LC1K09015F7 SQUARE D, LC1K09015F7 Datasheet - Page 2

no-image

LC1K09015F7

Manufacturer Part Number
LC1K09015F7
Description
CONTACTOR 600VAC 9AMP IEC +OPTIONS
Manufacturer
SQUARE D
Datasheet
Complementary
Environment
Control circuit voltage limits
Inrush power in VA
Hold-in power consumption in VA
Heat dissipation
Auxiliary contacts type
Signalling circuit frequency
Minimum switching current
Minimum switching voltage
Non overlap distance
Insulation resistance
IP degree of protection
Protective treatment
Ambient air temperature for operation
Ambient air temperature for storage
Operating altitude
Flame retardance
Mechanical robustness
Height
Width
2
Average impedance
[Ui] rated insulation
voltage
Electrical durability
Mounting support
Standards
Product certifications
Connections - terminals
Operating time
Safety reliability level
Mechanical durability
Operating rate
0.2...0.75 Uc at <= 50 °C drop-out
0.8...1.15 Uc at <= 50 °C operational
30 VA at 20 °C
4.5 VA at 20 °C
1.3 W
Type instantaneous (1 NC)
<= 400 Hz
5 mA for signalling circuit
17 V for signalling circuit
0.5 mm
> 10 MOhm for signalling circuit
IP2x conforming to VDE 0106
TC conforming to DIN 50016
TC conforming to IEC 60068
-25...50 °C
-50...80 °C
2000 m without derating in temperature
Requirement 2 conforming to NF F 16-102
Requirement 2 conforming to NF F 16-101
V1 conforming to UL 94
Vibrations contactor opened 2 Gn, 5...300 Hz IEC 60068-2-6
Vibrations contactor closed 4 Gn, 5...300 Hz IEC 60068-2-6
Shocks contactor opened, on Z axis 10 Gn for 11 ms IEC 60068-2-27
Shocks contactor opened, on Y axis 10 Gn for 11 ms IEC 60068-2-27
Shocks contactor opened, on X axis 6 Gn for 11 ms IEC 60068-2-27
Shocks contactor closed, on Z axis 15 Gn for 11 ms IEC 60068-2-27
Shocks contactor closed, on Y axis 15 Gn for 11 ms IEC 60068-2-27
Shocks contactor closed, on X axis 10 Gn for 11 ms IEC 60068-2-27
58 mm
45 mm
3 mOhm at 50 Hz - Ith 20 A for power circuit
600 V for signalling circuit conforming to UL 508
690 V for signalling circuit conforming to IEC
60947-5-1
690 V for signalling circuit conforming to IEC
60947-4-1
690 V for power circuit conforming to IEC 60947-4-1
600 V for signalling circuit conforming to CSA 22-2
No 14
600 V for power circuit conforming to CSA 22-2 No
14
600 V for power circuit conforming to UL 508
1.3 Mcycles 9 A AC-3 at Ue <= 440 V
0.18 Mcycles 20 A AC-1 at Ue <= 440 V
Printed circuit boards
BS 5424
IEC 60947
NF C 63-110
VDE 0660
CSA
UL
Solder pins 1.5 x 0.9 mm
10...20 ms coil energisation and NO closing
10...20 ms coil de-energisation and NO opening
B10d = 20000000 cycles contactor with mechanical
load conforming to EN/ISO 13849-1
B10d = 1369863 cycles contactor with nominal load
conforming to EN/ISO 13849-1
10 Mcycles
3600 cyc/h

Related parts for LC1K09015F7