ATV32HU40N4 SQUARE D, ATV32HU40N4 Datasheet - Page 6
ATV32HU40N4
Manufacturer Part Number
ATV32HU40N4
Description
ATV32 5 HP 480V 3 PHASE
Manufacturer
SQUARE D
Datasheet
1.ATV32HU40N4.pdf
(10 pages)
Product data sheet
Connections and Schema
Connection Diagrams
Single or Three-phase Power Supply - Diagram with Line Contactor
Connection diagrams conforming to standards EN 954-1 category 1 and IEC/EN 61508 capacity SIL1, stopping category 0 in accordance
with standard IEC/EN 60204-1.
(1)
(3)
Single or Three-phase Power Supply - Diagram with Switch Disconnect
Connection diagrams conforming to standards EN 954-1 category 1 and IEC/EN 61508 capacity SIL1, stopping category 0 in accordance
with standard IEC/EN 60204-1.
(1)
(3)
Diagram with Preventa Safety Module (Safe Torque Off Function)
Connection diagrams conforming to standards EN 954-1 category 3 and IEC/EN 61508 capacity SIL2, stopping category 0 in accordance
with standard IEC/EN 60204-1.
When the emergency stop is activated, the drive power supply is cut immediately and the motor stops in freewheel, according to category 0
of standard IEC/EN 60204-1.
A contact on the Preventa XPS AC module must be inserted in the brake control circuit to engage it safely when the STO (Safe Torque Off)
safety function is activated.
6
Line choke (if used)
Fault relay contacts, for remote signaling of drive status
Line choke (if used)
Fault relay contacts, for remote signaling of drive status
ATV32HU40N4