (AFPX-EFP0)
The unified unit height of 90 mm makes
the panel surface look clean.
Easily removable
(Two screws to secure the unit)

Related parts for AFPX-E16T