CNTL 750VA 380, 277, 208-120X2
Manufacturer
HAMMOND POWER SOLUTIONS
Type
Controlr
Datasheet

Specifications of PH750MGJ

Brand/series
Imperator™ Series
Configuration
Encapsulated
Current, Secondary
6.25/3.13 A
Dimensions
6.81"L×5.25"W×4.94"H
Frequency
50/60 Hz
Mounting Hole Centers
4.5, 4.44 "
Number Of Outlets
2
Phase
1
Power, Rating
750 VA
Standards
cULus, CE
Temperature, Operating
+80 °C
Termination
Screw Terminals
Voltage, Primary
380/277/208 VAC
Voltage, Secondary
120/240 VAC
Hammond Power Solutions Inc.
Key features:
1
2
For more information, click one of the links below:
special voltage and VA sizes available upon request
excluding PH750PH, PH1000PG, PH750MLI, PH1000MLI
600V class, machine tool rated industrial control transformers
11 standard multi primary and secondary voltage groups available
50/60 Hertz
VA range from up to 50 to 5000
Standard SEMS washers - supplied on all units up to and including 1500VA
UL listed
CE Mark standard onall molded units up to and including 1500VA
RoHS compliant
LIFETIME Warranty
HPS Imperator Brochure (ENCCON Control Brochure)
HPS Imperator Catalog Information (HTP-08 Catalog Sec. 1)
HPS Imperator Wiring Instructions (PHWD1-2 Wiring Instructions)
HPS Imperator Wiring Instructions - French (PHWD1-2 Wiring Instructions)
HPS Imperator Typical Specification (SPS 19, Rev 01)
(60Hz on PH***AJ & PH***AR
(Limited)
The HPS Imperator
designed to meet high inrush industrial applications where electromagnetic components such as
relays, solenoids and magnetic motor starters are used.
With 11 standard voltage groups, a VA range from 50VA to 5000VA and available with standard
secondary and optional primary fuse kits, the HPS Imperator
for any application.
The HPS Imperator's unique terminal block design (patent pending) allows for the quick and easy
installation of standard secondary or optional primary13/32" x 1 1/2" midget/type CC fuse clips on
every unit. This is the simplest and most inexpensive fusing installation provided on any industrial
control transformer in the market today.
1
©2008 Hammond Power Solutions Inc. All Rights Reserved
)
TM
series of machine tool rated industrial control transformers are specifcally
Machine Tool Industrial Control Transformers
1
2
TM
series provides the perfect solution
Page 1 of 1

Related parts for PH750MGJ

PH750MGJ Summary of contents

Page 1

... VA sizes available upon request 2 excluding PH750PH, PH1000PG, PH750MLI, PH1000MLI Machine Tool Industrial Control Transformers series of machine tool rated industrial control transformers are specifcally ©2008 Hammond Power Solutions Inc. All Rights Reserved series provides the perfect solution TM 2 Page ...

Page 2

... CE Mark standard on all molded units up to and including 1500VA (excluding PH***AJ & PH***AR) • LIFETIME Warranty (Limited) • RoHS Compliant 1 special voltages and VA sizes available upon request 2 excluding PH750PG, PH1000PG, PH750MLI, PH1000MLI © Hammond Power Solutions Inc. & B ENEFITS 1 encased in a custom injection 34 TM HPS IMPERATOR 1 ...

Page 3

... Optional removable fi nger safe terminal covers available on all units up to and including 1500VA. © Hammond Power Solutions Inc. C ONTINUED Standard secondary and optional primary fuse kits utilizing 13/32” 1/2” midget/type CC fuse clips provide an economical solution to your fusing requirements (fuses not available) ...

Page 4

... PH350MGJ B 2.92/1.46 500 PH500MGJ B 4.17/2.08 750 PH750MGJ B 6.25/3.13 1000 PH1000MGJ B 8.33/4.17 Secondary fuse clips, fuse clip mounting screws and primary and secondary voltage links/jumpers supplied with transformers up to and including 1000VA. Refer to page 62 for wiring schematic drawings. Special voltages and VA sizes available upon request. ...