209-1-1-62-4-8-10 AIRPAX, 209-1-1-62-4-8-10 Datasheet

CIRCUIT BREAKER, HYD-MAG, 1P, 240V, 10A

209-1-1-62-4-8-10

Manufacturer Part Number
209-1-1-62-4-8-10
Description
CIRCUIT BREAKER, HYD-MAG, 1P, 240V, 10A
Manufacturer
AIRPAX
Series
209r
Datasheet

Specifications of 209-1-1-62-4-8-10

Input Voltage Vac
240V
No. Of Poles
1
Current Rating
10A
Interrupting Capacity
5kA
Trip Time
18s
Voltage Rating Vdc
0V
Trip Time Max
18sec
Trip Time Min
2sec
Mounting Type
Panel
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Introduction
249 Power Selector System
Multi-Pole
Configurations
Operating Characteristics
Delay Curves
Specifications
Decision Tables
|
|
|
|
|
|
|
|
165
167
169
171
173
174
177
179
209/219/229/249/279 Series
Magnetic Circuit Protectors

Related parts for 209-1-1-62-4-8-10

209-1-1-62-4-8-10 Summary of contents

Page 1

... Introduction 249 Power Selector System Multi-Pole Configurations Operating Characteristics Delay Curves Specifications Decision Tables 209/219/229/249/279 Series Magnetic Circuit Protectors 165 | 167 | | 169 | 171 173 | 174 | | 177 | 179 ...

Page 2

... The unit is ideal for branch circuit applications such as EDP, air conditioners, panel boards and lighting controls. The 209 is actually a family of circuit breakers available in one through six pole assemblies with a variety of configurations and terminal styles to meet your application needs. First in this family is the 209, a general purpose E-Frame circuit breaker which complies with UL Standard 489 ...

Page 3

... MAGNETIC CIRCUIT PROTECTORS Terminal Style 209 E-Frame circuit breakers may be specified with either screw terminals, stud or solderless connectors. A choice of front or back connected terminal styles is available. The back connected terminal style is available with stud terminals only. Front terminal style is available with either screw terminals or solderless connectors ...

Page 4

... Series - 249 Power Selector Breaker System Trip Time Delay Three inverse time delays are available to permit close coor- dination with various loads. Delays 51 and 61 are short delays for electronic loads ...

Page 5

... MAX. .530 [13.46] +.015 -.005 2.250 +0.38 [57.15] -0.13 1.125 [28.58 1 Screw Terminals DIMENSIONS Number of Poles 209/219/229/249/279 Series - 249 Power Selector Breaker System .125 .200 (TYP.) [3.18] [5.08] .485 [12.32] 5.800 [147.32] 2.156 4.844 [54.76] [123.04] 2.375 [60.32] 4.750 [120 ...

Page 6

... MM ISO THD. OPTIONAL 1 Screw Terminals .390 [9.91] 169 209/219/229/249/279 Series - 209/219/229 Multi-Pole Three Phase, Four Pole Includes Control Protector Remote shutdown of equipment is sometimes necessary or desirable in today’s sophisticated equipment. The 219 four pole assembly fills this need for three phase operation. Three of the four poles are designed for the circuit’ ...

Page 7

... Caution: Elongation of mounting holes may be necessary for units with more than 6 poles and units poles due to tolerance compounding http://airpax.sensata.com/ DIMENSIONS Number of Poles Width 1 1.026 ± .010 [26.06 ± .254] 2 2.072 [52.63] Max 3 3.108 [78.94] Max 4 4.144 [105.26] Max 5 5.180 [131.57] Max 6 6.216 [157.89] Max 209/219/229/249/279 Series - 209/219/229 Multi-Pole 170 ...

Page 8

... Maximum short circuit interrupting current is 5000 amperes. The 279 series available only in a series trip configuration. Please consult Sensata for specific application details. 171 209/219/229/249/279 Series - 229D (Marine) / 279 (Communications) 209/219/229 CONFIGURATIONS Series Trip The most popular configuration for magnetic protectors is the series trip, where the sensing coil and contacts are in series with the load being protected ...

Page 9

... SEE NOTE A 3.550 [90.17] 1.250 [31.75] .750 [19.05] .190 [4.83] 209/219/229/249/279 Series - Configurations LINE LOAD RELAY RELAY LINE COIL COIL LOAD Relay Trip Dual Coil LINE LOAD SHUNT LINE V. COIL Shunt Trip LOAD ...

