PAXDR000 Red Lion Controls, PAXDR000 Datasheet

no-image

PAXDR000

Manufacturer Part Number
PAXDR000
Description
AC, Dual Rate, Upgradeable Red
Manufacturer
Red Lion Controls
Type
Rate/Totalizerr
Datasheet

Specifications of PAXDR000

Accuracy
± (0.01% of Input Signal Frequency)
Cut Out, Panel
3.62W x 1.77H Inches
Dimensions
3.80W x 1.95H Inches
Display Digit Height
.56 Inches
Display Type
LED Adjustable
Function
Rate/Totalizer
Input Type
Switch Selectable Pulse
Keypad Type
3 Programmable Function (5 Keys Total)
Number Of Digits
Rate = 5, Totalizer = 8
Primary Type
Electronic
Range, Measurement
Rate = 0 to 99999, Totalizer = ±99999999
Special Features
Programmable Function Keys
Termination
Cage Clamp
Voltage, Supply
85 to 250 VAC
Lead Free Status / Rohs Status
RoHS Compliant part
Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net
MODEL PAXDR - 1/8 DIN DUAL RATE METER / TOTALIZER
GENERAL DESCRIPTION
single meter. Two Rate and two Total displays are provided (A and B), along
with two additional calculation displays (C) to show the Sum, Difference, Ratio,
% of Total or Draw between A and B displays. Any of the six displays are
viewable: A, B or C Rate and A, B or C Total. The meter’s LED display has
0.56" digits, available in red sunlight readable or standard green. The display
intensity is adjustable for low level lighting conditions up to sunlight readable
applications.
derived. For the Rate displays, up to 10 point scaling is provided for each input,
to scale non-linear rate processes. Separate scaling is provided for both the A
and B Totalizers. The independent scaling allows for Rate only, Totalizer only
or combination Rate/Totalizer applications, with or without the calculation
displays.
where both flow rate and flow volume are measured. Two separate flow lines
can be monitored simultaneously, each scaled to convert flow to a common unit
of measure. Flow rate is easily scaled to read flow per time period (sec/min/hr).
The flow rate and volume for each line can be shown, as well as the Sum,
Difference, Ratio, etc. between the two lines for flow rate and/or volume. A
different calculation function may be used for Rate and Total if desired.
and communications capability. The Plug-in setpoint cards provide dual
FORM-C relays (5 A), quad FORM-A relays (3 A), or either quad sinking or
quad sourcing open collector logic outputs. The outputs can be assigned to any
of the Rate or Totalizer display values, and configured to suit a variety of control
and alarm requirements.
DIMENSIONS In inches (mm)
The PAXDR is a 5-digit Dual Rate Indicator and 6-digit Dual Totalizer in a
The meter has two signal inputs from which the Rate and Totalizer values are
While suitable for many applications, this meter is ideal for flow measurement
Optional plug-in cards provide up to four setpoint outputs, a linear DC output
C
A
B
8. 8 . 8 . 8 . 8 . 8
SP1
DSP
PAR
SP2
(96.5)
3.80
F1
SP3
F2
SP4
RST
(49.5)
1.95
(2.5)
.10
Note: Recommended minimum clearance (behind the panel) for
mounting clip installation is 2.1" (53.4) H x 5" (127) W.
(104.1)
4.10
1
output can be scaled independent of the input range and can track any of the
Rate or Totalizer displays.
These include RS232, RS485, Modbus, DeviceNet and Profibus-DP. Readout
values and setpoint alarm values can be controlled through the bus. Additionally,
the meter has a feature that allows a remote serial device to directly control the
meter outputs.
specifically designed for harsh industrial environments. With NEMA 4X/IP65
sealed bezel and extensive testing to meet CE requirements, the meter provides
a tough yet reliable application solution.
SAFETY SUMMARY
literature or on equipment must be observed to ensure personal safety and to
prevent damage to either the instrument or equipment connected to it. If
equipment is used in a manner not specified by the manufacturer, the protection
provided by the equipment may be impaired.
not equipped with safeguards. To do so can be potentially harmful to persons or
equipment in the event of a fault to the meter.
 SIX DISPLAYS - ONE EACH FOR: RATE A & B; TOTALIZER A & B;
 DISPLAY C CALCULATIONS: SUM (A+B), DIFFERENCE (A-B),
 0.56" RED SUNLIGHT READABLE DISPLAY
 VARIABLE INTENSITY DISPLAY
 10 POINT NON-LINEAR SCALING FOR BOTH RATE DISPLAYS
 SEPARATE INPUT SCALING FOR A AND B TOTALIZERS
 PROGRAMMABLE FUNCTION KEYS/USER INPUTS
 FOUR SETPOINT ALARM OUTPUTS (W/Option Card)
 RETRANSMITTED ANALOG OUTPUT (W/Option Card)
 COMMUNICATION AND BUS CAPABILITIES (W/Option Card)
 NEMA 4X/IP65 SEALED FRONT BEZEL
The linear DC output Plug-in card provides either 20 mA or 10 V signals. The
Communication and Bus Capabilities are also available as option cards.
The PAXDR is available in AC or DC powered versions. The meter has been
All safety related regulations, local codes and instructions that appear in this
Do not use this meter to directly command motors, valves, or other actuators
DISPLAY C RATE CALCULATION & TOTALIZER CALCULATION
RATIO (A/B), % OF TOTAL (A/A+B) OR DRAW (A-B/B)
installation and operation of the unit.
Read complete instructions prior to
CAUTION: Risk of Danger.
(44.5)
1.75
1
2
3
4
5
3.60 (91.4)
6
7
12
13
14
15
8
9
CAUTION: Risk of electric shock.
10
16
17
18
19
11
Bulletin No. PAXDR-X
Drawing No. LP0812
Effective 09/09
20
21
22
23
24
25
(44.5)
1.75

