XALD222 SQUARE D, XALD222 Datasheet

no-image

XALD222

Manufacturer Part Number
XALD222
Description
2 UNIT STATION WITH ARROWS
Manufacturer
SQUARE D
Datasheet
Product data sheet
Characteristics
Complementary
Apr 2, 2012
Cable entry
Product weight
Resistance to high pressure washer
Colour of marking
Positive opening
Operating travel
Operating force
Mechanical durability
Connections - terminals
Tightening torque
Shape of screw head
Contacts material
Short circuit protection
[Ith] conventional free air thermal current
[Ui] rated insulation voltage
[Uimp] rated impulse withstand voltage
[Ie] rated operational current
XALD222
dark grey station - white flush/black flush
pushbuttons Ø22 spring return
Main
Range of product
Product or component
type
Device short name
Product destination
Control station applica-
tion
Colour of base of en-
closure
Colour of cover
Material
Operator profile
Operators description
Control station compo-
sition
Marking location
Contacts operation
2 knock-outs for cable entry, clamping capacity: <= 14 mm
2 knock-outs for Pg 13 cable gland and ISO M20, clamping capacity: <= 12 mm
0.233 kg
7000000 Pa at 55 °C, distance: 0.1 m
Black marking when white caps
White marking when green, red or black caps
Without
2.6 mm (NO changing electrical state)
4.3 mm (total travel)
3.8 N (NO changing electrical state)
5000000 cycles
Screw clamp terminals: <= 2 x 1.5 mm² with cable end conforming to EN/IEC
60947-1
Screw clamp terminals: >= 1 x 0.22 mm² without cable end conforming to EN/IEC
60947-1
0.8...1.2 N.m conforming to EN/IEC 60947-1
Cross, Philips no 1
Cross, pozidriv No 1
Slotted, flat Ø 4 mm
Slotted, flat Ø 5.5 mm
Silver alloy (Ag/Ni)
10 A by gG cartridge fuse conforming to EN/IEC 60947-5-1
10 A conforming to EN/IEC 60947-5-1
600 V (degree of pollution: 3) conforming to EN/IEC 60947-1
6 kV conforming to EN/IEC 60947-1
AC-15, A600: Ue = 120 V Ie = 6 A conforming to EN/IEC 60947-5-1
AC-15, A600: Ue = 240 V Ie = 3 A conforming to EN/IEC 60947-5-1
AC-15, A600: Ue = 600 V Ie = 1.2 A conforming to EN/IEC 60947-5-1
DC-13, Q600: Ue = 125 V Ie = 0.55 A conforming to EN/IEC 60947-5-1
DC-13, Q600: Ue = 250 V Ie = 0.27 A conforming to EN/IEC 60947-5-1
DC-13, Q600: Ue = 600 V Ie = 0.1 A conforming to EN/IEC 60947-5-1
Harmony XALD
Complete control station
XALD
For XB5 Ø 22 mm control and signalling units
Two functions
Light grey RAL 7035
Dark grey RAL 7016
Polycarbonate
2 flush pushbuttons
White 'up arrow' 1 NO - black 'down arrow' 1 NC
1 flush pushbutton black 1 NC white down arrow
marking
1 flush pushbutton white 1 NO black up arrow mark-
ing
Marking on pushbutton
Slow-break
1

Related parts for XALD222

XALD222 Summary of contents

Page 1

... Contacts material Short circuit protection [Ith] conventional free air thermal current [Ui] rated insulation voltage [Uimp] rated impulse withstand voltage [Ie] rated operational current Apr 2, 2012 XALD222 dark grey station - white flush/black flush pushbuttons Ø22 spring return Main Range of product Harmony XALD Product or component ...

Page 2

Electrical durability Electrical reliability IEC 60947-5-4 Environment Protective treatment Ambient air temperature for storage Ambient air temperature for operation Class of protection against electric shock IP degree of protection NEMA degree of protection IK degree of protection Standards Product certifications ...

Related keywords