Description
SPEED DRIVE, 20HP, 230V, ATV71
Manufacturer
SQUARE D
Datasheet
Product data sheet
Characteristics
Complementary
Mar 30, 2012
Product destination
Power supply voltage limits
Power supply frequency
Power supply frequency limits
Speed range
Speed accuracy
Torque accuracy
Transient overtorque
Braking torque
ATV71HD15M3X
variable speed drive ATV71 - 15kW 20HP -
240V
Main
Range of product
Product or component
type
Product specific appli-
cation
Component name
Motor power kW
Motor power hp
Motor cable length
Power supply voltage
Network number of
phases
Line current
Assembly style
Apparent power
Prospective line Isc
Nominal output current
Maximum transient cur-
rent
Speed drive output fre-
quency
Nominal switching fre-
quency
Switching frequency
Asynchronous motor
control profile
Type of polarization
Asynchronous motors
Synchronous motors
170...264 V
50...60 Hz (- 5...5 %)
47.5...63 Hz
1...100 for asynchronous motor in open-loop mode, without speed feedback
1...1000 for asynchronous motor in closed-loop mode with encoder feedback
1...50 for synchronous motor in open-loop mode, without speed feedback
+/- 0.01 % of nominal speed for 0.2 Tn to Tn torque variation in closed-loop mode
with encoder feedback
+/- 10 % of nominal slip for 0.2 Tn to Tn torque variation without speed feedback
+/- 15 % in open-loop mode, without speed feedback
+/- 5 % in closed-loop mode with encoder feedback
170 % of nominal motor torque +/- 10 % for 60 s every 10 minutes
220 % of nominal motor torque +/- 10 % for 2 s
< 150 % with braking or hoist resistor
30 % without braking resistor
Altivar 71
Variable speed drive
Complex, high-power machines
ATV71
15 kW at 200...240 V 3 phases
20 hp at 200...240 V 3 phases
<= 50 m shielded cable
<= 100 m unshielded cable
200...240 V (- 15...10 %)
3 phases
61.6 A for 240 V 3 phases 15 kW / 20 hp
71.7 A for 200 V 3 phases 15 kW / 20 hp
With heat sink
25.6 kVA at 240 V 3 phases 15 kW / 20 hp
<= 22 kA, 3 phases
66 A at 4 kHz 230 V 3 phases 15 kW / 20 hp
109 A for 2 s 3 phases 15 kW / 20 hp
99 A for 60 s 3 phases 15 kW / 20 hp
0.1...599 Hz
4 kHz
1...16 kHz adjustable
4...16 kHz with derating factor
ENA (Energy adaptation) system for unbalanced
loads
Flux vector control (FVC) with sensor (current vec-
tor)
Sensorless flux vector control (SFVC) (voltage or
current vector)
Voltage/Frequency ratio (2 or 5 points)
No impedance for Modbus
1

Related parts for ATV71HD15M3X

ATV71HD15M3X Summary of contents

Page 1

... Power supply voltage limits Power supply frequency Power supply frequency limits Speed range Speed accuracy Torque accuracy Transient overtorque Braking torque Mar 30, 2012 ATV71HD15M3X variable speed drive ATV71 - 15kW 20HP - 240V Main Range of product Altivar 71 Product or component Variable speed drive type ...

Page 2

Synchronous motor control profile Regulation loop Motor slip compensation Diagnostic Output voltage Insulation Type of cable for mounting in an enclosure Electrical connection Tightening torque Supply Analogue input number Analogue input type Input sampling time Response time Absolute accuracy precision ...

Page 3

Acceleration and deceleration ramps Braking to standstill Protection type Insulation resistance Frequency resolution Communication port protocol Type of connector Physical interface Transmission frame Transmission rate Data format Number of addresses Method of access Marking Operating position Depth Height Width Product ...

Page 4

Environment Noise level Dielectric strength Electromagnetic compatibility Standards Product certifications Pollution degree IP degree of protection Vibration resistance Shock resistance Relative humidity Ambient air temperature for operation Ambient air temperature for storage Operating altitude RoHS EUR status RoHS EUR conformity ...

Page 5

... Dimensions with 1 Option Card (1) Dimensions 230 236 Dimensions in in 9.05 9.29 (1) Option cards: I/O extension cards, communication cards or "Controller Inside” programmable card. Dimensions with 2 Option Cards (1) Dimensions 230 259 Dimensions in in. ATV71HD15M3X G H 210 386 G H 8.26 15. 210 386 G H 8.26 15. ...

Page 6

Option cards: I/O extension cards, communication cards or "Controller Inside” programmable card 8.26 15.20 K Ø 0.31 0.23 ...

Page 7

... The protective blanking cover may vary according to the drive model (refer to the user guide). The protective blanking cover must be removed from ATV 71P•••N4Z drives when they are mounted in a dust and damp proof enclosure. Specific Recommendations for Mounting the Drive in an Enclosure Ventilation To ensure proper air circulation in the drive: ATV71HD15M3X 7 ...

Page 8

Fit ventilation grilles. ● Ensure that there is sufficient ventilation. If there is not, install a forced ventilation unit with a filter. The openings and/or fans must provide a flow rate at least equal to that of the drive ...

Page 9

... All terminals are located at the bottom of the drive. Fit interference suppressors on all inductive circuits near the drive or connected on the same circuit, such as relays, contactors, solenoid valves, fluorescent lighting, etc. Wiring Diagram Conforming to Standards EN 954-1 Category 1, IEC/EN 61508 Capacity SIL1, in Stopping Category 0 According to IEC/EN 60204-1 ATV71HD15M3X 9 ...

Page 10

Three-Phase Power Supply with Downstream Breaking via Switch Disconnector A1 ATV71 drive L1 DC choke Q1 Circuit-breaker Q2 Switch disconnector (Vario) (1) Line choke (three-phase), mandatory for ATV71HC11Y…HC63Y drives (except when a special transformer is used (12-pulse)). (2) For ATV71HC40N4 ...

Page 11

... ATV71 drive A2 Preventa XPS AC safety module for monitoring emergency stops and switches. One safety module can manage the “Power Removal” function for several drives on the same machine. In this case, each drive must connect its PWR terminal to its + 24 V via the safety contacts on the XPS  ...

Page 12

... ATV71 drive A2 Preventa XPS ATE safety module for monitoring emergency stops and switches. One safety module can manage the "Power Removal” (5) safety function for several drives on the same machine. In this case the time delay must be adjusted on the drive controlling the motor that requires the longest stopping time. In addition, each drive must connect its PWR terminal to its + 24  ...

Page 13

... Product data sheet Performance Curves Derating Curves The derating curves for the drive nominal current (In) depend on the temperature, the switching frequency and the mounting type. For intermediate temperatures (e.g. 55°C), interpolate between 2 curves. X Switching frequency (1) Mounting type ATV71HD15M3X 13 ...