FN284B-4-06 Schaffner EMC Inc, FN284B-4-06 Datasheet

POWER ENTRY MODULE

FN284B-4-06

Manufacturer Part Number
FN284B-4-06
Description
POWER ENTRY MODULE
Manufacturer
Schaffner EMC Inc
Series
FN280r
Type
IEC 320-C16 (Male Pins)r
Datasheet

Specifications of FN284B-4-06

Gender
Plug
Voltage Rating
250VAC
Current Rating
4A
Connector Mounting
Panel
Contact Termination
Quick Connect
Leakage Current Max
2µA
Connector Type
Medical Filtered / Fused Power Entry
Current
4A
Features
Fuse Holder, Switch On/Off Non-Illuminated
Filter Type
Medical
Fuse Drawer
Included
Mounting Type
Panel Mount, Screw Hole
Termination Style
Quick Connect - .250" (6.3mm)
Voltage
250VAC
Filtered
Yes
Product
Modules
Mounting Style
Flange
Operating Temperature Range
- 25 C to + 85 C
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
294-925
817-1109
FN 284B- 4 -06

Available stocks

Company
Part Number
Manufacturer
Quantity
Price
Part Number:
FN284B-4-06
Manufacturer:
Schaffner EMC Inc
Quantity:
135
Technical specifications
Maximum continuous operating voltage:
Operating frequency:
Rated currents:
High potential test voltage:
Protection category:
Temperature range (operation and storage):
Design corresponding to:
Flammability corresponding to:
MTBF @ 40°C/230V (Mil-HB-217F):
Fuse holder:
Marking:
Rocker switch description:
Function:
Electrical specifications:
Mechanical life:
Switch ratings:
USA (UL) and Canada (C-UL):
Europe (ENEC):
*
The FN 280 power entry module combines
an IEC inlet, a mains filter with single or dual-
fuse holder and a 2-pole rocker switch in a
small form factor. Choosing FN 280 product
line brings you the rapid availability of a
standard filter associated with the necessary
safety acceptances. Standard IEC connector
filters are a practical solution helping you to
pass EMI system approval in a short time.
A wide selection on amperage ratings, fuse
options, mounting possibilities and filters for
medical applications are designed to offer
you the desired solution.
Compact filtered power entry module
Value in () relates to the inductive current charge: cos g = 0.65
n
n
n
n
n
n
250VAC, 50/60Hz
50 to 400Hz
1 to 10A @ 40°C max.
P –> E 2000VAC for 2 sec (standard types)
P –> E 2500VAC for 2 sec (B types)
P –> N 760VAC for 2 sec
IP40 according to IEC 60529
-25°C to +85°C (25/85/21)
UL 1283, CSA 22.2 No. 8 1986, IEC/EN 60939
UL 94V-2 or better
1,500,000 hours
1 or 2 fuses (Ø5 x 20mm)
2-pole, dark not illuminated
Marking I - 0
Inrush current 82A
6,000 on-off operations according to UL 1054, TV 5
10,000 on-off operations according to ENEC
50,000 cycles
10A, 125VAC; 10A, 250VAC; 1/3HP
10A (4A), 250VAC*
Features and benefits
n
n
n
n
n
Rated currents up to 10A
Single or dual-fuse holder
Fuses Ø5 x 20mm
2-pole rocker switch
General purpose application
Optional earth line choke (E type)
High conducted attenuation performance,
based on chokes with high saturation
resistance and excellent thermal behavior.
Rear/front or snap-in mounting.
Single or dual-fuse holder.
2-pole rocker switch.
Custom-specific versions are available on
request.
max. 250V ~ (text is print. below fuse symbol)
IEC inlet filters
FN 280
Approvals
Typical electrical schematic
Standard types
N
E
P
E types
N
E
P
Typical applications
n
n
n
n
n
n
Line
Line
Portable electrical and electronic
equipment
Consumer goods
EDP and office equipment
Single-phase power supplies, switch-mode
power supplies
Test and measurement equipment
Medical equipment
Cx
Cx
R
R
2xL1
2xL1
L2
2xCy
2xCy
Load
Load
N‘
E‘
P‘
N‘
E‘
P‘

Related parts for FN284B-4-06

FN284B-4-06 Summary of contents

Page 1

Compact filtered power entry module Technical specifications Maximum continuous operating voltage: Operating frequency: Rated currents: High potential test voltage: Protection category: Temperature range (operation and storage): Design corresponding to: Flammability corresponding to: MTBF @ 40°C/230V (Mil-HB-217F): Fuse holder: Marking: Rocker ...

Page 2

Components > FN 280 Filter selection table Filter Rated current Leakage current* @ 40°C (25°C) @ 230VAC/50Hz [A] FN 281-1-06 1 (1.2) FN 281-2-06 2 (2.4) FN 281-4-06 4 (4.8) FN 281-6-06 6 (7.2) FN 281-10-06 10 (11.6) FN ...

Page 3

Components > FN 280 Product selector FN 28xx-yy-zz 06: Faston 6.3 x 0.8mm (spade/soldering 10: Rated current Blank: Standard version E: Optional earth line choke B: Medical version (with bleed resistor and without Y2-capacitor) 1: Flange mounting ...

Page 4

Components > FN 280 Mechanical data FN 281 / FN 282 A 6 285 / FN 286 A 6 ...

Related keywords