Setting the Front Panel Switches
Set the unit number of the Serial Communications Unit with the rotary switches on the front
of the Unit. Use a flat-blade screwdriver to set the numerals and symbols of the switch's set-
ting display window, as follows:
Connecting to CJ-series Serial Communications Units
CJ-series Units:
CPU Unit DM Area Settings
Write the settings directly from the Programming Device (Programming Console or CX-
Programmer) to the DM Area (Parameter Area) in the CPU Unit. After writing the settings,
enable the settings by turning ON the power again, restarting the Unit, restarting the com-
munications port, or executing the CHANGE SERIAL PORT SETUP (STUP) instruction.
The following table shows the allocated DM Area words and settings.
The allocations and settings are the same for RS-232C and RS-422A.
Note: When connecting a single Unit in a 1:N connection, set the value of @ to 1 or higher.
Reference
Allocated DM Area words
DM m + 1
DM m + 6
Port 1
DM m
CJ1W-SCU41 (Port 1 is an RS-422A port and Port 2 is an RS-232C port.)
CJ1W-SCU31 (Both ports 1 and 2 are RS-422A ports.)
To set high-speed 1:N NT Link communications from the CX-Programmer, set the baud
rate to 115,200 bps.
DM m + 10
DM m + 11
DM m + 16
Port 2
Unit number setting
Set a value between 0 and F that is different from
that of any other Units in the system.
Write value
000@
000A
8200
1:N NT Link Mode
Baud rate (high-speed)
@: Largest unit number (1 to 7) of the connected PTs. (See
note.)
Settings
m = 30000 + 100 × unit number
4-3 High-speed 1:N NT Link