HDL36100 SQUARE D, HDL36100 Datasheet - Page 33

CIRCUIT BREAKER, THERMAL MAG, 3P, 100A

HDL36100

Manufacturer Part Number
HDL36100
Description
CIRCUIT BREAKER, THERMAL MAG, 3P, 100A
Manufacturer
SQUARE D
Series
PowerPactr
Type
Standardr
Datasheets

Specifications of HDL36100

Actuator Style
Toggle
No. Of Poles
3
Current Rating
100A
Voltage Rating Vdc
250V
Voltage Rating Vac
600V
Mounting Type
DIN Rail
Terminals
Lug
Actuator Type
Handle
Brand/series
HD Series
Characteristic
Adjustable Trip
Dimensions
6.40 (H) × 4.12 (W) × 4.36 (D) in.
Frame Type
H
Number Of Poles
3
Terminal Type
Line: Lug - Load: Lug
Voltage Rating
600/250 VAC/DC
Weight
5.00 lbs.
Wire Size
#14-3/0 AWG (Al/Cu)
Ampere Interrupting Ratings
25 k @ 240 VAC, 18k @ 480 VAC
Standards
UL489, CSA, NOM, IEC 60947, CE
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Toggle Escutcheon
© 2004–2010 Schneider Electric
All Rights Reserved
pu sh
to
trip
Drawout Circuit Breaker Mounting
The drawout-mounted chassis is Listed under UL file E113555 and Certified under CSA file LR69561.
The chassis is made up of two side plates installed on the base and two other plates mounted on the
circuit breaker.
Figure 9:
Table 41:
Table 42:
Chassis Functions
All functions of the plug-in base, plus:
Description
Kit for PowerPact J- and H-Frame Circuit Breaker (Stationary and Moving Part) N
Consisting of:
Description
Secondary
Disconnecting
Blocks
Shutters
Chassis
Accessories
Disconnected position: the power circuit is disconnected, the circuit breaker is simply “withdrawn”
and may still be operated (ON (I), OFF (O), push-to-trip)
Circuit breaker may be locked using one to three padlocks–padlock diameters 0.19–0.31 in.
(5–8 mm)
Drawout Mounting Positions
Drawout Mounting
Plug-In and Drawout Accessories
Fixed Part
Moving Part
Two Shutters for Plug-In Base
Extended Escutcheon for Toggle
(For circuit breakers with toggle through front panel, intended to maintain the
degree of protection whatever the position of the circuit breaker. Supplied with a
toggle extension.)
Locking Device (Key Lock is Not Included)
Two Position Indicating Switches (Connected/Disconnected)
(Circuit breaker position switches may be applied on the fixed part of the
chassis, indicating the “connected” and “disconnected” positions.)
Stationary Part
Moving Part
Plug-In Base
Fixed Part of Chassis
Moving Part of Chassis
Short Terminal Covers
Safety Trip Interlock
Power Connections
Connected
9-Wire Connector
9-Wire Connector
Support for 2 Moving Connectors
PowerPact
Disconnected
Section 2—Mounting and Connections
®
H- and J-Frame Circuit Breakers
Suffix
HJ00
Catalog No.
29278
29321
29270
29268 (3)
29303
29282
29283
Removed
Catalog No.
29273
29274
29275
29271
29284
29286
29287
06/2010
33