Related parts for PAXDR000

PAXDR000 Summary of contents

Page 1

Tel +1 (717) 767-6511 Fax +1 (717) 764-0839 www.redlion.net MODEL PAXDR - 1/8 DIN DUAL RATE METER / TOTALIZER GENERAL DESCRIPTION The PAXDR is a 5-digit Dual Rate Indicator and 6-digit Dual Totalizer in a single meter. Two Rate and ...

Page 2

ABLE F ONTENTS Ordering Information . . . . . . . . . . . . . . . . . . . . 2 Meter Specifications . . . . . . . . . ...

Page 3

M S ETER PECIFICATIONS 1. DISPLAY: 6 digit, 0.56" (14.2 mm) red sunlight readable or standard green LED, intensity adjustable. 2. POWER: AC Versions: AC Power 250 VAC, 50/60 Hz Isolation: 2300 Vrms for 1 min. ...

Page 4

O P PTIONAL LUG WARNING: Disconnect all power to the unit before installing Plug-in cards. Adding Option Cards The PAX and MPAX series meters can be fitted with up to three optional plug- in cards. The details for each plug-in ...

Page 5

I NSTALLING THE Installation The PAX meets NEMA 4X/IP65 requirements when properly installed. The unit is intended to be mounted into an enclosed panel. Prepare the panel cutout to the dimensions shown. Remove the panel latch from the unit. ...

Page 6

I NSTALLING The Plug-in cards are separately purchased optional cards that perform specific functions. These cards plug into the main circuit board of the meter. The Plug-in cards have many unique functions when used with the PAX. The literature ...

Page 7

W IRING THE WIRING OVERVIEW Electrical connections are made via screw-clamp terminals located on the back of the meter. All conductors should conform to the meter’s voltage and current ratings. All cabling should conform to appropriate standards of good ...

Page 8

INPUT WIRING CAUTION: Sensor input common is NOT isolated from user input common. In order to preserve the safety of the meter application, the sensor input common must be suitably isolated from hazardous live earth referenced voltage; or input ...

Page 9

SERIAL COMMUNICATION WIRING RS232 Communications PAX METER (DTE) TXD RXD 12 RXD TXD 13 COMM RS232 Terminal Block Connection Figure 5 9 PIN 2 TXD 6 1 PIN 3 RXD PIN 5 COMMON FEMALE Extended Comms ...

Page 10

P ROGRAMMING THE DISPLAY MODE PAR NO User Input/ Rate Function Setup Key Parameters Parameters Pro F1/F2 Keys PAR PAR 1-rAtE 2-FNC PROGRAMMING MODE ENTRY (PAR KEY) The meter normally operates in the Display Mode. No parameters can be ...

Page 11

MODULE 1-rAtE PAR LO-Udt HI-Udt C rAtE C SCLr Low Update High Update Rate C Rate C Display Time Time Calculation Multiplier Module 1 is the programming for the Rate parameters. The Rate A signal is ...

Page 12

Non-linear Application – Scaling Points Non-linear processes may utilize up to nine segments (ten scaling points) to provide a piece-wise linear approximation representing the non-linear function. The Rate display will be linear throughout each individual segment (i.e. ...

Page 13

RATE B DISPLAY VALUE FOR SCALING POINT 2     to   Enter the desired Rate B Display Value for the second Scaling Point by using the arrow keys. RATE B INPUT VALUE FOR SCALING POINT 2 ...

