PR11-2-10.0A-XX-V AIRPAX, PR11-2-10.0A-XX-V Datasheet - Page 12

CIRCUIT BREAKER, HYD-MAG, 1P, 250V, 10A

PR11-2-10.0A-XX-V

Manufacturer Part Number
PR11-2-10.0A-XX-V
Description
CIRCUIT BREAKER, HYD-MAG, 1P, 250V, 10A
Manufacturer
AIRPAX
Series
PRr
Datasheet

Specifications of PR11-2-10.0A-XX-V

Input Voltage Vac
250V
No. Of Poles
1
Current Rating
10A
Interrupting Capacity
500A
Dielectric Strength
1.5kV
Trip Time
15s
Voltage Rating Vdc
32V
Leaded Process Compatible
Yes
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
71
General notes:
All supplementary protectors are of the overcurrent (OC) type
The family of protectors has been evaluated for end use application for use group (UG) A
The terminals (FW) are suitable for factory wiring only (0)
The maximum voltage ratings for which the protectors have been tested are shown in the chart
The current is the amperage range that the protectors have been tested
The tripping current (TC) for the protectors is either “1” (in the range of 125% to 135% of ampere rating) or “2” (more
than 135% of ampere rating)
The overload rating (OL) – designates whether the protector has been tested for general use or motor starting applica-
tions.
0 – tested at 1.5 times amp rating for general use
1 – tested at 6 times AC rating or 10 times DC rating for motor starting
The short circuit current rating (SC) – The short circuit rating in amperes following a letter and number designating the
test conditions and any calibration following the short circuit test is defined below:
Voltage
32
38
65
65
65
65(2)
65(2)
65(2)
125
125
125(2)
125(2)
120/240
120/240
125/250
250
250
250
250(2)
125
125/250
250
250
CR/CPP/CPR COMMUNiCATiONS EqUiPMENT CiRCUiT BREAKERS
65
80
(1) Non-standard construction. “Fit For Further Use” approval; (2) Non-snap action design; (3) No auxiliary switch available above 20A; (4) With 30A max. series fuse
AGENCY APPROVAlS (T/P/PP/PR SUPPlEMENTARY PROTECTORS)
AUxIlIARY SWITCH RATING
Silver
Gold
APPROxIMATE WEIGHT PER POlE
.100 amps
3.0 amps
1.5 amps
Rocker Configuration
Toggle, PP, PR
SNAPAK® Series - Specifications
Frequency (Hz)
DC
DC
DC
DC
DC
DC
DC
DC
50/60
50/60
50/60
50/60
50/60
50/60
50/60
50/60
50/60
50/60
50/60
400
400
400
400
DC
DC
Voltage (Volts), Frequency (hz), Phase, Min Poles, TC, Ol
@
@
@
120 VAC
Ounces
32 VAC
–––
0.9
1.2
Phase
-
-
-
-
-
-
-
-
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
-
-
32 VDC
32VDC
Grams
–––
25
32
Min. Poles
1
1
1
2
2
1
2 only
2
1
1
1
1
2
2
2
1
1
2
2
1
2
2
1
1 only
1 only
TC
1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
2
1
2
1
2
2
2
2
-
-
C – indicates short circuit test was conducted with series overcurrent protection
U – indicates short circuit test was conducted without series overcurrent protection
1 – indicates a recalibration was not conducted as part of the short circuit testing
2 – indicates a recalibration was performed as part of the short circuit testing
3 – indicates recalibration was performed along with the dielectric and voltage withstand for “Suitable for Further
Use” rating
Short Circuit interrupting Capacity
1000 amperes maximum for UL and CSA, 500 amperes maximum for VDE. Consult factory for details.
Handle and Body Material
The handle and upper body material is polycarbonate and the lower body is PET.
Chemical Resistance
Handle and case may be cleaned with detergents or alcohols and should be restricted to outside surfaces only.
Organic solvents are not recommended. Special attention should be given when solvents are used to remove
excess flux from terminals. No oils or lubricants should be introduced into handle openings or onto bushing
threads.
iEC, UL, CSA, SEV, VDE, CCC, CE, TÜV
Recognized by UL to STD-1077 and UL certified to spacing requirements of iEC 950 for basic and functional insu-
lation for front panel mounting. Certified by CSA, file number LR26229 as recognized supplementary protectors,
SEV approved, CCC approved, TÜV approved (including screw terminals) and VDE approved to VDE 0642. VDE
approval of unmarked rocker handle option for appliance disconnect requires status of protectors to be indicated
on the panel. Only VDE approved part numbers will be marked CE compliant. See shaded areas of part number
decision tables for approved configurations and/or consult factory for exceptions and limitations.
Shock
Withstands 75G without tripping while carrying full rated current per MiL-STD-202, Method 213, Test Condition
i. instant trip breakers are tested at 80% of rated current.
Vibration
Time delayed units withstand 10G without tripping while carrying full rated current per MiL-STD-202, Method
204, Test Condition A. instant trip breakers are tested at 80% of rated current.
UL 489A Listed
The CR, CPP and CPR are dimensionally the same as the popular R, PP and PR Snapack products, but provide
UL listing to UL489A for Communications Equipment. Available only in single pole with DC trip time delays for
series or series with silver auxiliary switch configurations. As a circuit breaker, the CR, CPP or CPR provides
communication equipment manufacturers with a UL listed circuit breaker in an extremely compact package that
meets the stringent environmental requirements of today’s marketplace. This makes the CR, CPP and CPR ideal
for switching, transmission and wireless applications.
OL
0
0
0
0
0
0
0
0
0
0
0
1
0
0
0
0
0
0
1
0
0
0
0
-
-
UL/CSA
.10-30(3)
.10-15
.10-7.5
.10-15
.10-20
.10-30
.10-25
.10-25
.10-20
.10-30(3)
.10-30
.10-30
.10-20(3)
.10-30(3)
.10-20
.10-20
.10-7.5
.10-20
.10-30
.10-20
.10-20
.10-20
.10-7.5
.10-30
.10-30
Current (Amps)
VDE
.10-20
-
-
-
.10-20
.10-30
-
-
7.6-20
-
-
20.1-30
-
-
-
.1-7.5
-
.10-20
-
-
-
-
-
.10-30
.10-30
http://airpax.sensata.com/
U1, 1000
U1, 1000
U2, 1000
U3, 300(1)
U2, 1000
U1, 650
U1, 1000
U1, 500
C1, 1000(4)
U1, 1000
U3, 300
U1, 1000
U1, 1000
U1, 1000
U1, 1000
1000
600
UL 1077 & CSA
U1, 1000
U2, 1000 / U1, 1000
U2, 500 /U1, 500
U1, 1000
U2, 500 / U1, 500
U2, 120
U1, 100
U2, 500
Short Circuit Current Rating (Amps)
VDE
500
-
-
-
500
120
-
-
500
-
-
500
-
-
-
500
-
500
-
-
-
-
-
1000
600
Notes
PR only
R, PP, PR only
R only
R only
T only
R, PP, PR only
R, PP, PR only
R only