R25060-2SR Cooper/Bussmann, R25060-2SR Datasheet

R25060-2SR

Manufacturer Part Number
R25060-2SR
Description
Manufacturer
Cooper/Bussmann
Datasheet

Specifications of R25060-2SR

Product Height (mm)
Not Requiredmm
Product Depth (mm)
Not Requiredmm
Lead Free Status / RoHS Status
Compliant
Catalog Symbol: LPN-RK_SP (non-indicating version)
Ratings:
Volts – 250Vac/dc (70-600A)
Agency Information:
CE, UL Listed–Special Purpose*, Guide JFHR, File E56412
CSA Certified, (200kA IR) Class 1422-02, File 53787,
Class RK1 per CSA C22.2 No. 248.12
* Meets all performance requirements of UL Standard 248-12 for Class RK1 fuses.
Catalog Numbers - Non-indicating versions
LPN-RK-70SP
LPN-RK-80SP
LPN-RK-90SP
LPN-RK-100SP
LPN-RK-110SP
LPN-RK-125SP
Carton Quantity and Weight
Ampere
Ratings
70–100
110–200
225–400
450–600
**Weight per carton.
0310 BU-SB08916
Catalog Numbers - Indicating versions
LPN-RK-70SPI
LPN-RK-80SPI
LPN-RK-90SPI
LPN-RK-100SPI
LPN-RK-110SPI
LPN-RK-125SPI
Low-Peak
Indicating & Non-indicating Class RK1 – 250 Volt 70-600 Amps
LPN-RK_SPI & LPN-RK_SP Series
IR – Vac: 300kA RMS Sym.
– Vdc: 100kA
®
Carton
Dual-Element, Time-Delay Fuses
LPN-RK_SPI (indicating version)
Qty.
5
1
1
1
LPN-RK-150SP
LPN-RK-175SP
LPN-RK-200SP
LPN-RK-225SP
LPN-RK-250SP
LPN-RK-300SP
LPN-RK-150SPI
LPN-RK-175SPI
LPN-RK-200SPI
LPN-RK-225SPI
LPN-RK-250SPI
LPN-RK-300SPI
Lbs.
1.9
0.9
2.0
3.0
Weight**
LPN-RK-350SP
LPN-RK-400SP
LPN-RK-450SP
LPN-RK-500SP
LPN-RK-600SP
LPN-RK-350SPI
LPN-RK-400SPI
LPN-RK-450SPI
LPN-RK-500SPI
LPN-RK-600SPI
Kg.
0.9
0.4
0.9
1.4
Dimensions - in
Features:
• Current-limiting for maximum short-circuit protection.
• Type 2 “No Damage” protection for IEC and NEMA starters
• High in-rush current motor protection.
• Time-delay that permits 130% FLA sizing for back-up motor
• Provides protection against single-phase motor damage.
• Low watt loss power consumption.
• Electrically isolated end caps.
• 250Vdc, UL Listed, CSA Certified.
Applications:
• Branch distribution
• Motors
• Transformers
• Solenoids
• General purpose circuits
Fuse Reducers For Class R Fuses
Equipment
Fuse Clips
200A
400A
600A
***Reducer 2621-R does not apply to 70 through 100 amp Low-Peak fuses.
****Single reducer only (pair not required).
For additional information on Class R fuse reducers, see Data Sheet 1118.
Amp Ratings
when properly sized.
protection.
Page 1 of 2
110-200
225-400
450-600
70-100
Fuse (Case)
A
Desired
10.38 (± 0.094)
100A
100A
200A
100A
200A
400A
Size
5.88 (± 0.062)
7.13 (± 0.062)
8.63 (± 0.094)
Data Sheet 1004
Recommended fuseblocks for
Class R 250V fuses
See Data Sheet: 1110
“A”
Catalog Number
No. 2621-R***
No. 2641-R
No. 642-R
No. 2661-R
No. 2662-R
No. 2664-R****
1.10 (± 0.020)
1.61 (± 0.020)
2.36 (± 0.020)
2.88 (± 0.020)
B
(Pairs)
600V
“B”

Related parts for R25060-2SR

R25060-2SR Summary of contents

Page 1

... Features: • Current-limiting for maximum short-circuit protection. • Type 2 “No Damage” protection for IEC and NEMA starters when properly sized. • High in-rush current motor protection. • Time-delay that permits 130% FLA sizing for back-up motor protection. • ...

Page 2

Current Limitation Curves 400,000 100,000 10,000 A 1,000 RMS SYMMETRICAL CURRENTS IN AMPS A-B=ASYMMETRICAL AVAILABLE PEAK (2.3 x SYMM RMS AMPS) Current-Limiting Effects Prosp. Let-Through Current (Apparent RMS S.C.C. Symmetrical) Versus Fuse Rating 100A 200A 5,000 2,100 3,150 10,000 2,600 ...

Related keywords