Page 14

MODULE 2-FNC PAR USr-1 USr-2 USr-3 USER INPUTS Module 2 is the programming for rear terminal user inputs and front panel function keys. Three rear terminal user inputs are individually programmable to perform specific meter control ...

Page 15

TOTALIZER MAINTAINED (LEVEL) RESET AND INHIBIT     The meter performs a reset and inhibits the totalizer displays configured long as activated (maintained action).  DISPLAY DESCRIPTION  Totalizer A  Totalizer B TOTALIZER MOMENTARY ...

Page 16

MODULE 3-LOC PAR x x rAtE tot Rate x Totalizer x Display Display Lock-out Lockout Module 3 is the programming for Display lock-out and “Full” and “Quick” Program lock-out. When in the Display Mode, the available ...

Page 17

MODULE 4-tot PAR x tot xrESEt Totalizer x Totalizer x Operating Reset Action x = Totalizer Mode Module 4 is the programming for Totalizer A and Totalizer B. Totalizer B parameters follow Totalizer ...

Page 18

TOTALIZER B OPERATING MODE         Select the operating mode for Totalizer B. SELECTION MODE DESCRIPTION  Does not count.  Count X1 Adds Input B falling edge.  Count X1 Adds Input B ...

Page 19

MODULE 5-totC PAR C tot CdECPt Totalizer C Totalizer C Calculation Decimal Position Module 5 is the programming for Totalizer C. For maximum input frequency, the Totalizer C Calculation should be set to  the remaining ...

Page 20

MODULE 6-SPt PAR SPSEL OUt-n LIt-n Setpoint Output Setpoint Select Logic Annunciator PAR Stb-n HYS-n tOFF-n Standby Setpoint Off Time Operation Hysteresis Module 6 is the programming for the setpoint (alarms) output parameters. To have setpoint ...

Page 21

SETPOINT ACTION       : When not using a setpoint, it should be set to  For Rate Assignments: Refer to diagrams “Setpoint (Alarm) Figures for Rate” on page 22.  With Latch action, the setpoint ...

Page 22

TOTALIZER AUTO RESET        This parameter automatically resets the Setpoint Assigned Totalizer ( each time the setpoint value is reached. The automatic reset can occur at output start ( ) or output ...

Page 23

MODULE 7-SrL PAR bAUd dAtA Baud Rate Data Bit PAR A rAtE b rAtE Print Print Rate A Rate B Module 7 is the programming module for the Serial Communications Parameters. These parameters are used to ...

Page 24

SENDING SERIAL COMMANDS AND DATA When sending commands to the meter, a string containing at least one command character must be constructed. A command string consists of a command character, a value identifier, numerical data (if writing data to the ...

Page 25

Auto/Manual Mode Register (MMR) ID: U This register sets the controlling mode for the outputs. In Auto Mode (0) the meter controls the setpoint and analog output. In Manual Mode (1) the outputs are defined by the registers SOR and ...

Page 26

COMMUNICATION FORMAT Data is transferred from the meter through a serial communication channel. In serial communications, the voltage is switched between a high and low level at a predetermined rate (baud rate) using ASCII encoding. The receiving device reads the ...

Page 27

MODULE Pro 9-FCS PAR d-LEV COdE Display Factory Intensity Level Service Code DISPLAY INTENSITY LEVEL  Enter the desired Display Intensity Level (0-15) by  using the arrow keys. The display will actively dim or  ...

Page 28

PARAMETER VALUE CHART PAXDR Model Number _________ Meter# _____________ Security Code __________  Rate Setup Parameters DISPLAY PARAMETER  LOW UPDATE TIME  HIGH UPDATE TIME  RATE C CALCULATION  RATE C DISPLAY MULTIPLIER**  RATE C DECIMAL POSITION** ...

Page 29

Totalizer C Setup Parameters DISPLAY PARAMETER  TOTALIZER C CALCULATION  TOTALIZER C DECIMAL POSITION  TOTALIZER C SCALE FACTOR (A) TOTALIZER C SCALE FACTOR (B)*  TOTALIZER C SCALE MULTIPLIER  TOTALIZER C RESET AT POWER-UP * See ...

Page 30

This page intentionally left blank ...

Page 31

PAXDR PROGRAMMING QUICK OVERVIEW 31 ...

Page 32

... The Company disclaims all liability for any affirmation, promise or representation with respect to the products. The customer agrees to hold Red Lion Controls harmless from, defend, and indemnify RLC against damages, claims, and expenses arising out of subsequent sales of RLC products or products containing components manufactured by RLC and based upon personal injuries, deaths, property ...