QO112M100 SQUARE D, QO112M100 Datasheet - Page 13

CIRCUIT BREAKER, LOAD CENTER, 240V, 100A

QO112M100

Manufacturer Part Number
QO112M100
Description
CIRCUIT BREAKER, LOAD CENTER, 240V, 100A
Manufacturer
SQUARE D
Series
QOr
Datasheet

Specifications of QO112M100

Supply Voltage
240VAC
Current Rating
100A
No. Of Branch Circuits
12
External Depth
3.75"
External Height
17.92"
External Width
14.25"
Enclosure Material
Steel
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
03/2007
QO330MQ150
QO330L200G
Three-Phase, 3–42 Circuits, 60–225 A, Convertible or Fixed Mains
UL Listed
Short Circuit Current Rating
Mains
Cover
Interior
Branch Neutral Termination
QO
File E-6294
Suitable for use as service equipment
75 °C wire rating (see Technical Information on page 19)
Main lugs: up to 65,000 AIR (depends on lowest interrupting rating of
branch circuit breakers installed)
Main circuit breaker up to 225 A: 22,000 AIR standard; optional up to
65,000 AIR for 100 A to 225 A main circuit breakers
Factory-installed main lugs or main circuit breaker
Main neutral terminal located next to the phase terminals on 125 2 25 A
main circuit breaker devices
Top or bottom feed (see Technical Information on page 24)
Fully convertible from main circuit breaker to main lugs (100 225 A)
100 A maximum back-fed main QO
retaining kit PK3MB
Flush- and surface-mount covers sold separately
Flush covers have spring-loaded interior trim for automatic flush
adjustment
Positive action, easy-to-open door latch
Shielded one-piece plated copper bus on 100 2 25 A
Removable interior with single, captive mounting screw on 100 22 5 A
(indoor only)
Main lugs load centers have equipment grounding bar kits included
(not factory-installed)
Suitable for copper or aluminum wire
Terminals suitable for one #14 #4 AWG coppe r or one #12 #4 AWG
aluminum wire
Positioned on both sides of the mains compartment
Slot/square drive wire binding screws
Three (3) #14 1 /0 AWG copper or #14 # 6 AWG aluminum terminations
standard on 12 4 2 circuits, 100 22 5 A load centers
®
and Homeline
General Information and Application Data
© 2007 Schneider Electric All Rights Reserved
®
Load Centers and Enclosures
®
circuit breaker; requires the use of
13

Related parts for QO112M100