QO112M100 SQUARE D, QO112M100 Datasheet - Page 7

CIRCUIT BREAKER, LOAD CENTER, 240V, 100A

QO112M100

Manufacturer Part Number
QO112M100
Description
CIRCUIT BREAKER, LOAD CENTER, 240V, 100A
Manufacturer
SQUARE D
Series
QOr
Datasheet

Specifications of QO112M100

Supply Voltage
240VAC
Current Rating
100A
No. Of Branch Circuits
12
External Depth
3.75"
External Height
17.92"
External Width
14.25"
Enclosure Material
Steel
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
03/2007
Tandem circuit breaker mounts on rails.
Branch Circuit Breaker
Class CTL
Phasing
Line Lugs
Neutral Assemblies
QO
Class CTL load centers are UL Listed
Circuit breaker mounting rails have slots to accept tandem circuit
breakers, on specified load centers
Meets paragraph 408.35 of the 2005 National Electrical Code
Load centers have distributed phase bussing
Most branch circuit breakers can be mounted in any position
All lugs suitable for 75 °C copper or aluminum wires (see Main Lugs
and Main Circuit Breaker Ratings on page 20)
Main lugs and main circuit breaker load centers have wire binding screw
torque values on the wiring diagrams and circuit breaker labels
All lugs suitable for copper or aluminum wire (see Main Lugs and Main
Circuit Breaker Ratings on page 20)
Branch neutral terminals suitable for one #14 #4 AWG copper or one
#12 #4 AWG aluminum wire
Three #14 1/0 AWG copper or #14 #6 AWG aluminum terminals
provided on 12 42 circuits, 100 225 A load centers
Suitable lugs provided on the neutrals for termination of the grounding
conductor
All unused neutral terminals may be used to terminate bare or green
equipment grounding conductors when the load center is used as
service equipment:
one or two #14 # 12 AWG copper
one or two #12 # 10 AWG aluminum
®
and Homeline
Neutral assemblies accept copper or aluminum wire.
General Information and Application Data
© 2007 Schneider Electric All Rights Reserved
®