HDL36100 SQUARE D, HDL36100 Datasheet - Page 26

CIRCUIT BREAKER, THERMAL MAG, 3P, 100A

HDL36100

Manufacturer Part Number
HDL36100
Description
CIRCUIT BREAKER, THERMAL MAG, 3P, 100A
Manufacturer
SQUARE D
Series
PowerPactr
Type
Standardr
Datasheets

Specifications of HDL36100

Actuator Style
Toggle
No. Of Poles
3
Current Rating
100A
Voltage Rating Vdc
250V
Voltage Rating Vac
600V
Mounting Type
DIN Rail
Terminals
Lug
Actuator Type
Handle
Brand/series
HD Series
Characteristic
Adjustable Trip
Dimensions
6.40 (H) × 4.12 (W) × 4.36 (D) in.
Frame Type
H
Number Of Poles
3
Terminal Type
Line: Lug - Load: Lug
Voltage Rating
600/250 VAC/DC
Weight
5.00 lbs.
Wire Size
#14-3/0 AWG (Al/Cu)
Ampere Interrupting Ratings
25 k @ 240 VAC, 18k @ 480 VAC
Standards
UL489, CSA, NOM, IEC 60947, CE
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
26
PowerPact
Section 2—Mounting and Connections
Section 2—Mounting and Connections
06/2010
®
H- and J-Frame Circuit Breakers
Table 30:
1
Unit-Mount Circuit Breakers
The standard lugs can be removed for the installation of compression-type lugs or bus connections. All
lugs are UL Listed for their proper application and marked for use with aluminum and copper (Al/Cu) or
copper only (Cu) conductors. Lugs suitable for copper and aluminum conductors are made of tin-
plated aluminum.
Mounting
H- and J-frame circuit breakers may be mounted vertically, horizontally or flat on their back without any
derating of characteristics.
Fixed-mounted H- and J-frame individually-mounted circuit breakers are supplied with two mounting
screws. These mounting screws are inserted through mounting holes molded into the circuit breaker
case and threaded into the mounting enclosure, rails or through the panel door for flush mounting.
A DIN rail mounting bracket (catalog no. S29305) is available for the H- and J-frame circuit breakers .
NOTE: DIN rail mounting is not compatible with motor operated applications.
Figure 6:
Circuit Breaker Construction
Connections
H-Frame
J-Frame
Including rail, backplate, and flush mounting
Mounting on Rails
Circuit Breaker Mounting and Connections
Unit-Mounting Options
Mounting on Backplate
Lug-Lug
X
X
Unit Mount
Rear
X
X
Flush Mounting
1
Bus Bar
X
X
© 2004–2010 Schneider Electric
I-Line
All Rights Reserved
X
X
®
Drawout
X
X

Related parts for HDL36100