26
Connecting Expansion Unit and Expansion I/O Units
Up to seven Expansion Units and Expansion I/O Units can be connected when a CP1H CPU Unit is used, but the
following restrictions apply. Observe these restrictions when using the models in the shaded areas in the
following tables. A maximum total of 15 input words is allocated for Expansion Units and a maximum total of 15
output words is allocated for Expansion Units and Expansion I/O Units.
Maximum Number of CP1W/CPM1A Expansion Unit and Expansion I/O Units
Words Allocated to CP1W Expansion Units and Expansion I/O Units
Expansion
I/O Units
Analog Units
Temperature
Sensor Units
CompoBus/S
I/O Link Unit
Restrictions on the Number of CP1H Expansion Unit and I/O Unit Connections
CP1H CPU Unit
CP1L (M) CPU Units with 60, 40, or 30 Points
CP1L (L) CPU Units with 20 or 14 Points
Unit type
40 I/O points
32 outputs
20 I/O points
16 outputs
8 inputs
8 outputs
2 analog inputs,1 analog output
4 analog inputs
4 analog outputs
2 thermocouple inputs
4 thermocouple inputs
2 platinum resistance
thermometer inputs
4 platinum resistance
thermometer inputs
8 inputs and 8 outputs
CP1W-40EDR
CP1W-40EDT
CP1W-40EDT1
CP1W-32ER
CP1W-32ET
CP1W-32ET1
CP1W-20EDR1
CP1W-20EDT
CP1W-20EDT1
CP1W-16ER
CP1W-16ET
CP1W-16ET1
CP1W-8ED
CP1W-8ER
CP1W-8ET
CP1W-8ET1
CP1W-MAD11
CP1W-AD041
CP1W-DA041
CP1W-TS001
CP1W-TS002
CP1W-TS101
CP1W-TS102
CP1W-SRT21
Model
1 max.
No. of words
Input Output
2
1
1
2
4
2
4
2
4
1
Note: CP1L (L Type) CPU Units with 10 points do not support Expansion Units.
3 max.
2
4
1
2
1
1
2
4
1
7 max.
For example, the CP1W-TS002 Temperature Sensor Unit is allocated
four words per Unit, so no more than three Units can be connected (4
words x 3 Units = 12 words). It would then be possible to mount a
combination of other Units to use the remaining three input and 15
output words.
Examples of Possible Combinations
CP1H-X40DR-A
CP1W-TS002 x 3
CP1W -TS001 x 1
CP1W -20EDR1 x 1
CP1W - DA041 x 2
Total: 7 Units
Number of Units
7 Units
(Refer to restrictions below.)
4 words x 3 Units = 12 words
2 words x 1 Unit = 2 words
1 word x 1 Unit = 1 word
0 words
Total: 15 words
15 words
Input
0 words
0 words
1 word x 1 Unit = 1 word
4 words x 2 Units = 8 words
Total: 9 words
15 words
Output
• I/O Connecting Cable can be connected to any Unit from the CP1H/CP1L CPU Unit to the third Expansion Unit or
• Only one I/O Connecting Cable can be used in each CP1H or CP1L PLC.
• Even when I/O Connecting Cable is used, the above restrictions on the number of connectable CP1W/CPM1A
Up to two CJ-series Special I/O Units or CPU Bus Units can be connected by using a CP1W-EXT01 CJ Unit
Adapter. The number of Units that can be used is as described below.
Use CP1W-CN811 I/O Connecting Cable when
using CP1W/CPM1A Expansion Units and
Expansion I/O Units at the same time as a CJ
Unit Adapter. In this situation, the number of
CP1W/CPM1A Expansion Unit and Expansion
I/O Units that can be connected is subject to
the restrictions described above. Only one I/O
Connecting Cable can be used.
CP1H CPU Unit, the maximum number of Units that can be used is two CJ-series Units and seven
CP1W/CPM1A Expansion Units and Expansion I/O Units.
