CP1W-20EDT Omron, CP1W-20EDT Datasheet - Page 9

no-image

CP1W-20EDT

Manufacturer Part Number
CP1W-20EDT
Description
Expansion 12 In, 8 Out NPN
Manufacturer
Omron
Datasheet

Specifications of CP1W-20EDT

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
16
CP1H/CP1L CPU Unit
(except CP1L-L10)
Serial Communications
A Standard USB Port and Two Serial Ports Enable Connecti ons and
Communications with a Wide Range of Components.
Up to two Option Boards can be mounted for RS-232C or RS-422A/485 communications. A peripheral
USB port has been added to connect to a personal computer for a total of three communications ports,
making it easy to simultaneously connect to a PT, various components (such as Inverters, Temperature
Controllers, and Smart Sensors), Serial PLC Link for linking to other PLCs, and a personal computer.
Applicable CPU Units and Functions
CP1H CPU Unit
USB cable
Serial Option Board for
up to two ports.
Personal
computer
CP1H/CP1L
CPU Unit
Devices such as OMRON
Temperature Controllers with
CompoWay/F
Smart FB Library
Serial Option Board for
up to two ports.
CP1L CPU Unit
RS-232C Option Board
CP1W-CIF01
Two option board slots can be used for either an
RS-232C or RS-422A/485 interface.
NS-series
PT
Serial PLC Links
(60, 40 or 30 Points)
CP1H/CP1L
CPU Unit
RS-422A/485 Option Board
CP1W-CIF11
(Maximum transmission
distance 50m)
Modbus-RTU Easy Master
CP1L CPU Unit
Serial Option Board for
only one port.
NV-series
PT
RS-422A/485(Isolated-type)
Option Board
CP1W-CIF12
(Maximum transmission
distance 500m)
(20 or 14 Points)
CP1H/CP1L
CPU Unit
When multiple boilers are being controlled, up to 10
words/Unit of data for settings and monitoring can
be exchanged using data links between up to nine
CP1H, CP1L, and CJ1M CPU Units. Serial PLC Links
can be used with either serial port 1 or serial port 2.
Note: Cannot be used for the CP1L-L10.
Connecting inverter speed control is made simple
using the Modbus-RTU Easy Master.
When the address, function, and data for a slave
device are preset in a fixed memory area (DM Area),
a message can be sent or received simply by turning
ON an AR Area bit (A640.00 for port 1 or A641.00 for
port 2) in the PLC.
OMRON Function Blocks are provided for operations
such as run/stop, frequency settings, and monitoring
when connected to Inverters by serial
communications, and for setting SPs and reading
PVs for Temperature Controllers.
Serial PLC Links
Modbus-RTU Easy Master
The OMRON Function Blocks provide
function blocks for communicating with
Inverters and Temperature Controllers.
Easy Communications Programming Using OMRON Function Blocks
Setting/monitoring operation
Set temperature/present
temperature
Errors
Standard Programming
Function Blocks for
CP1H/CP1L
CPU Unit
CP1H/CP1L CPU Unit
Slave
Command
Response
RS-485
PT
NS-AL002 (for NS Series)
Master
Master
Slave
Slave
No. 0
No. 7
Port 1: D32200
Port 2: D32300
Port 1: D32250
Port 2: D32350
Slave
address
(00 to F7 hex)
Slave
address
AR Area bits ON/OFF
Slave No. 0 Slave No. 7
Inverter
Temperature
Controller
Data transfer
Function
code
Master
Slave
Slave
Response
No. 0
No. 7
Function
code
Always ON
Inverter No.
Frequency
Direction
Area No.
Error
code
Number
of bytes
Start
Area
Master
Slave
Slave
to
to
to
to
No. 0
No. 7
Note: Check the version of
the inverter serial connection
OMRON Function Block
Library that can be used with
the CP1L and CP1H on page
62 before using the OMRON
Function Block Library.
(BOOL)
EN
(INT)
NodeNo
(BOOL)
Execute
(REAL)
Velocity
(INT)
Direction
(WORD)
AreaID
(INT)
AreaNo
Number
of bytes
_INV032_MoveVelocityHz
Serial Communications
NS-series PTs can also be
incorporated as slaves
(1:N NT Link connections)
to exchange data using
the NT Links with only the
master CP1H. Each is
treated as one slave node.
Data (94 bytes max.)
CommandAborted
The CJ1M can also
be connected.
Data
(93 bytes max.)
InVelocity
Inverter
(e.g., 3G3MX)
(WORD)
(BOOL)
(BOOL)
(BOOL)
(BOOL)
ErrorID
Error
ENO
D32249
D32349
D32299
D32399
Speed
coincidence
Abort
Error
Error code
17

Related parts for CP1W-20EDT