CP1W-MODTCP01-US Omron, CP1W-MODTCP01-US Datasheet

no-image

CP1W-MODTCP01-US

Manufacturer Part Number
CP1W-MODTCP01-US
Description
CP1 Modbus TCPIP Option Board
Manufacturer
Omron
Datasheet

Specifications of CP1W-MODTCP01-US

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Modbus/TCP Master for CP1L and CP1H Micro PLCs
Modbus/TCP Slave for CJ2M-CPU3x, CP1L and CP1H PLCs
The CP1W-MODTCP01-US allows Omron CP1L, CP1H and CJ2M-CPU3x PLCs to function as slave nodes on a
Modbus/TCP network. The adapter can function as either a Modbus/TCP Master or as a Modbus/TCP Slave, but not
both simultaneously. The Modbus/TCP Master mode is used to control/monitor IO blocks and other remote devices.
The Modbus/TCP Slave mode responds to commands from a Modbus/TCP Master such as a PC or PLC.
Key Features and Benefits
Specification
Typical Master/Slave Configuration
Item
Part #: CP1W-MODTCP01-US
Type, Max # of Modbus Slave nodes
Applicable PLCs
Max Distance, Communication Method
Max number of units mounted in PLC
Max connection/adapter - Slave mode
Max connection/adapter - Master mode
Current IP Address (Slave mode)
Default IP Address, Web Page Set-up
CP1W-MODTCP01-US
CP1 Modbus/TCP Adapter
Cat. No. P063I-E-01
CJ2M-CPU3x
Most Popular Network – Modbus/TCP/IP is the most popular remote I/O Ethernet network for PLC systems in the world
Simple setup – Web page configuration for IP Address & Master/Slave selection
Operates as a Modbus/TCP Master or Slave - As a Master, the adapter is used to control/monitor IO blocks and other remote
devices. As a Modbus/TCP Slave it responds to commands from a Modbus/TCP Master (PC, PLC, other)
Perfect for Data Collection – The CP1W- MODTCP01-US turns a CJ2M-CPU3x, CP1L/H PLC into a Modbus/TCP Slave that can
easily share information with a Modbus/TCP Master for remote data collection or control
High Speed Counters & Expandable I/O – 4 x 100Khz counters built-in, up to 320 I/O (CP1H-X) & 180 I/O (CP1L-M60) PLCs
Programmable Slave for Motion, Temperature Control – Each PLC can be a powerful motion controller* (CP1H - 4 Axis, CP1L
– 2 Axis) with high speed interrupts, Real Time Clock, PID, Floating Point Math and is expandable with digital I/O or analog for
Temperature or Process Control. The addition of a Modbus/TCP adapter turns the PLC into a Low Cost Programmable Slave
*Transistor models
Supports Multiple Connections - If the adapter is configured in Modbus/TCP slave mode, it can also support communications to
CX-Programmer, NS HMI or other devices that use FINS (Omron’s open communication protocol)
Gateway for Modbus/TCP & FINS Ethernet – Allows CS/CJ PLCs with Ethernet or EtherNet/IP to communicate using FINS
through a CP1 PLC as a Modbus/TCP Slave
Modbus/TCP Slaves can perform Motion Control, Process Control, etc.
Modbus/TCP Master
09/10
W4S Ethernet Switch
CP1H
Specifications subject to change without notice.
Description
CJ2M-CPU3x, CP1L/H - Modbus/TCP Slave or CP1L/H Modbus/TCP Master (not both simultaneously)
100Base-TX (Can be used as 10Base-T), 254 Max Slave Nodes
CP1L-L14, CP1L-L20, CP1L-M30, CP1L-M40, CP1L-M60, CP1H
100 m (distance between hub and node), Modbus/TCP/IP protocol
2 (1 Modbus/TCP Master, 1 Modbus/TCP Slave)(CP1L 30 I/O or more or CP1H)
4 – (2 Modbus/TCP connections & 2 FINS)
1 connection (CP1L, CP1H PLCs only can be set to Master Mode)
D1200, D1201 (D1200=1st & 2nd Octets in Hex, D1201=3rd & 4th Octets in Hex)
192.168.250.11 Web Page Set-up: http://192.168.250.11
CP1H
CP1H
© 2010 Omron Electronics LLC
CP1L
W4S Ethernet
Switch
CP1L

Related parts for CP1W-MODTCP01-US

CP1W-MODTCP01-US Summary of contents

Page 1

... Modbus/TCP Master for CP1L and CP1H Micro PLCs Modbus/TCP Slave for CJ2M-CPU3x, CP1L and CP1H PLCs The CP1W-MODTCP01-US allows Omron CP1L, CP1H and CJ2M-CPU3x PLCs to function as slave nodes on a Modbus/TCP network. The adapter can function as either a Modbus/TCP Master Modbus/TCP Slave, but not both simultaneously ...

Page 2

... Solar Farms Modbus/TCP Master to IP67 Slaves, etc. Modbus TCP Master Shown above is a CP1H PLC with a CP1W-MODTCP01-US adapter configured for Master mode communicating to two remote Omron IP67 Modbus TCP slaves. An Omron W4S Ethernet switch is used to connect the various Ethernet devices. ...

Related keywords