The current consumption for the CP1H must be no more than 2 A for 5 V and 1 A for 24 V, and the total
current consumption must be no more than 30 W.
Check the total current consumption to be sure these limits are not exceeded referring to page 29 for the
CP1H CPU Unit and CP1W Expansion Unit and Expansion I/O Unit current consumptions and to the above
table for CJ-series Unit current consumptions.
Expansion I/O Unit (i.e., the fourth Unit).
Expansion Units and Expansion I/O Units still apply.
Based on the current consumption when CJ-series Special I/O Units or CPU Bus Units are used with a
Using CP1W-CN811 I/O Connecting Cable
Using CJ-series Special I/O Units or CPU Bus Units with a CP1H CPU Unit
CJ Unit Adapter
CP1W-EXT01
Expansion: 1st Unit
7 max.
Up to two CJ-series
Special I/O Units or
CPU Bus Units can
be connected.
End Cover
Can be used.
2nd Unit
Analog
Input Units
Analog
Output Units
Analog
I/O Unit
Process
Temperature
Control Units
CompoBus/S
Master Unit
CompoNet
Master Unit
Input Units
CJ-series Special I/O Units and CPU Bus Units
Unit name
3rd Unit
CJ1W-AD081-V1
CJ1W-AD041-V1
CJ1W-DA08V
CJ1W-DA08C
CJ1W-DA041
CJ1W-DA021
CJ1W-MAD42
CJ1W-PH41U
CJ1W-AD04U
CJ1W-PTS51
CJ1W-PTS52
CJ1W-PTS15
CJ1W-PTS16
CJ1W-PDC15
CJ1W-TC001
CJ1W-TC002
CJ1W-TC003
CJ1W-TC004
CJ1W-TC101
CJ1W-TC102
CJ1W-TC103
CJ1W-TC104
CJ1W-SRM21
CJ1W-CRM21
Model
4th Unit
consumption (A)
Connecting Expansion Unit and Expansion I/O Units
0.15 A
0.40 A
Current
0.42 A
0.14 A
0.12 A
0.58 A
0.30 A
0.32 A
0.25 A
0.18 A
0.25 A
5 V
5th Unit
Cannot be used.
*
Position Control
Units
High-speed Counter
Unit
ID Sensor Units
Serial
Communications
Units
Ethernet Unit
EtherNet/IP Unit
DeviceNet Unit
Controller Link Unit
MECHATROLINK-II
Position Control Unit
MECHATROLINK-II
Motion Control Unit
FL-net Unit
Storage/Processing
Unit
The current consumption increases by 0.15 A/Adapter
when NT-AL001 Link Adapters are used, and by 0.04 A/
Converter when CJ1W-CIF11 RS-422A Converters
are used.
(For details, refer to the CJ1 Catalog (Cat. No. P052)).
Unit name
6th Unit
CJ1W-NC113
CJ1W-NC213
CJ1W-NC413
CJ1W-NC133
CJ1W-NC233
CJ1W-NC433
CJ1W-CT021
CJ1W-V680C11
CJ1W-V680C12
CJ1W-V600C11
CJ1W-V600C12
CJ1W-SCU41-V1
CJ1W-SCU21-V1
CJ1W-SCU31-V1
CJ1W-ETN21
CJ1W-EIP21
CJ1W-DRM21
CJ1W-CLK23
CJ1W-NC271
CJ1W-NC471
CJ1W-NCF71
CJ1W-NCF71-MA
CJ1W-MCH71
CJ1W-FLN22
CJ1W-SPU01-V2
Model
7th Unit
consumption (A)
(24 VDC
(24 VDC
(24 VDC
(24 VDC
0.13 A)
0.26 A)
0.12 A)
0.24 A)
Current
0.25 A
0.36 A
0.25 A
0.36 A
0.25 A
0.26 A
0.32 A
0.26 A
0.32 A
0.38 A*
0.28 A*
0.38 A
0.37 A
0.41 A
0.33 A
0.35 A
0.36 A
0.37 A
0.56 A
5 V
0.6 A
27