Page 10

... No Trip . Trip 12 to 100 66 No Trip 70 to 800 Notes: *279 is available only with DC delays 173 209/219/229/249/279 Series - Operating Characteristics INRUSH PULSE TOLERANCE Delay 61, 62, 63 64, 65, 66 Note: These limits do not apply to dual coil and tapped coil units 150% 200% 400 ...

Page 11

... PERCENT OF RATED CURRENT 10000 1000 100 .01 .001 0 100 150 200 300 400 125 PERCENT OF RATED CURRENT 209/219/229/249/279 Series - 209/219/229 Delay Curves DELAY 61 500 600 700 800 900 1000 DELAY 62 500 600 700 800 900 1000 DELAY 63 500 600 700 800 ...

Page 12

... Series - Delay Curves 209/219/229/279 DELAy CURVES 60Hz Delay Curves (typ) 10000 1000 DELAY 64 100 .01 .001 0 100 150 200 300 400 500 600 125 PERCENT OF RATED CURRENT 10000 1000 100 .01 .001 0 100 150 200 300 400 500 600 125 PERCENT OF RATED CURRENT ...

Page 13

... PERCENT OF RATED CURRENT http://airpax.sensata.com/ DELAY 51 700 800 900 1000 DELAY 52 700 800 900 1000 DELAY 53 700 800 900 1000 209/219/229/249/279 Series - 209/219/229 Delay Curves 400Hz Delay Curves(typ) 10000 1000 DELAY 41 100 .01 .001 0 100 150 200 300 400 500 600 ...

Page 14

... DC ratings only, 0.1 to 100 amperes. Voltage Ratings On 209/219/229, voltages up to and including 240Vac, 50/60Hz or 400Hz, or 125Vdc are available. Multi-pole units can be supplied for 277Vac/480Vac, 50/60Hz. 279 types are available with a voltage of 160Vdc. All units will be marked with the standard maximum voltage ...

Page 15

... UL/CSA VDE UL1077 & CSA VDE 1 .10-100 - U1, 5000 - 1 .10-100 - U1, 5000 - - - .10-100 - 4000 - - .10-100 - 4000 209/219/229/249/279 Series - Agency Approvals Rated Current (Amps) Interrupting Capacity (Amps) Frequency (Hz) Min. Poles UL VDE UL 508 DC 1 .10-100 .10-100 5000 50/60 2 .10-100 - 5000 50/60 2 .10-100 - 10000 50/60 1 .10-100 ...

Page 16

... DECISION TABLES How to Order The ordering code for 209, E-Frame Circuit Breakers may be determined by following the steps in the decision tables shown here. The coding given permits a self-assigning part number for standard configurations. Factory part numbers are assigned to units with mixed ratings, combinations of styles or con- struction not listed in the Third Decision Table, etc ...

Page 17

Terminal -1 Solderless connector -2 Solderless connector -2C Solderless connector -3 10-32 screw (100 amps max.) -3C 10-32 screw (100 amps max.) † -4 10-32 screw (50 amps max.) -5 10-32 screw (50 amps max.) -5C 10-32 screw (50 ...

Page 18

... Series - 249 Decision Tables 249 POWER SELECTOR BREAkER SySTEM DECISION TABLES How to Order To evolve a convenient ordering system for most applications, the following code has been developed system is required which is not covered below, please consult factory or describe in detail. The number shown as an example describes a 120 volt, three section system, such as may be used on a boat with a port and starboard shore power receptacle and an AC generator ...

Page 19

... This document is generated from the AIRPAX™ full-line catalog #2455005000 printed in USA, January 2011 BUSINESS CENTERS Sensata Technologies 807 Woods Road Cambridge, MD 21613, USA Phone: +1 410-228-1500 Brands: Airpax™ Sensata Technologies Inc. 529 Pleasant Street Attleboro, MA 02703, USA Phone: +1 508-236-3287 Brands: klixon™, Sensata Technologies™ ...

Page 20

... This document is generated from the AIRPAX™ full-line catalog #2455005000 printed in USA, January 2011 BUSINeSS CeNTeRS Sensata Technologies 807 Woods Road Cambridge, MD 21613, UsA phone: +1 410-228-1500 Brands: Airpax™ Sensata Technologies Inc. 529 Pleasant Street Attleboro, MA 02703, UsA phone: +1 508-236-3287 Brands: Klixon™, sensata technologies™ ...