ATV71HD30N4 SQUARE D, ATV71HD30N4 Datasheet - Page 11

no-image

ATV71HD30N4

Manufacturer Part Number
ATV71HD30N4
Description
SPEED DRIVE, 40HP, 460V, ATV71
Manufacturer
SQUARE D
Datasheet
Three-Phase Power Supply, Low Inertia Machine, Vertical Movement
A1
A2
F1
L1
Q1
S1
S2
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(10) There is no PO terminal on ATV71HC11Y…HC63Y drives.
(11) Optional DC choke for ATV71H•••M3, ATV71HD11M3X…HD45M3X, ATV71•075N4…•D75N4 and ATV71P•••N4Z drives. Connected in
(12) Software-configurable current (0…20 mA) or voltage (0…10 V) analog input.
(13) Reference potentiometer.
All terminals are located at the bottom of the drive. Fit interference suppressors on all inductive circuits near the drive or connected on the
same circuit, such as relays, contactors, solenoid valves, fluorescent lighting, etc.
Wiring Diagram Conforming to Standards EN 954-1 Category 3, IEC/EN 61508 Capacity SIL2, in Stopping
Category 1 According to IEC/EN 60204-1
ATV71 drive
Preventa XPS AC safety module for monitoring emergency stops and switches. One safety module can manage the “Power Removal”
function for several drives on the same machine. In this case, each drive must connect its PWR terminal to its + 24 V via the safety
contacts on the XPS AC module. These contacts are independent for each drive.
Fuse
DC choke
Circuit-breaker
Emergency stop button with 2 contacts
XB4 B or XB5 A pushbutton
Power supply: 24 Vdc or Vac, 48 Vac, 115 Vac, 230 Vac.
S2: resets XPS AC module on power-up or after an emergency stop. ESC can be used to set external starting conditions.
Requests freewheel stopping of the movement and activates the “Power Removal” safety function.
Line choke (three-phase), mandatory for and ATV71HC11Y…HC63Y drives (except when a special transformer is used (12-pulse)).
The logic output can be used to signal that the machine is in a safe stop state.
For ATV71HC40N4 drives combined with a 400 kW motor, ATV71HC50N4 and ATV71HC40Y…HC63Y, refer to the power terminal
connections diagram.
Fault relay contacts. Used for remote signalling of the drive status.
Connection of the common for the logic inputs depends on the positioning of the SW1 switch. The above diagram shows the internal
power supply switched to the “source” position (for other connection types, refer to the user guide).
Standardized coaxial cable, type RG174/U according to MIL-C17 or KX3B according to NF C 93-550, external diameter
2.54 mm /0.09 in., maximum length 15 m / 49.21 ft. The cable shielding must be earthed.
place of the strap between the PO and PA/+ terminals. For ATV71HD55M3X, HD75M3X, ATV71HD90N4…HC50N4 drives, the choke
is supplied with the drive; the customer is responsible for connecting it.
11