I/O Memory Areas
Data can be read and written to I/O memory from the ladder programs. I/O memory consists of an area for I/O with external devices, user areas,
and system areas.
Work Area (W)
Holding Area (H)
I/O Memory Areas
Name
Input Bits
CIO Area
Output Bits
Serial PLC Link Words
Work Area (W)
Holding Area (H)
E-type CPU Unit
Data Memory Area (D)
N/NA-type CPU Unit
Present values
Timer Area (T)
Timer Completion Flags
Present values
Counter Area (C)
Counter Completion Flags 256
Read only
Auxiliary Area (A)
Read-write
14
Input bits (starting from CIO 0)
User Areas
Timer Area (T)
DM Area (D)
Counter Area (C)
Output bits (starting from CIO 100)
No. of bits
Word addresses
1,600 bits (100 words)
CIO 0 to CIO 99
1,600 bits (100 words)
CIO 100 to CIO 199 For NA-type, CIO190 is occupied by analog output 0.
1,440 bits (90 words)
CIO 200 to CIO 289
1,600 bits (100 words)
W0 to W99
800 bits (50 words)
H0 to H49
2K words
D0 to D2047
8K words
D0 to D8191
256
T0 to T255
256
256
C0 to C255
7168 bits (448 words)
A0 to A447
4,896 bits (306 words)
A448 to A753
System Areas
Auxiliary Area
(A)
Condition Flags
Clock Pulses
Remarks
For NA-type, CIO90, CIO91 is occupied by analog input 0, 1.
--
--
Data in this area is retained during power interruptions if a
Battery Set (sold separately) is mounted to an N/NA-type CPU
Unit.
Data in specified words of the DM Area can be retained in the
built-in EEPROM in the backup memory by using a bit in the
Auxiliary Area.
Applicable words: D0 to D1499
(One word can be specified at a time.)
Data in specified words of the DM Area can be retained in the
built-in EEPROM in the backup memory by using a bit in the
Auxiliary Area.
Applicable words: D0 to D6999
(One word can be specified at a time.)
--
--
Data in this area is retained during power interruptions if a
Battery Set (sold separately) is mounted to an N/NA-type CPU
Unit.
--
Data in this area is retained during power interruptions if a
Battery Set (sold separately) is mounted to an N/NA-type CPU
Unit.