G3HD-202SN DC12-24V Omron, G3HD-202SN DC12-24V Datasheet - Page 3

Solid State Relay

G3HD-202SN DC12-24V

Manufacturer Part Number
G3HD-202SN DC12-24V
Description
Solid State Relay
Manufacturer
Omron
Series
G3HDr
Datasheet

Specifications of G3HD-202SN DC12-24V

Circuit
SPST-NO (1 Form A)
Output Type
DC
Load Current
2.5A
Voltage - Input
9.6 ~ 28.8VDC
Voltage - Load
19 ~ 264 V
Mounting Type
Socket
Termination Style
Socketable
Package / Case
Module
Control Voltage Range
19.2 VDC to 264 VDC
Load Voltage Rating
240 V
Load Current Rating
2.5 A
Output Device
Diode
Mounting Style
Socket
Relay Type
Solid State
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
On-state Resistance
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
G3HD-202SNDC12-24V
G3HD202SNDC1224V
Output
■ Characteristics
Engineering Data
Load Current vs.
Ambient Temperature
Characteristics
G3H-203SN-VD/203S-VD/203SLN-VD/
203SL-VD
G3HD-X03SN-VD/X03S-VD
G3HD-202SN-VD
G3H-203SN-VD
G3H-203S-VD
G3H-203SLN-VD
G3H-203SL-VD
G3HD-X03SN-VD
G3HD-X03S-VD
G3HD-202SN-VD
Operate time
Release time
Output ON voltage drop 1.6 V (RMS) max.
Leakage current
Insulation resistance
Dielectric strength
Vibration resistance
Shock resistance
Ambient temperature
Ambient humidity
Certified standards
EMC
Weight
2.5
1.5
−30 − 20
4
3
2
1
0
Model
Model
G3HD-202SN-VD
0
G3H-203SN-VD, G3H-203S-VD
G3H-203SLN-VD, G3H-203SL-VD
G3HD-X03SN-VD, G3HD-X03S-VD
20
100 to 240 VAC
4 to 48 VDC
24 to 240 VDC
40
Ambient temperature (°C)
G3H-203SN-VD/203S-VD G3H-203SLN-VD/203SL-VD G3HD-X03SN-VD/X03S-VD
1/2 cycle of load power
source + 1 ms max.
1/2 cycle of load power source + 1 ms max.
5 mA max. (at 100 VAC);
10 mA max. (at 200 VAC)
100 MΩ min. (at 500 VDC)
2,000 VAC, 50/60 Hz for 1 min
Destruction: 10 to 55 to 10 Hz, 0.75-mm single amplitude
Destruction: 1,000 m/s
Operating: –30°C to 80°C (with no icing)
Storage:
45% to 85%
G3H: UL508, CSA C22.2 No. 14, EN60947-4-3
G3HD: UL508, CSA C22.2 No. 14, EN60950-1
Emission: EN55011 Group 1 Class B
Immunity: EN61000-6-2
Approx. 50 g
Rated load voltage
60
80
–30°C to 100°C (with no icing)
100
2
One Cycle Surge Current: Non-repetitive
Non-repetitive (Keep the inrush current to half the rated value if it occurs repetitively.)
G3H-203SN-VD/203S-VD/203SLN-VD/
G3H-203SL-VD
75 to 264 VAC
3 to 52.8 VDC
19.2 to 264 VDC
50
40
30
20
10
0
1 ms max.
2.5 mA max. (at 100 VAC);
5 mA max. (at 200 VAC)
10
Load voltage range
30 50 100 200
Applicable load
500 1,000
Energized time (ms)
0.1 to 3 A at 40°C
0.1 to 3 A at 40°C
0.001 to 2.5 A at 40°C
0.5 ms max.
2 ms max.
5 mA max. (at 50 VDC)
1,500 VAC, 50/60 Hz for 1 min
5,000
Load current
G3HD-X03SN-VD/X03S-VD
G3HD-202SN-VD
30
28
26
24
22
20
18
16
14
12
10
8
6
4
2
0
10
20 30
G3HD-202SN-VD
45 A 60 Hz, 1 cycle
18 A (10 ms)
20 A (10 ms)
5 ms max.
10 ms max.
3 V max. (output ON-resis-
tance: 1.25 Ω max.)
0.1 mA max. (at 200 VDC)
50 70 100
G3HD-202SN-VD
Inrush current
G3H/G3HD
G3HD-X03SN-VD
G3HD-X03S-VD
200 300 500 1,000 2,000
Energized time (ms)
3

Related parts for G3HD-202SN DC12-24V