LPS58-M Emerson Network Power, LPS58-M Datasheet

POWER SUPPLY, SWITCH MODE, 48V

LPS58-M

Manufacturer Part Number
LPS58-M
Description
POWER SUPPLY, SWITCH MODE, 48V
Manufacturer
Emerson Network Power
Datasheet

Specifications of LPS58-M

Power Supply Type
Open Frame
Power Supply Output Type
Fixed
No. Of Outputs
1
Output Voltage
48V
Output Current
1.25A
Power Rating
60W
Input Voltage
90V AC To 264V AC / 127V DC To 300V DC
Commercial/medical
Medical
Output Power Rating
60 W
Number Of Outputs
1
Output Voltage (channel 1)
48 VDC
Output Current (channel 1)
1.25 A
Open Frame/enclosed
Open Frame
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
LPS50-M Series
60 Watts
Special Features
• Medical Safety Approvals
• Universal input
• Less than 1U high
• 2” x 4” footprint
• Remote sense
• Overload and short circuit
• Adjustable output voltage
• High efficiency
• High MTBF
• Built in EMI filter
• LED power good indicator
• Input power < 74 watts
• Complies with EN61000 -3-2
• UL Class I approved
• LPX50 enclosure kit available
• Dual AC fuses
Safety
Total Power:
Input Voltage:
# of Outputs:
protection
(CISPR 22 Class B)
UL:
CSA: CSA-C22.2 No. 601.1-M90
VDE: EN60601-1
CE:
UL 60601-1
LVD & EMC
55 - 60 Watts
90 - 264 VAC
127 - 300 VDC
Single
Electrical Specifications
Input
Input range:
Frequency:
Inrush current:
Input power:
Efficiency:
EMI/RFI:
Safety ground leakage
current:
Output
Maximum power:
Adjustment range:
Hold-up time:
Overload protection:
Overvoltage protection: 30-50% above nominal output
Remote sense:
90 - 264 VAC (wide range) 127-300 Vdc
47-440 Hz
< 60 A peak @ 230 VAC, cold start @ 25°C
< 74 Watts
80% - 85% typical at full load
FCC Class B conducted; CISPR 22 Class B conducted; EN55022 Class B
conducted, VDE0878PT3 Class B conducted
275uA @ 50/60 Hz; 264 VAC input
60W for convection (LPS52, 55 W)
±20% minimum
10/ 2 0 ms 115/230 VAC input line
Short circuit protection on all outputs. Case overload protected @
110-160% of normal rating
Compensatesd for 0.5 V lead drop max. Will operate without remote sense
connected. Reverse connection protected.
Embedded Power for
Business-Critical Continuity
Rev. 1.08.09_149
LPS50-M Series
1 of 3

Related parts for LPS58-M

LPS58-M Summary of contents

Page 1

LPS50-M Series 60 Watts Total Power Watts Input Voltage 264 VAC 127 - 300 VDC # of Outputs: Single Special Features • Medical Safety Approvals • Universal input • Less than 1U high • 2” x 4” footprint • Remote sense • Overload and short circuit protection • Adjustable output voltage • High efficiency • High MTBF • Built in EMI filter (CISPR 22 Class B) • LED power good indicator • Input power < 74 watts • Complies with EN61000 -3-2 • UL Class I approved • LPX50 enclosure kit available • Dual AC fuses Safety UL 60601-1 ...

Page 2

Environmental Specifications Operating temperature: 0° °C ambient derate each output as 2.5% per degree from 50° °C. -20 °C start up Storage temperature: -40 °C to +85 °C Electromagnetic susceptibility: Designed to meet EN61000-4; -2, -3, -4, -5, -6, -8, -11 Level 3 Humidity: Operating; non-condensing 10% to 95% RH Vibration: IEC68-2-6 to the levels of IEC721-3-2 MTBF demonstrated: > 550,000 hours at full load and 25 °C ambient conditions Mechanical Drawing M1 GRN DB1 YEL TP1 GND SK1 T3.15A 2. 250VAC 2005 0.197” (5.0) Minimum ...

Page 3

... Peak Regulation Convection Cooling Load ± 5.4 A ± 4.4 A ±2% 2.5 A 2.75 A ±2% 1.25 A 1.35 A ±2% LPS54-M LPS55-M LPS58-M Line Line Line Neutral Neutral Neutral +15 V +24 V +48 V +15 V +24 V +48 V Common Common Common Common Common Common -Sense -Sense -Sense +Sense ...

Related keywords